In-Use / USA Commercial V6 /
Part 2
Information correct as of 20thOctober 2026. Please see kb.breeam.com for the latest compliance information.
Acoustic sample testing approach – calculation procedure - KBCN1675
The methodology sets out a sample testing approach which can be applied to group rooms into those of similar room type or performance requirement category or construction type.
Where rooms are grouped to the same use and construction for instance, only 1 in 4 pairs of adjacent rooms would need to be tested, and the results would be representative of all similar rooms e.g. where there are 12 pairs of similar offices and 3 are tested and are compliant, all 12 would be deemed compliant (or 100%).
Therefore, it is not a requirement to test 80% of the rooms to be 80% compliant for those projects where a sampling approach can be applied.
Applicability – Management – common areas only assessment - KBCN1559
Principle
In an assessment of common areas only, building management are still responsible for the common welfare all users and for policies governing the overall asset.
Evidence
For assessments of common and tenanted areas, the scope of the manual states:
“The assessment must include evidence of a representative sample of the tenants to ensure that central management practices are in place and fully implemented in line with the assessment criteria.”
For assessments of common areas only, evidence is required from building management only.
| Issue |
Scope of issue |
| Part 2 |
| Man 01 Building user guide |
No change to the criteria or evidence requirements.
A building user guide is required regardless of scope. |
| Man 02 Management engagement and feedback |
No change to the criteria or evidence requirements.
Engagement with building users is required regardless of scope. |
| Man 03 Maintenance policies and procedures |
Applies only to core systems which serve the common areas and are maintained by the building management. This includes any core systems which also serve tenanted areas (for instance, asset-wide ventilation systems) where this cannot be separated from tenanted space. |
| Man 04 Environmental policies and procedures |
Applies to asset-wide environmental policies only.
Answer D can apply to improvement targets for common areas only, where this can be separated from tenant targets. |
| Man 05 Green lease |
Where there are tenants occupying the asset, this issue is not filtered out.
Consideration of green contracts are within the control of building management regardless of scope. |
Applicability – no occupied spaces - KBCN1551
Principle
Where:
- The scope of assessment covers no occupied spaces and,
- There is no valid way to filter credits from that issue,
Credits specifically related to occupied space are not awarded.
Outcome
The tables below show how this principle applies to affected issues.
- Y means all credits are available (unless the comments state otherwise).
Standard filtering rules still apply, so some credits can be filtered out where allowed in the criteria.
- N means all credits in the issue cannot be awarded.
These credits are not filtered out.
| Issue |
Credits available |
Scope |
| Part 1 |
|
|
|
| Hea 01 Daylighting |
Y |
|
Only answer C is available. |
| Hea 02 Control of glare from sunlight |
|
N |
|
| Hea 03 Internal and external lighting levels |
|
N |
|
| Hea 04 Lighting control |
|
N |
|
| Hea 05 Minimising flicker from lighting systems |
Y |
|
|
| Hea 06 View out |
|
N |
|
| Hea 07 User comfort control |
|
N |
|
| Hea 08 |
Y |
|
|
| Hea 09 |
|
N |
|
| Hea 10-13 |
Y |
|
|
| Part 2 |
|
|
|
| Hea 14 Thermal comfort |
|
N |
|
| Hea 15 Smoking policy |
Y |
|
|
| Hea 16 Indoor air quality management |
Y |
|
|
| Hea 17 Acoustic conditions |
|
N |
|
| Hea 18 Legionella risk management |
Y |
|
|
| Hea 19 Drinking water management |
Y |
|
|
16-Jul-2026 - Hea 09 corrected.
16-Dec-2022 - KBCN title and scope updated for better visibility. Error in Hea 03 amended. Applicability of KBCN applied only to affected issues (N, or modified answer options) with to minimise header space in the UI. Original content on Resources moved to new KBCN.
27-Nov-2025 - KBCN applicability updated to include all Hea credit issues.
Applicability – Resources – common areas only assessment - KBCN1557
In an assessment of common areas only - the scope of some issues are modified in the table below.
Answers which are unavailable cannot be filtered out, and cannot be awarded by default.
| Issue |
Scope |
| Part 1 |
|
| Rsc 02 Reuse and recycling facilities |
Answers D and E are only available if occupants store waste in a central waste storage facility within the assessed common area. All other credits are available. |
| Part 2 |
|
| Rsc 06 Optimising resource use, reuse, and recycling |
Answer D is only available if occupants store waste in a central waste storage facility within the assessed common area. All other credits are available. |
Apportioning Water Consumption – common areas only assessment - KBCN1679
For assets where only the common areas are being assessed, the water consumption targets and actual figures reported should be based on the water used within the assessed areas only.
Therefore, where metering is provided for the whole building consumption and no separate metering of common areas is available, a logical assessment of the sanitary (and other) water use and distribution should be carried out so that the figures are based on an accurate estimation of water usage within the common areas. Apportioning must not be based purely on the percentage of floor area.
A logical assessment could be based, for example, on the percentage of water using equipment installed, such as the proportion of toilets/taps/dishwashers etc within the scope of the assessment against those outside of the scope.
Justification and calculations should be provided within the evidence to support the reported figures.
Clarification – reasonable timescale for refrigerant replacement - KBCN1733
If the asset targeting Answer D with a future commitment to replace refrigerants, these must be replaced within
3 years.
BREEAM In-Use assesses the current performance of an asset, and does not recognise far-future commitments. 3 years is the period of a single BREEAM In-Use certification cycle, and it is intended that any replacements are made during this current cycle.
28-Apr-2025 - Published.
Energy Consumption Reporting – common areas only assessment - KBCN1698
For assets where only the common areas are being assessed, the energy consumption targets and actual figures reported should be based on the energy within the assessed areas only.
Please note that where the asset does not have consumption data which covers the assessment area only, the BREEAM In-Use International Energy Allocation Calculator should be used when completing the Management Performance Energy Category.
Energy consumption reporting – Link to Man 04 - KBCN1612
The link to meeting compliance with Man 04, outlined in Ene 23 Criterion 1 is incorrect and should be disregarded.
Answer option D in Man 04 includes targets for Energy, Water and Waste. Whereas the intent of Ene 23 relates to targets for Energy only. This will be updated in the next reissue of the technical manual.
Erratum – [BIU V6 Rsl 06] – Incorrect evidence requirements for answers G – H - KBCN1696
Please note that the requirements for the report to include 'opportunities identified' and the 'key metrics' does not align with the criteria requirements. This can therefore be disregarded.
This will be updated in the next reissue of the manual
Erratum – [BIU V6.0.0 Wat 14] – Incorrect evidence requirements - KBCN1695
The criterion 3 evidence requirement, "evidence of monitoring data" is incorrect and invalid. Assessments should not try to meet this requirement.
Criterion 3 requires the water strategy to have senior management approval. This has no relation to monitoring water consumption, which is already addressed in Wat 13 Water consumption reporting.
This error will be addressed in future updates.
LZC – Local regulations and private wire arrangements - KBCN1658
Where local regulations do not permit electricity generated by on-site renewables to be connected directly to the building, and where evidence of the relevant regulations is provided at QA, the requirement for a private wire arrangement can be waived.
On-site LZC – whole site shared connection - KBCN1424
To be recognised in BREEAM, the on-site Low and Zero Carbon (LZC) technology must have a direct physical connection to the assessed asset.
OR
Where the LZC technology is;
- Located on the same site,
- Is owned and managed by the same organization as the assessed building, and
- Where it is impractical to physically connect the assessed building to the system,
It is acceptable to allocate the renewable energy generated proportionally as a calculation of the asset's predicted energy consumption compared to the total energy consumption of the whole site.
To allocate renewable electricity by proportional consumption:
- Obtain the total annual renewable electricity generated on-site.
- Exclude all renewable electricity which has been exported to the grid.
- Determine the respective electricity consumption of all assets on the whole site (predicted for new builds and measured for existing assets).
Where consumption data is missing, renewable electricity must not be allocated to the assessed asset. In this case, it is assumed that all electricity consumed is sourced from the grid.
17-Jan-2024 - Applicability BIU V6 Ene 13 removed, as this approach is not applicable to assessing the area of PV fitted.
21-Dec-2022 - Applicability to In-Use V6 confirmed.
Operational energy and water use during Covid-19 lockdown - KBCN1425
As we continue to adapt to and assess the impacts of the COVID-19 pandemic, the BREEAM team is seeking to ensure that the data underpinning BREEAM in Use certification accurately reflect typical operational performance.
We appreciate that the full or partial lockdown conditions related to the pandemic may have had a significant impact on the performance of the asset particularly the operational energy and water consumption.
We trust our assessors to use their professional judgement to determine the extent that operational energy and water consumption has been impacted by the COVID-19 restrictions. They must ensure that submitted consumption data is representative of consumption under normal conditions. Clients should work with their assessors if they are unsure how they should proceed.
Assets are likely to have been affected by many different local lockdown scenarios so one approach to reporting consumption data is unlikely to apply to all situations. For example, normal consumption data is likely to be sufficient for assets that have only had a minor changes to their operations (e.g. two weeks), if the rest of the 12 month period has been unaffected.
For assets that been more significantly affected (e.g. several months of reduced occupancy), it is likely that energy and water consumption data will need to be taken from a period of time before local lockdown restrictions came into force. In this scenario, the following approach can be used:
The consumption reported must cover the 12 months prior to the restrictions coming into force. The reported consumption would need to be validated against the year prior to the reporting period to provide assurance to the Assessor that it was in line with typical operations. Additional evidence and verification will be required for submission. The following sections should help clarify how this should work:
Normal BREEAM requirements
Consumption Reporting:
- 12 months prior to submission, validated against the evidence requirements
Evidence requirements:
- Bills or other third-party evidence to support the consumption data reported for this period.
New requirements for this KBCN
Consumption Reporting:
- 12 months prior to the lockdown period validated against the 12-month period prior to the reporting period to confirm usage as “typical”
Evidence requirements:
- Bills or other third-party evidence to support the consumption data reported for this period
- Bills or other third-party evidence to support the consumption data in the validation period
- A description of the changes that took place to the property’s operations due to COVID-19 and provide evidence of the circumstances
Example for a building submitting for certification in October 2020 subject to lockdown from March 2020:
Normal reporting period
October 2019 – September 2020
Adjusted reporting period in line with this KBCN
March 2019 – February 2020
Validation period: March 2018 – February 2019
This KBCN will remain in place but will be under review as we continue to monitor the impacts of COVID-19 and amend requirements as circumstances change. We will keep assessor informed of BREEAM In-Use users and assessors via further service announcements and other communication channels.
Procedures and plans for cleaning the interior of the asset – Scope of the requirements - KBCN1649
The criteria only apply to areas or systems for which the landlord is responsible for the cleaning arrangements. However, the landlord must provide written guidance to tenants on 'procedures and plans for cleaning the interior of the asset' that aligns with relevant aspects of Criterion 2.
It is not a requirement that the landlord monitors or enforces this, however, in order to meet the intent of the criteria as far as possible, evidence must be provided that such guidance has been provided to all tenants.
Note: This guidance is not intended to change the criteria, but rather to clarify the overall intent. The applicability of the requirements to tenanted areas is not stated in the technical manual. Therefore, if it can be demonstrated that an assessment has based compliance on landlord's/common areas only prior to the date of publication of this guidance, this will be accepted.
Updated guidance on the scope of these requirements will be included in the technical manual at the next opportunity.
Single tenant - KBCN1640
Where the assessment area is only occupied by a single tenant, the issue is not filtered out. All relevant credits apply.
The criteria is designed to recognise efforts between the asset owner and tenants to coordinate sustainability policies and resource monitoring. This principle is not affected by having a single tenant, even if they might act in the role of a managing occupier.
Smoking policy – External areas - KBCN1680
The criteria do not require that the asset provide a designated external smoking area.
The intent of Specific Note 1 is that the asset management encourage compliance with the no smoking policy by identifying areas where building users are not prohibited from smoking. However, where it is justified that no such areas can be identified within proximity of the asset, this requirement can be disregarded.
Using water from natural underground sources to offset water consumption - KBCN00094
Water from natural underground sources (for instance aquifer water accessed via boreholes) cannot be used to offset:
- NC / RFO: potable water consumption.
- IU: utility supplied water consumption.
A significant amount of water used for public consumption is already drawn from aquifers. Private boreholes may be drawing water from the same sources as public utility companies.
27-Mar-2024 - Title and text updated to broaden definition. Scheme applicability updated.
Verification of Security Needs Assessments/Security Risk Assessments - KBCN1770
Where the author of a Security Needs Assessment [‘Security Risk Assessment’ in BIU] does not meet the BREEAM competency requirements, compliance can still be achieved where the report is reviewed and verified by a qualified SQSS [‘Competent Person’ in BIU], who confirms in writing that it is accurate, appropriate and in line with industry best practice.
In these circumstances, the SQSS or ‘Competent Person’ is expected to verify and take ownership of the report and accept professional responsibility for its content.
Water consumption reporting – Link to Man 04 - KBCN1611
The link to meeting compliance with Man 04, outlined in Wat 13 Criterion 1 is incorrect and should be disregarded.
Answer option D in Man 04 includes targets for Energy, Water and Waste. Whereas the intent of Wat 13 relates to targets for Water only. This will be updated in the next reissue of the technical manual.
Water strategy – Replacement and Schedule - KBCN1673
Replacement
The intent is that there is a programme in place which identifies any planned refurbishments and confirms that, where relevant, the works will include upgrading high water-consuming fittings and appliances with low water-consuming equivalents.
This does not require the systematic replacement of all fittings and appliances. However, it must also include a commitment to upgrading the efficiency of existing fittings and appliances when they reach the end of their service life.
Schedule
This may include specific fittings and appliances with low water consumption, or it can be based on a performance specification that these must meet, e.g. the flow rate or efficiency rating.
Information correct as of 20thOctober 2026. Please see kb.breeam.com for the latest compliance information.