New Construction / International / 2013 / 05 - Water /

Wat 03 - Water Leak Detection and Prevention

Information correct as of 19thOctober 2026. Please see kb.breeam.com for the latest compliance information.

Fire hydrants and sprinklers – Leak detection - KBCN0680

Where it is confirmed by an appropriate project team member that it is not possible to fully meet the leak detection criteria for fire hydrants or sprinklers, an alternative approach can be implemented for these systems. This must demonstrably meet the aim of the issue by detecting and alerting the building management to major water leaks.   Previous guidance - superseded on 30 May 2024 To meet BREEAM compliance, emergency systems such as fire hydrants and sprinklers need also to be covered by a leak detection system. The leak detection system must cover all mains water supply between and within the building and the ‘site boundary'.
11 Sep 2024 - Applicability to BIU V6 confirmed - QN-75509-C8H8V1
30 May 2024 - New guidance introduced to clarify that BREEAM compliance should not compromise the operation of building safety-critical systems. Applicability to NC V6 standards confirmed.

Flow control devices – Applicability - KBCN00057

The criteria are applicable to the cold water supply only and include cold taps, WCs and urinals. Any solution implemented to achieve compliance with this Issue should effectively mitigate the risk of hot-water scalding in showers, in the event that the cold water supply is shut off.
06/03/18 - Wording amended to make the guidance more outcome-driven and to account for solutions other than not providing flow-control devices on the supply pipework to shower areas.

Flow control devices – residential accommodation - KBCN0415

The credit for the specification of flow control devices in WC areas or facilities does not apply to ensuite facilities in residential areas, e.g. ensuite facilities in individual private bedrooms and a single bathroom for a collection of individual private bedrooms in halls of residence, key worker accommodation or sheltered accommodation. The credit and criteria are however applicable to buildings which have guest bedrooms with ensuite facilities, e.g. hotel rooms, and communal WC areas or facilities, e.g. communal WC facilities in hotels or hostels and care homes. In accommodation where occupancy is long-term and there is a sense of ownership of the space, flow control does not need to be assessed as the occupants are likely to detect and report leaks.
26 Oct 2023 - Applicability to BIU V6 Commercial confirmed

Flow control devices – Use of devices on individual sanitary fittings - KBCN1550

The intent of the requirement for flow control devices is to minimise the impact of undetected wastage and leaks from sanitary fittings and supply pipework. The use of flow control devices on individual sanitary fittings alone does not, therefore, fully meet this aim.

Flow control devices for multiple blocks - KBCN1186

The criteria are set to encourage isolation of the water supply to each WC block when it is not being used. If a single flow control device, for example one programmed time controller, is adequate to switch the water on at predetermined times that suit the usage patterns of more than one WC blocks or facilities, this can be used to demonstrate compliance. Please note that if only one timed controller is used for a large area/number of facilities, the assessor must justify that this is appropriate to the usage patterns within the building and confirm that multiple timers would be redundant (i.e. they would all be set to the same time).  Consideration should be given of any facilities that may be open longer than others, requiring these timers to be programmed differently in different areas. As long as the aim of the credit (‘to reduce the impact of water leaks that may otherwise go undetected’) can be achieved through the specification of an appropriate number of flow control devices, the credit may still be achieved if timers cover more than one WC area/facility to prevent minor water leaks.
14 Apr 2023 - Applicability to BIU V6 Commercial confirmed.

Flow control devices on rainwater supply for toilets - KBCN0868

Flow control devices will be required on water supplied from rainwater and serving the toilet facilities. Rainwater tanks are topped up by mains water and leaks could reduce levels of stored water and hence increase the use of mains water. The leak detection requirements apply to all relevant water systems, regardless of the water source.

Flow control on cold water supply - KBCN0417

A shut-off on the cold water supply to the whole WC facility provides a simple and effective way of reducing potential water loss. Taps which contain built in shut-off valves will not prevent any water leaks from the supply to the tap and so do not fulfil this intent. The intent of the flow control criteria is to prevent minor water leaks occurring within the pipework of WC facilities.

Leak detection – compliance principle – alternative technologies - KBCN1566

Where it can be demonstrated that alternative leak detection technologies can meet or exceed the capabilities of systems set out in the BREEAM guidance, subject to approval, these can also be considered compliant. It is the role of the Assessor and the project team to provide evidence and justification in a compliance principle query (see KBCN1555). The following alternative solutions are currently recognised:
06-Jul-2026 - Title updated for consistency. Scheme applicability updated. Principle also applied to refrigerant leak detection.

Leak detection – extent of responsibility - KBCN0688

For the credit to be awarded, all the pipework in a development that the owner/occupier has responsibility for must meet the leak detection criteria.  In situations where third party organisations place restrictions on the pipework that can be metered, the scope of works (and hence placement of a meter for the use of leak detection) will start immediately after this point.  For instance where the utility company's meter is placed midway between the boundary and the building, the scope of leak detection for BREEAM purposes will be between utility meter and the building, not to the boundary (as stated in the guidance). The scope of the BREEAM criteria is only on pipework that the owner/occupier has control over.

Leak detection – inseparable building and site boundary - KBCN0388

Where there is no distinction between the site boundary and the building; the utility meter being either located on the boundary or within the building, the leak detection criteria apply to the mains water supply within the building only. The BREEAM criteria apply to the pipework that the owner/occupier has responsibility for.  

Leak detection – recycled water use - KBCN0433

The leak detection requirements still apply to all relevant water systems where water recycling systems are specified for WCs and urinals. Recycled water should be considered as a valuable resource as it replaces potable water use and, in many instances, recycling systems will still incorporate a mains-water back up.    

Leak detection – shell-only projects - KBCN0900

For shell-only projects, where no internal plumbing works are within the scope of work and the developer is only providing a capped-off water supply, it is acceptable to demonstrate compliance using one of the shell & core options 1-3. The assessor must also demonstrate that the developer has, within the base-build, provided the necessary infrastructure to facilitate the future installation and connection of a leak detection system which complies with criteria 1 and 2. Where the scope of the developer's work does not allow the installation of a leak detection system, the shell & core options provide a route to compliance.

Leak detection – system notification - KBCN0245

So long as the compliant system alerts the appropriate person to the leak so they are able to respond immediately, the assessor can judge if the aim of the issue is being met by a reliable, robust and fail-safe means of notification.
13-Jul-2026 - Title updated for consistency. Scheme applicability updated. Principle extended to refrigerant leak detection, allowing refrigerant leak detection systems to notify a person to initiate shutdown in line with this principle.
   

Leak detection – using a BMS - KBCN0439

A BMS can be used for leak detection if it can be shown that its integrated or add-on features meet all the requirements for a leak detection system.
07-Feb-2022 - Applicability to BIU V6C confirmed.
06-Jul-2026 - Scheme applicability updated, and applied also to refrigerant leak detection across all relevant schemes.

Leak detection between building and utilities meter - KBCN1116

For all pipework which is the responsibility of the building owner or occupier leak detection is generally required between the building and the utilities water meter. This requirement is applicable regardless of the length of the pipework. However, for campus type developments or those with multiple buildings on the same site served by common pipework, leak detection is required both within the building and externally for the length of pipework that exclusively serves that building. Where it can be demonstrated that it is not physically possible for a meter to be installed on the pipework outside the building, the requirement for leak detection between the building and the utilities meter can be considered not applicable, and the credit awarded based on the leak detection within the building.
02 Jul 2024 - Updated to account for campus type developments. Applicability to UK NC V6 and INC V6 confirmed.

Information correct as of 19thOctober 2026. Please see kb.breeam.com for the latest compliance information.