ENE 66 - Sub-metering: tenanted areas
Information correct as of 19thOctober 2026. Please see kb.breeam.com for the latest compliance information.
Full or Partial sub-metering - KBCN1203
Fully sub-metered
For an asset to be considered as fully sub-metered both heating and cooling consumption must be sub-metered for each tenant.
Partially sub-metered
For an asset to be partially sub-metered, the asset must have at least one tenant that has both heating and cooling consumption sub-metered. An area cannot be considered either fully or partially sub-metered where only one of heating or cooling is sub-metered.
Heating and cooling provided through one system - KBCN1204
Where heating and cooling is provided through the same system and it is not possible to separate the consumption related to each, then one sub-meter covering the system can be considered to be fully sub-metered.
Sub-metering requirements for a Single Tenant - KBCN1201
Where the asset has a single tenant, or where it is owner occupied, this space must have both heating and cooling sub-metered to achieve maximum credits.