Refurbishment and Fit Out / International / 2015 / 02 - Health and Wellbeing /
HEA 04 - Thermal Comfort
Information correct as of 2ndDecember 2024. Please see kb.breeam.com for the latest compliance information.
Air-conditioned spaces - KBCN00035
Air-conditioned spaces are assessed to ensure appropriate thermal comfort levels are achieved. Cooling capacity should be sufficient to comply with the requirements of CIBSE Guide A, however providing sufficient space to install additional capacity to meet the requirements at a later date in line with projected climate change scenarios is also acceptable.
In addition, if it can be demonstrated that the air-conditioning system can achieve the thermal comfort criteria in accordance with CIBSE Guide A, Table 1.5, thermal modelling does not need to be carried out. The “time out of range” (TOR) metric should be reported as 0%.
Alternative weather files - KBCN1182
Different or newer weather files can be used instead of those referenced in the manual, as long as they achieve the aim of the credit. Weather files based on climate projections with higher temperatures than those specified in the relevant criteria, set a more robust standard for overheating and so they are acceptable. The alternative weather files need to include same variables as the specified weather files e.g. dry bulb & wet bulb temperature, wind speed & direction, solar altitude & azimuth, cloud cover etc. for each hour of the year. It is the role of the assessor or design team to verify this and ensure that meeting the BREEAM criteria does not become easier by using the alternative weather file.
Approach to thermal model when using BMS - KBCN0169
Where there are smart systems such as BMS in place, modelling must consider normal operating conditions, with the heating and cooling system in operation regardless of the control strategy.
In order for the design team to size the heating/cooling plant, they will carry out modelling to calculate the heat/cold loss throughout the year. Results of these calculations must be submitted, with the heating/cooling plant specification which would demonstrate that the building has been designed to ensure internal winter/summer temperatures will not drop below an acceptable level, and that in effect the winter TOR is zero.
Assessing industrial spaces – exemptions - KBCN0734
The thermal comfort criteria do not apply to the operational or storage areas typically found in industrial assets or other similar asset types. The criteria is still be applied to the other parts of the asset as appropriate.
Operational and storage areas often have function-related thermal requirements determined by operational or storage needs. These functional requirements override the needs of any occupants.
17-Jan-2024 - Scheme applicability updated.
Definition of concourse - KBCN0386
A concourse is an open area within or in front of a public building which is used primarily for circulation, short term waiting, or incidental interaction, analogous to the concourse of a train station. It should not be considered occupied space.
Natural ventilation – use of CIBSE TM52 - KBCN0935
For a naturally ventilated building, it is acceptable for the thermal comfort limits and calculation methodology in CIBSE TM52: The Limits of Thermal Comfort: Avoiding Overheating in European Buildings to be used in place of ISO 7730:2005.
BREEAM recognises that adaptive comfort models can provide more appropriate thermal comfort limits for naturally ventilated buildings.
Occupant control – BMS and degree of control - KBCN0175
A Building Management System controlled set point with local override controls limited to a set range would satisfy the occupant control requirement so long as the temperature range available to building users is confirmed as appropriate for the building type and user profile.
Occupant control – spaces requiring user controls - KBCN0170
This guidance is intended to clarify the types of area for which user controls are required or would be considered beneficial.
Zoning is required in all areas of the asset where specified in the assessment criteria. Please refer to the specific requirements of the applicable BREEAM standard to interpret this guidance appropriately.
User controls required
Spaces where users are expected to have independent control over their environment.
- Owned spaces: small rooms for a few people.
For instance, cellular offices, owned spaces in residential assets.
- Temporarily owned spaces: where occupants expect to operate the environmental controls while they are there.
For instance, meeting rooms and hotel bedrooms.
- Shared spaces.
For instance, multi-occupied areas such as open-plan offices or workshops.
User controls not required
Spaces where users are not expected to have independent control over their environment.
- Managed spaces: where environmental control is expected to be centrally managed.
For instance, atria, circulation areas, concourses, entrance halls, function halls, restaurants, libraries, and shops.
- Occasionally visited spaces.
For instance, storerooms, bookstacks in libraries, aisles of warehouses, toilets.
14-Dec-2022 - KBCN applicability updated to include BIU. Wording clarified, and amended for compatibility with BIU criteria.
Part 2 Assessments & Thermal Zoning - KBCN0460
Some criteria related to thermal zoning and controls may not be applicable to Part 2 assessments.
These should however, be addressed as far as possible within the work to the core services and associated infrastructure, given the scope of works. Where compliance with any requirement is not possible, this should be justified by the design team in the evidence for this Issue.
10/02/2017 - This replaces the previous CN which stated, incorrectly, that the criteria relating to thermal zoning do not apply to Part 2 assessments. This approach now aligns with the BREEAM manual and the scoring & reporting tool.
PMV and PPD reporting for mixed mode ventilation buildings - KBCN0632
When assessing buildings where both naturally ventilated and air conditioned spaces are included, reporting the PMV and PPD indices is required.
Projected climate change weather file - KBCN0117
Although other scenarios are available, for the thermal simulation of climate change environments, the 50th percentile weather file should be used for consistency with other assessments.
Reporting PPD and PMV Figures - KBCN0867
The PMV (Predicted Mean Vote) and PPD (Predicted Percentage Dissatisfied) values need to be entered into the scoring & reporting tool for data recording purposes.
The thermal modelling specialist should be able to provide values for both the PMV and PPD for the asset.
The values to report are the observed range of values for PMV and PPD:
- Across all occupied areas and,
- Across all expected occupied hours.
If the software or calculation method used does not generate these PMV / PPD metrics, they do not have to be provided.
[accordion]
[accordion_block title="Example"]
An asset has the following thermal comfort ranges across its occupied spaces:
- PMV ranges from -0.3 to +0.2.
Enter '-0.3 to +0.2' into the relevant field.
- PPD ranges from 3% to 10%.
Enter '3% to 10%' into the relevant field.
[/accordion_block]
[/accordion]
15.09.22 Wording and example clarified.
Thermal comfort – Changing rooms - KBCN1133
Whilst thermal comfort in changing rooms may be considered as significant, such spaces are, generally, outside the scope of this Issue, as they would not fall within the definition of an 'occupied space'.
17/06/2019 - This supersedes the advice previously provided in this KBCN, which was published in error on 13/06/2018
Thermal modelling for large scale projects - KBCN1171
In cases where the scale of the project makes it unfeasible to provide thermal modelling for every space, it is acceptable to demonstrate compliance with a representative sample of floors or rooms, ensuring any worst case scenarios are included.
Thermal modelling for Part 1 assessments - KBCN0944
Where a Shell Only (Part 1) assessment is being carried out, but the future servicing strategy is unknown, the thermal comfort credit is still applicable.
To assess compliance, the upgraded shell of the building shall be modelled with a typical servicing configuration which meets as a minimum:
- UK: Recommended minimum standards in the Non-Domestic Building Services Compliance Guide.
- International: relevant building services minimum standards within local building regulations, or Tables 6.8.1 A-K of ASHRAE Standard 90.1.
The thermal modelling credit can be awarded when the notional modelled system achieves the BREEAM thermal comfort criteria.
The intent is to ensure that thermal comfort is achievable with the proposed upgraded shell for any future occupiers. The details of the notional system could be passed on to future occupiers or servicing specialists to inform their servicing strategy.
Weather File Location - KBCN1013
In accordance with the guidance provided in CIBSE AM11, in instances where the weather file for the nearest location does not represent the most appropriate climatic conditions for the actual location, it is permissible to use the weather file from another, nearby location, which more closely matches the climate at the actual location.
This can take account of the climatic influences of height above sea level, a coastal location or other local, climate-moderating features such as mountains, woodland, lakes, prevailing wind direction or urban heat island effect.
Weather files applicable internationally - KBCN0732
Prometheus is currently referred to in the technical manual to demonstrate compliance with the 'Adaptability - for a projected climate change scenario' criteria. Since this is not applicable internationally, until an alternative has been formally approved, the following can be used:
Climate change world weather file generator Version 1.8
http://www.energy.soton.ac.uk/ccworldweathergen/
Weather files can be found here, or on other national sources.
https://www.ashrae.org/resources--publications/bookstore/iwec2
The instructions are included in the first link.
Technical manual to be updated accordingly in next reissue.
Information correct as of 2ndDecember 2024. Please see kb.breeam.com for the latest compliance information.