New Construction / International / 2013 / 09 - Pollution /
Pol 05 - Noise Attenuation
Information correct as of 19thOctober 2026. Please see kb.breeam.com for the latest compliance information.
Achieving a reduction in noise levels where background levels are low - KBCN1692
Where existing background levels are low, such as during night-time, there is no dispensation or flexibility that can be applied in achieving the requirements. The aim of the issue is to reduce the potential impact of noise from the assessed building to local noise-sensitive buildings. Acoustic experts have confirmed that the requirements for the background noise levels are still appropriate where existing levels are low, including where a 5dB reduction is stated within the criteria.
Campus with multiple building assessments - KBCN0597
If a campus development project has multiple building assessments being built in conjunction with each other, each building should be assessed independently. Where there are noise sensitive buildings; including any new buildings in the process of being built, the criteria requirements must still be met.
Compliant attenuated noise levels - KBCN00047
BS 4142 noise level requirements can be used to demonstrate compliance provided the best practice testing methodologies for noise attenuation outlined in BS 7445 are followed.
Extension using existing building services - KBCN0914
When assessing an extension, which is served by existing building plant, the existing plant, should be considered as contributing to the existing pre-development background noise level. Any additional plant or changes to the operation of the existing plant should be considered as a new noise source.
This Issue seeks to address any increase in background noise levels which result from the assessed development.
22/02/2018 Wording amended to clarify how existing plant should be considered
Superseded wording:
Existing building services serving a building extension have to be included in the assessment of this issue.
Issue Pol 05 is applicable to all treated buildings, even where existing building services are used for an extension building, without being upgraded. The issue assesses the impact on any nearby noise-sensitive buildings of existing and newly specified plant and the effectiveness of any fabric measures to reduce this.
International suitably qualified professionals - KBCN1266
In some issues the International NC and RFO schemes prescribe specific requirements for suitably qualified professionals. We appreciate that some countries might have different recognition schemes in place, and these might differ from the BREEAM requirements. Where this is the case, assessors should submit a technical query with appropriate information, and we will review and approve each situation on a country basis.
No external plant specified - KBCN0931
Where there is no external plant specified and the acoustician confirms that there is no significant noise source, it is acceptable for the acoustician to provide a formal statement in lieu of the noise impact assessment. All other evidence for this issue must be provided as listed in the Evidence table.
The formal statement should be produced by a 'suitably qualified acoustician' (as defined in the Relevant Definitions for this issue) and should justify this approach with reference to the specific internal plant to be installed and the proximity of any noise sensitive areas or buildings.
The statement must explain clearly how the aim of the issue is being met.
08 Jan 2026 - Applicability to UK RFO 2014 and IRFO 2015 removed - the issue is filtered out where no external plant.
Post construction noise level testing - KBCN00043
Noise level measurements do not need to be taken at the post construction stage if the acoustician has accurately modelled the noise level from the plant, using manufacturer's literature, and site measurements taken at the design stage. Any attenuation measures specified by the acoustician in their report must be confirmed as being present post construction.
If the acoustician has been unable to model the noise level accurately, post construction measurements are needed to demonstrate compliance.
Calculations and recommendations from the acoustician are relied on to be accurate and in keeping with best practice; attenuation measures are assumed to be specified and installed correctly.
Scope of issue – clarification – fixed installations - KBCN1660
The scope of this issue covers noise from external building services (or 'fixed installations' as written in the manual) serving areas
designed for human comfort.
The noise impact assessment excludes:
- Noise from process-related plant.
- Noise from emergency or back-up plant which are not used during normal operation.
Temporary power solutions in noise impact assessments - KBCN0171
Plants such as standby generators that are only used temporarily are excluded from the noise impact assessment.
Verification of measurements undertaken by non-SQA - KBCN1661
It is acceptable for individuals who do not meet the BREEAM definition of a suitably qualified acoustician (SQA) for Pol 05 to undertake the testing for this issue, provided the measurements or calculations are verified by a SQA. The SQA must review the report and confirm in writing that they have found it to:
- Represent sound industry practice
- Be appropriate given the building being assessed and scope of works proposed
- Avoid invalid, biased and exaggerated recommendations
Additionally, written confirmation from the SQA how they comply with the definition of a SQA is required.
Information correct as of 19thOctober 2026. Please see kb.breeam.com for the latest compliance information.