New Construction / International / V6 /

02 Health & wellbeing

Information correct as of 18thJune 2026. Please see kb.breeam.com for the latest compliance information.

Accreditation – sampling and testing laboratories - KBCN1337

Analysis / testing laboratory NC 2016 or newer: Where an organisation used for the analysis of indoor air or emissions from building products is not accredited to ISO/IEC 17025, the organisation must be accredited, either by a national accreditation body, or by a member of any one of the following accreditation groups: European Cooperation for Accreditation International Accreditation Forum International Laboratory Accreditation Cooperation The accreditation must specifically cover the analysis of indoor air or emissions from building products. Other schemes: Accreditation to ISO/IEC 17025 is not required in the criteria. However, this KBCN has been applied to encourage a consistent approach towards accreditation. Accreditation by a national or internationally recognised organisation helps to ensure rigorous, consistent and reliable testing results. Sampling organisation If another organisation carries out sampling on behalf of the analysis / testing laboratory, this organisation does not need to be accredited to the above. However, they must provide a brief report justifying: This report is provided to the BREEAM assessor and submitted as supporting evidence for this issue.
31-Oct-2022 Wording clarified. Scheme applicability updated.
10-Oct-2022 Title amended for clarity. Scheme applicability updated.
24-May-2022 Updated to differentiate between sampling and analysis requirements. 
07-May-2021 Added clarification regarding alternative qualifications. 
10-May-2021 Updated scheme applicability.

Applicability – industrial operational areas - KBCN1342

The aim of this issue is to encourage a healthy internal environment.  For the operational areas of industrial buildings, the internal environment is dictated by health and safety requirements.  This means that the BREEAM requirements should not be made applicable to them, and so the operational areas can be ignored in the assessment of Hea 02.
10-Oct-2022 - Title amended to align with standard KBCN naming format for clarity and consistency. Made applicable to UK and International NC V6.

Applicability – retail asset with no office areas - KBCN0531

The compliance note regarding industrial and retail areas incorrectly suggests that the minimising sources of air pollution credits are not applicable to retail areas with no associated offices. These credits do apply to retail sales areas, although they are excluded for operational areas in industrial buildings. The 'potential for natural ventilation' credit is not applicable for retail sales areas, as it applies only to office areas. Therefore, where a retail building does not contain any office, this credit is not applicable. While the requirements apply to permanently or semi-permanently occupied offices, small admin areas, which are only used occasionally can be excluded. This also applies to shell only and shell and core new build projects, where it can be demonstrated that no office spaces will be provided as part of the fit-out. The online tool will award the credit by default in both issue 1.0 of the INC 2016 scheme and up to issue 1.4 of the IRFO 2015 scheme. When assessing against INC 2016 2.0 and V6, the online tool will instead filter this credit out.
22-Oct-2022 Title amended to align with standard KBCN naming format for clarity and consistency. Made applicable to International NC V6.
11-Sep-2018 Clarification added in relation to spaces that are used occasionally, and shell only/shell and core new build projects. 
15-Sep-2017 Clarification added on the procedure for making the 'potential for natural ventilation' credit N/A on the online tool. Technical manual to be updated accordingly in next re-issue.

Applicability of ‘Internal lighting’ and ‘zoning and occupant control’ criteria to Residential buildings - KBCN0978

These criteria, ie 7 to 9 and 11 to 13, are not applicable to Residential buildings.
Technical manual to be updated in the next reissue.

Assessing industrial spaces – exemptions - KBCN0734

The thermal comfort criteria do not apply to the operational or storage areas typically found in industrial assets or other similar asset types. The criteria is still be applied to the other parts of the asset as appropriate. Operational and storage areas often have function-related thermal requirements determined by operational or storage needs. These functional requirements override the needs of any occupants.
17-Jan-2024 - Scheme applicability updated.

Emissions from products – Building materials for M&E purposes - KBCN1740

All M&E materials are excluded from VOC assessment requirements. However, from V7 onward, while finished M&E products may be excluded, all on-site applications of paints, coatings, adhesives and sealants used for M&E purposes must be included in VOC assessments under their relevant material categories.
02 July 2025 - Inclusion of duct insulation removed

Emissions from products – earlier versions of AgBB standard - KBCN0655

Guidance Note GN22 lists the standard AgBB (2015) as a recognised scheme for emissions from building products for pre-December 2015 launched BREEAM schemes. Previous versions of the AgBB scheme are not listed as recognised schemes because earlier versions of AgBB did not include any requirement for the testing of Formaldehyde. If an earlier version AgBB has been used, further evidence will be required to provide additional information on the required Formaldehyde testing.
10-Oct-2022 - Title amended to align with standard KBCN naming format for clarity and consistency. Made applicable to International NC V6.
 

Emissions from products – EU CLP Regulation and Category 1A/B carcinogen emission limits - KBCN1280

The European Regulation (EC) No.1272/2008 on classification, labelling and packaging of substances and mixtures (‘the CLP Regulation’ or ‘CLP’) applies to all EU Member States. CLP requires manufacturers, importers, downstream users and distributors to communicate the identified hazards of a substance or mixture to the other parties in the supply chain, including to consumers. The regulation requires products with hazardous properties to be labelled in accordance with CLP before being placed on the market. CLP requires products containing any ingredients that have been classified as Category 1A and 1B carcinogens to be labelled as carcinogenic. Therefore, with respect to the BREEAM Category 1A and 1B carcinogens emission limit criteria, for products marketed in EU Member States, if a product’s safety information (e.g. safety data sheet) or a manufacturer’s declaration confirms that that the product does not need to be labelled as a Category 1A or 1B carcinogen in accordance with CLP, then this information would be an acceptable form of evidence for demonstrating compliance with the criteria.
10-Oct-2022 - Title amended to align with standard KBCN naming format for clarity and consistency. Made applicable to International NC V6.

Emissions from products – French regulations and Category 1A/B carcinogen emission limits - KBCN0741

As highlighted in Table 1 of BREEAM Guidance Note GN22, for certain product types, the French VOC regulation ('Arrêté du 19 avril 2011 relatif à l’étiquetage des produits de construction ou de revêtement de mur ou de sol et des peintures et vernis sur leurs émissions de polluants volatils') can be used to demonstrate compliance with the VOC emissions from building products requirements in pre-December 2015 launched BREEAM schemes. The emissions from building products criteria were significantly updated for the BREEAM International New Construction 2016. Unfortunately the 2011 French VOC regulation does not meet the updated performance requirements for post-November 2015 BREEAM schemes for the following reason. The updated BREEAM requirements require testing for Category 1A and 1B carcinogens (defined as “Carcinogenic compounds detectable by the VOC emission testing requirements in Table 1 and Table 2 and that are classified as category 1A or 1B carcinogens in Annex VI to Regulation (EC) No. 1272/2008 on classification, labelling and packaging of substances and mixtures, which are listed as Carcinogenic VOCs in Annex G.2 of prEN 16516 (draft)"). Annex G.2 of prEN 16516 (draft) lists a total of 57 carcinogenic substances. The 2011 French VOC regulation does not contain any requirements to test for any of these substances. BREEAM is aware of a 2009 French VOC regulation ('Arrêté du 30 avril 2009 relatif aux conditions de mise sur le marché des produits de construction et de décoration contenant des substances cancérigènes, mutagènes ou reprotoxiques de catégorie 1 ou 2') that contains performance requirements for category 1A or 1B carcinogens; however these only cover two substances in Annex G.2 (trichloroethylene and benzene). While BREEAM does not expect all of the substances in Annex G.2 to be analysed by a regulation or testing regime, we do expect more than two. Additionally only the A+ label would meet the updated BREEAM performance requirement for TVOC of 1.0 mg/m³ and only the A and A+ labels would meet the updated BREEAM performance requirement for formaldehyde of 0.06 mg/m³. As such, additional evidence would need to be provided to confirm French VOC regulation A+ labelled products are compliant with the BREEAM International New Construction 2016 performance requirements for category 1A and 1B carcinogens. As such, additional evidence would need to be provided to confirm French VOC regulation A+ labelled products are compliant with the BREEAM International New Construction 2016 performance requirements for category 1A and 1B carcinogens, (see also KBCN1280).
10-Oct-2022 - Title clarified, and amended to align with standard KBCN naming format for clarity and consistency. Made applicable to International NC V6.
26-Apr-2019 - Final paragraph and cross-reference to KBCN1280 added.

Emissions from products – installations manufactured off-site - KBCN0137

Internal finishes to installations manufactured off-site such as elevators need to be assessed for the emissions from products criteria. The specification of internal finishes (regardless of whether they are installed on site or in the factory) will impact on VOC emissions. By specifying low VOC finishes, design teams will be encouraging manufacturers to consider the environmental impacts of their products.
10-Oct-2022 - Title amended to align with standard KBCN naming format for clarity and consistency. Made applicable to UK and International NC V6.
 

Emissions from products – manufacturers’ calculations for paints and varnishes - KBCN0452

Manufacturers' calculations of VOC content, based on the constituent ingredients, can be used to demonstrate compliance with the testing requirement for paints and varnishes.

10-Oct-2022 - Title amended to align with standard KBCN naming format for clarity and consistency. Scheme applicability updated.

Emissions from products – scope of assessment - KBCN0212

General This issue covers any product installed or applied inside the inner surface of the building’s infiltration, vapour or waterproof membrane. Where this membrane is not present, it applies to the inside of the building envelope’s interior-facing thermal insulation layer. Only products that are installed or applied in parts of the building where their emissions are likely to affect indoor air quality need to be assessed. Paints and coatings Any decorative paints and varnishes that occupants are exposed to should be assessed. This is likely to include paints and coatings applied to walls, ceilings, floors, doors, etc. Whole products A finish applied to a product in the factory is assessed as a whole product, and not separately as a paint or coating. For instance, a wood panel has a finish applied in the factory. The whole panel, including all the elements that make up that panel, would need to comply with the requirements set for wood panel products in this issue. The finished product as a whole must meet the performance requirements / emission limits set in the manual.
11-Oct-2022 - Title amended for clarity and consistency. Content merged with KBCN871.
10-Oct-2022 - Wording simplified. Scheme applicability updated.
16-Jun-2017 - Title and general principle amended to extend the applicability of the KBCN to all finishes. Paints specified for specialist applications covered in KBCN0872.
 

Emissions from products – specialist paints and coatings - KBCN0872

Where a paint or coating falls within: then the paint or coating must be assessed. Specialist paints and coatings are exempted from meeting the VOC content and emission limits where there are no alternative products available that can perform the function, and still meet the emission limits. This must be clearly evidenced.
02-Oct-2025 Reference to 'VOC content' added and KBCN applied to INC V7 to clarify CN2.1
27-Oct-2022 Wording clarified. New compliance principle added from UKNC V6.
10-Oct-2022 Title amended for clarity. Scheme applicability updated.
13-Mar-2020 KBCN amended to clarify exceptions and applicability.
16-Jun-2017 Content merged with KBCN0212.

Emissions from products – testing to ISO 16000-10 - KBCN1134

Results of testing to ISO 16000-10 can be considered compliant with the relevant testing requirements of the emissions from construction products credit where the product manufacturer can demonstrate the results generated by testing to ISO 16000-10 correlate to results that would be achieved using EN 16516 or ISO 16000-9. This is because EN 16516 classifies ISO 16000-10 as an ‘indirect method’, which means “any simplified, screening, secondary, derived or alternative method. An indirect method can be applied if it provides a result that is comparable to or that correlates with the result of the reference method under the conditions applied. The validity of the correlation with the reference method is limited to the field of application for which it has been established.
11-Oct-2022 - Title amended for clarity and consistency. Scheme applicability updated.

Exemplary level criteria – not all product categories specified - KBCN0636

The assessment of exemplary level criteria assumes that every product category is specified. It awards credit(s) based on the number of product categories that meet the exemplary levels. Where the assessment does not contain every product category, all product categories must meet the exemplary level requirements. [accordion] [accordion_block title="1 exemplary credit"] Exemplary credit requirement:  3 out of 4 product types meet the exemplary requirements. An assessment has only specified 3 product types in total. To achieve the credit, all product types must meet the exemplary criteria. [/accordion_block] [accordion_block title="2 exemplary credits"] Exemplary credit requirement: An assessment has only specified 3 product types in total. [/accordion_block] [/accordion]
19-Oct-2022 - Wording and title clarified. Scheme applicability updated. Scenario added.

GN06 Indoor air quality plans - KBCN0618

Latest version: v2.2, July 2025 Guidance Note 6 (GN06) provides guidance to assessors and project teams regarding the content and rigour of an Indoor Air Quality Plan (IAQP) as required by the indoor air quality criteria in BREEAM New Construction and BREEAM Refurbishment and Fit-Out. It should not be interpreted as BREEAM criteria. It is intended to provide assessors and project teams with further, flexible information and guidance regarding the rigour, content, and tasks of an IAQP. Download Guidance Note 6 View all Guidance Notes on BREEAM Projects (licensed assessors only)
16-Jul-2025 - Updated for release of v2.2

GN22 Recognised schemes for emissions from construction products - KBCN0719

Latest version: v3.1, March 2026 Within the Health and Wellbeing category of several BREEAM schemes, credits are awarded for specifying materials that minimise emissions from building products of formaldehyde and volatile organic compounds (VOCs). The criteria involve meeting emission level performance requirements in accordance with compliant performance and testing standards. Guidance Note 22 (GN22) lists schemes that show equivalent or better performance than the current BREEAM and HQM criteria, and therefore can be used to demonstrate compliance with the criteria. This document should be read in conjunction with the relevant assessment issue guidance provided in the appropriate BREEAM or HQM technical manual. The guidance note contains two tables: Download Guidance Note 22 View all Guidance Notes on BREEAM Projects (licensed assessors only)   Applying for inclusion in GN22 The list of approved schemes is based on those which have made a successful application to BREEAM. As such, there may be other operational schemes that could potentially be recognised. To be considered for inclusion, the scheme operator must complete an application form, providing full details of the scheme, and submit this to BRE Global for technical approval. A flat rate charge is payable to cover the costs of administering and reviewing the application. GN22 will be updated following the approval of any schemes via this process. The application form (BF1648) provides full details of the application process, and licensed BREEAM assessors can request a copy by submitting a technical query using the webform. Other parties may request a copy by contacting: breeam@bregroup.com
25-Mar-2026 - Release of GN22 3.1
25-Sep-2025 - Updated to provide details of the approval process and title updated.
30-Jan-2025 - Release of GN22 3.0
30-Sep-2024 - Release of GN22 2.9
01-Feb-2024 - Release of GN22 2.8
31-Jan-2023 - Release of GN22 2.7
10-Oct-2022 - This KBCN merged with KBCN0646. Title amended to align with standard KBCN naming format for clarity and consistency. Made applicable to UK and International NC V6.
25-Jan-2019 - Link to Guidance Note updated
12-Mar-2018 - Link to Guidance Note updated

Indoor air quality plan – later consideration - KBCN1544

Where BREEAM has been engaged at a later stage in the project (for instance, at the beginning of a Post-Construction Assessment) the IAQ plan must still be produced. The late stage plan must clearly identify opportunities to improve indoor air quality that: The plan is focused on decisions and actions that can still be practically carried out. The indoor air quality plan is an on-going consideration that extends into the operational life of the asset.

Indoor air quality plan – scope - KBCN0294

Where possible, the indoor air quality plan must cover all items in the criteria. This means the plan must be completed for: Within these requirements, there is flexibility for the design team to use their professional judgement to determine what is appropriate to meet the criteria. Any exclusions must be clearly evidenced and justified. As the basis for effective asset management, the indoor air quality plan must be written in a consistent and comprehensive manner. The report must address relevant aspects as fully as possible within the scope of the development.
11-Oct-2022 Title updated for clarity. Wording clarified. Content merged with KBCN0556. Reference to KBCN1544 added. Scheme applicability updated.

Post-construction measurement – formaldehyde / VOC levels exceed limits - KBCN0258

If the measured formaldehyde / VOC concentrations were above the prescribed limits, the appropriate remedial action must be taken, as described in the IAQ Plan. The criterion requires confirmation of 'the measures that have or will be undertaken' however it does not specifically address re-testing. We would expect, however that the IAQ Plan should outline what remedial measures are appropriate depending upon the severity and type of the non-compliance with prescribed limits. Such measures may include re-testing as a matter of 'best practice'. Where levels are found to exceed these limits, the project team confirms the measures that have, or will be undertaken in accordance with the IAQ plan, to reduce the TVOC and formaldehyde levels to within the above limits.
10-Oct-2022 - Title amended to align with standard KBCN naming format for clarity and consistency. Made applicable to International NC V6.

Post-construction measurement – sampling methodology and KPIs - KBCN0380

When testing for VOCs post-completion and pre-occupancy, a representative sample of the building needs to be carried out. Each sample TVOC and formaldehyde measurement needs to achieve the threshold levels individually, either in the initial testing or after remedial measures have been implemented. This ensures that all tested areas of the building are below the limits, and that areas of non-compliance are not ‘averaged out’. 'When providing KPI test results for air quality post-construction / pre-occupancy within scoring and reporting tool, where the limits are exceeded and remediation and re-testing are carried out, the figure should be an average for the whole building post-remediation, as this is the key figure that reflects the building at its certified state'. Where testing is not a requirement of the IAQ Plan and this is not carried out, the original testing figures should be entered and the assessment report should provide details of the remediation measures undertaken to reduce these to within the prescribed limits.
10-Oct-2022 Title amended to align with standard KBCN naming format for clarity and consistency. Scheme applicability updated. 
06-Dec-2017 Amended to account for situations where re-testing is not required by the IAQ Plan.

Potential for natural ventilation – mechanically ventilated and mixed mode assets - KBCN1533

Scope of KBCN This KBCN clarifies the associated compliance note for this credit. Clarification Mechanically ventilated and mixed mode assets can potentially achieve the 'potential for natural ventilation' credit by:
  1. Meeting the relevant criteria for room depth and glazing area OR, where this is not possible:
  2. Show through modelling that the building has the potential to be ventilated entirely via a natural ventilation strategy.
For 2. the second paragraph of the CN allows flexibility in demonstrating adaptability to an entirely natural ventilation strategy. An asset can allow for mechanical ventilation for ≤ 5% of its annual operating hours to boost ventilation rates, and (for this credit) can still be considered to be a fully naturally ventilated strategy. ≤ 5% mechanical ventilation rule The focus of this credit is to demonstrate future adaptability to introduce fresh air into the asset for occupant comfort, so this requirement relates only to mechanical ventilation. Active heating / cooling is not considered. ≤ 5% is a weighted average over all of the asset's occupied spaces. The basis for the weighting will be determined by the modelling software used. Scope and time scale of modelling The modelling covers all occupied spaces. Where relevant, exclusions are allowed - see related KBCNs for details. The modelling period is one year, during the asset's operating hours. The modelling must be based on a plausible scenario that is realistic. This means that:

Potential for natural ventilation – use of doors to comply - KBCN0690

Doors can only be used to demonstrate potential for natural ventilation where: In all cases, the use of doors must be clearly and robustly justified by the Assessor.
19-Oct-2022 - Wording clarified. Scheme applicability updated.
 

Prerequisite – Users with special hearing and communication needs - KBCN0969

Intent Criterion 1c ensures that the suitably qualified acoustician has influenced the design of the asset to: What this should cover will depend on the asset type and expected users. Asset users The UK Department for Education document BB93 Acoustic design of schools: performance standards building bulletin 93 (February 2015) defines users with special hearing or communication needs as those with any of the following: This list is not exhaustive, and the suitably qualified acoustician must consider typical asset users, along with the other points a-d when giving early design advice regarding room layout, sound insulation and reverberation times. Accessibility features The principles of accessible design are universal and could be applied in a wide range of assets. Additional features that could be relevant to accessible acoustic design include, but are not limited to: The suitably qualified acoustician must use their professional judgement to determine the scope of any such features as part of the design. Where no features are applicable this must be clearly justified.
04-Sep-2024: Wording and intent clarified. Information on additional accessibility features added. Scheme applicability updated. Title updated.
01-Mar-2019: Amended to clarify that this is a 'typical' list of users, but does not impose a new requirement.

Ventilation – E-cigarettes - KBCN1014

The use of e-cigarettes and vaporizers is considered equivalent to smoking. A smoking ban must also include a ban on e-cigarettes and vaporizers.
11-Oct-2022 - Scheme applicability updated.

Ventilation – external requirement for window opening restrictors - KBCN1032

Opening restrictors to windows may sometimes need to be installed to meet: Where such external requirements are in force, these requirements cannot be used as a mitigating factor for meeting the BREEAM ventilation criteria. Even with window restrictors, adequate ventilation can still be achieved.

Ventilation – filtration – non-residential assets - KBCN0797

Relevant specialist required The design and specification of air filtration for mechanical ventilation requires the input and review of a relevant ventilation designer or specialist. It is their responsibility to interpret the requirements of this KBCN to align with local conditions. Referenced standard The requirements for air filtration in mechanical ventilation systems follows EN 16798-3:2017 Section B4.2. This standard replaces EN 13779:2007. See KBCN1054. Supply air quality Outdoor air quality The filtering required to achieve SUP2 is affected by outdoor air quality. Outdoor air quality (ODA) in both EN 16798-3:2017 and EN 13779:2007 are defined as: As ODA definitions are relative to national air quality standards, these will depend on local regulations and the location of the asset. Please refer to the relevant specialist on how to correctly classify ODA for your asset.
18-Nov-2022 Title amended to differentiate between residential and non-residential filtration KBCNs.
06-Sep-2022 KBCN re-written and re-named to clarify BREEAM ventilation filtration requirements in relation to new ventilation standards.

Ventilation – single room MVHRs - KBCN1042

Single room mechanical ventilation heat recovery units do not need to show that the air intake and exhaust are a suitable distance apart. However, the air intakes of these units must be located to minimise intake of other potential external pollutants.
11-Oct-2022 - Title amended for clarity and consistency. Wording simplified. Scheme applicability updated.

Ventilation – suitable filtration – residential assets - KBCN1279

Multiple-occupancy residential developments with central air conditioning systems can demonstrate compliance with criterion 6 by incorporating filtration with a filter class of F7. For single occupancy dwellings, it is sufficient to demonstrate that a suitable filtration system is incorporated in the installed HVAC system, in accordance with the manufacturers' recommendations.
18-Nov-2022 Title amended to differentiate between residential and non-residential filtration KBCNs.
10-Oct-2022 Scheme applicability updated.

Ventilation – withdrawal of EN 13779:2007 - KBCN1054

Standard EN 13779:2007 has been withdrawn (01/02/2018) and in its place the following should be used: Non-residential buildings: Both standards provide three methods for selecting design ventilation rates: Dwellings (only applicable to the BREEAM International New Construction scheme): Both standards provide different options for selecting design ventilation rates: It is the design team’s responsibility to determine and apply the most appropriate method or option(s) for the project undergoing assessment. Existing projects can continue to use EN 13779:2007 where applicable. Any new assessment registrations should use the replacements above.
11-Oct-2022 - Scheme applicability updated. 
03-May-2020 - Typo corrected to clarify that 'EN 16798-1:2019 Annex B.3 'either Category I OR Category II default design values' are to be used. 
10-Jan-2020 - KBCN updated to clarify methods for complying with new standards. 
01-Sep-2019 - KBCN updated to reference new standard.

View out – Corrections to Table - KBCN1136

The values for distance from window to workplace in the View out Table are incorrect. The Table should read as follows:
07-Oct-2025 - Applicability to INC V6 confirmed

Weather files – 50th percentile - KBCN0117

For the thermal simulation of climate change environments, where this not specified in the manuals, the 50th percentile weather file is used in all cases. This applies also to the use of any alternative weather files or formats which are not listed in the manual. See KBCN1182.
18-Dec-2024 - Title updated for clarity. Scheme applicability updated. Link to KBCN1182 added.

Weather files – alternative format or location - KBCN1182

If they achieve the aim of the credit, alternative weather file formats not listed in the manuals can be used instead of those referenced in the manual. Format - current climate The alternative weather files must include same variables as the specified weather files for each hour of the year e.g.: - Dry bulb & wet bulb temperature, - Wind speed & direction, - Solar altitude & azimuth, - Cloud cover etc. For example, TMY (Typical Meteorological Year) is an accepted alternative format for BREEAM, meeting the requirements above. The assessor or design team must verify this and ensure that meeting the BREEAM criteria does not become easier by using the alternative weather file. Format - projected climate These alternative files must be based on climate projections with equal or higher temperatures than those specified in the relevant criteria, setting an equally or more robust standard for overheating. Where there are no suitable weather files available for projected climate change, use any one of the following: To modify weather data for existing climates into the relevant future climate change scenarios required in the criteria. Alternative location Where the weather file for the nearest location for the project is not representative of the actual location’s climatic conditions, the project team can use the weather file from another nearby location which is more representative. This can take account of the climatic influences of altitude, prevailing wind, proximity to climate-moderating features, or heat island effect.
19-May-2025 - Added example alternative format. Added links to future climate change resources.
18-Dec-2024 - Merged with KBCN1013. Scheme applicability updated.

Weather files – files applicable internationally - KBCN0732

The technical manual refers to Prometheus, which is not applicable internationally for the projected climate change scenario criteria. Until an alternative has been formally approved, the following can be used: Climate Change World Weather File Generator ASHRAE weather data files
18-Dec-2024 - Title updated. Link updated.

Information correct as of 18thJune 2026. Please see kb.breeam.com for the latest compliance information.