In-Use / USA Commercial V6 / Part 1 / 02 - Energy /
ENE 15 - Monitoring energy uses
Information correct as of 9thNovember 2026. Please see kb.breeam.com for the latest compliance information.
Clarification – percentage of end uses - KBCN1650
This percentage is measured by the energy consumption (kWh) of significant energy uses, not by the number of end uses.
Combined sub-metering – electric space / water heating and small power - KBCN00068
For bedrooms and associated spaces in:
- Multi-residential or residential institution building types (New Construction).
- Hospitality or supportive housing asset types (BREEAM In-Use).
It is acceptable for an electric space or water heating system to be combined with lighting and small power, provided that sub-metering is provided for each floor plate or other appropriate sub-division.
For these asset types, sub-metering electric heating in multiple bedrooms may be costly and technically challenging. Where occupants have individual control but are not responsible for paying the utility bills, the building manager may have little influence on their energy consumption. Therefore, sub-metering electric heating would provide little or no benefit in meeting the aim of the issue.
06-Mar-2024 - Scheme applicability extended to V6.
15-Dec-2023 - Title updated to clarify that this approach can be applied to both space heating and domestic hot water heating, where appropriate.
Combined system for heating / cooling and domestic hot water - KBCN0329
It is permissible to have combined metering for a shared on-site or district system that combines heating / cooling, and domestic hot water generation.
In all cases, justification is provided in the QA report for the combined metering, and explains why it is not technically feasible to provide separate meters.
21-Sep-2022 Applicability of KBCN added to BIU V6. Amended to include district heating and cooling networks.
Erratum – up to V6 – methodology – no default energy assumptions - KBCN1630
The scope of the issue applies only to systems with
significant energy use.
The methodology section states that the online platform will calculate
default values, and use this to indicate which systems are in scope.
This is incorrect, as default values are
not automatically calculated.
The energy use of each system will need to be manually estimated. This can be done based on:
- Typical benchmark values, and / or,
- Estimates based on the capacity of equipment, and annual equivalent full load hours of use.
Information correct as of 9thNovember 2026. Please see kb.breeam.com for the latest compliance information.