Domestic Refurbishment / 2012 / 07 - Pollution /

POL 01 - Nitrogen Oxide Emissions

Information correct as of 5thNovember 2026. Please see kb.breeam.com for the latest compliance information.

Air conditioning and cooling - KBCN0373

Energy used for air conditioning and cooling systems should not be included when assessing NOx emissions.

CHP NOx emission conversion - KBCN0592

If the CHP manufacturer cannot provide the NOx emissions in mg/kWh it is not possible to award any credits. The CHP manufacturer must provide the NOx emissions in mg/kWh, the conversion factors provided in the Technical Manual can only be used for boilers.

Grid NOx emission factors - KBCN0151

The Grid NOx emission factors should be compliant and relevant to the scheme of the development under assessment i.e. BREEAM NC 2011/ 2014 or BREEAM 2008. In the same way that we do not apply the more stringent requirements of some BREEAM NC 2011 / 2014 Issues retrospectively to 2008 schemes, for a BREEAM 2008 scheme, the emission figures stated in the relevant manual must be used.
09 Aug 2023 - Applicability to IRFO 2015 removed due to conflict with the guidance.

Heat pumps powered by renewable energy - KBCN0422

Where renewable energy is used partially to offset grid electricity in heat pumps, this can contribute towards a reduction in equivalent NOx emissions. To account for seasonal variations in renewable energy generation, this must be calculated over the course of a year.
Information correct as of 5thNovember 2026. Please see kb.breeam.com for the latest compliance information.