Meeting the minimum standard requirement – compliance when chain of custody is broken - KBCN1816

Where there is a broken chain in the last link between the purchase and delivery of certified timber from the supplier and the forwarding distribution of the timber to the site under assessment, such as where the timber has been delivered to a subcontractor or fabricator’s premises instead of direct to site (e.g. as part of a bulk order or where limited storage is available on site), compliance can still be achieved if a documented risk assessment confirms that there is low risk of mixing or substitution of certified and non-certified timber. Ways to demonstrate compliance: A. Verification that the subcontractor or fabricator only purchases and uses certified timber. There must be robust mechanisms in place to verify that all timber materials purchased and delivered originate from sustainably managed sources. This includes maintaining documented timber procurement policies and procedures that mandate certified timber orders and delivery checks. Comprehensive supplier details should be readily accessible for review upon request to demonstrate that all timber is certified. B. Where non-certified timber is handled/stored or sourced, that there are robust control measures in place to prevent any substitution or mixing of certified and non-certified timber at every stage of the process. Documentation demonstrating compliance should be maintained and made available upon request. Examples of appropriate control measures are listed below:
Control
Evidence required
Purchasing records All purchase orders, requisition notes, and contracts must explicitly specify the product details and confirm that materials are to originate from legal and sustainable sources.

Segregated storage of timber

Site layout map, stock control processes and records to confirm that certified timber is stored away from non-certified timber.
Segregated delivery of timber to site - All timber must be thoroughly inspected and verified before shipment to confirm that it is correctly marked/labelled as FSC/PEFC-certified. - Delivery notes must be accurately maintained. - A second-party verification process to check tickets and stock, must be carried out upon site delivery to confirm certified status of timber.
Documentation Comprehensive documentation must enable independent assessors to trace any timber back to its sustainable source. This includes maintaining purchase records, goods-inward notices, stock records, and sales documentation such as orders and invoices.