Refurbishment and Fit Out / UK RFO 2014 /
04 - Transport
Information correct as of 19thOctober 2026. Please see kb.breeam.com for the latest compliance information.
AI calculation – changes to public transport services during the assessment - KBCN1527
The AI is calculated as part of the design stage transport analysis and its value relates to the site location and to informing transport-related design decisions. This must be based on current information, including any planned and publicly-notified changes at the time the transport assessment is carried out. This should be used as the AI benchmark for the assessment.
Where later, unforeseen changes to public transport availability are implemented before post-construction certification, the AI benchmark should not be updated at post-construction stage.
Assessments should not be disadvantaged by, or benefit from such changes.
Alternative transport measures not applicable to the project - KBCN0965
It is acknowledged that certain alternative transport measures may be considered not applicable to the project under assessment, due to building type, scope of refurbishment, etc.
Upon provision of clear justification for the exclusions, in such instances, in order to ensure a fair assessment, an alternative calculation method has been introduced.
This method is only applicable where there are less than six measures deemed to be appropriate and in all other instances the methodology outlined in the manual applies.
The Assessor will:
- Identify the number of measures applicable to the assessment;
- Determine the number of measures that have been complied with;
- Determine the percentage of measures achieved, and based on this, the proportion of credits achieved.
Please see the worked example below, where the Assessor:
- Deems that five alternative transport measures are appropriate for the project;
- Demonstrates compliance with three of these measures;
- Determines the percentage of compliance, ie 60% (three out of five measures). This results in the awarding of 60% of the three credits available to this assessment, ie 1.8, which, to ensure robustness, will be rounded down to the nearest whole number, with a final one credit achieved.
The number of credits achieved is proportioned to the percentage of compliant measures against the total number of measures applicable to the project.
Amenities – Assessed building is one of the listed amenities - KBCN0264
Where the assessed building is itself included in the list of amenities, that particular amenity criterion can be deemed to be met, e.g. a supermarket development itself meets the proximity to food outlet required for a Retail type building.
Amenities – Pharmacy within a hospital or health centre - KBCN0321
To meet the requirements of 'Over the counter services associated with a pharmacy', a dispensary within a health centre or hospital can be considered as meeting the intent, provided it is publicly accessible and also offers the type of over-the-counter services associated with a stand-alone pharmacy, such as non-prescription medication and health products.
Note: This is a change to the approach outlined in the previous KBCN wording, therefore, for assessments registered before this update, where it can be demonstrated that the the assessor has advised the project team based on the previous wording, this can be accepted:
Superseded guidance:
A publicly accessible pharmacy would typically be required in order to constitute a suitable amenity. If it can be confirmed that an internal pharmacy (in Northern Ireland this may also include an onsite controlled medical dispensary) will provide prescribed medicines for building users, this is acceptable.
18 June 2025 - Title updated and wording amended to clarify the intent. Applied to NC V6 standards.
Amenities – Sandwich van as a food outlet - KBCN0557
A food truck/ mobile catering service would not be sufficient to meet the criteria for this issue.
The aim of this Issue is to assess the location of the built asset relative to amenities.
Amenities – Vending machine as a food outlet - KBCN0653
A vending machine can be considered as a food outlet if a range of items, as can be reasonably expected, are for sale to meet the needs of the building users and it is confirmed to be a permanent fixture.
Bristol Transport Access Level (BrisTAL) - KBCN1426
BrisTAL is no longer being updated, and the platform may no longer be available. Therefore, the Accessibility Index (AI) output from BrisTAL is no longer compliant with BREEAM.
Previously, BrisTAL offered an Accessibility Index (AI) that measures the level of public transport connectivity within the city of Bristol, based on the PTAL method, and could be used as evidence of compliance with the AI for BREEAM. Now, Bristol projects will need to calculate the AI using the BREEAM transport tool.
03 08 2022 - Updated to clarify that the dataset used must be current at the time of the transport assessment, but this does not need to be updated at post-construction stage
03 12 2025 - This route is no longer applicable for assessments registered after this update.
Campus or campus-type developments – Entrance to consider - KBCN1726
For assessments on sites with multiple buildings (e.g. education campus, business or industrial parks):
- Distances to amenities and public transport nodes can be measured from the site’s main entrance if ≥80% of buildings are within 1000 m. Otherwise, use the assessed building’s main entrance, and in such cases, where multiple buildings are included, calculations must always be based on the worst-case scenario (the entrance furthest from the node or amenity)
- Where the site has more than one main entrance, either entrance may be used for the calculation.
Purpose: To ensure fair assessment on large sites and to encourage the provision or location of amenities and public transport nodes within or at the periphery of the site.
01-Oct-2026 - Applicability to INC2016 confirmed
26-Sep-2025 wording update for clarification and including BIU
Car sharing – aim and principles - KBCN1510
Aim
The aim of this measure is that the asset’s management establishes, promotes and administers a process which encourages building users to share private car journeys to and from work, reducing the number of cars used for this purpose.
Principles
A car sharing group will, generally:
- Be available to all building users who normally travel to work by private car.
A car sharing group is not:
- A vehicle hire/loan scheme.
- Intended to offset journeys which would otherwise have been made by public transport or active travel modes (e.g. walking or cycling).
The criteria do not prescribe what terms and conditions should be implemented and, whilst the above principles should generally be followed, specific arrangements may vary.
Evidence and justification must always be provided to demonstrate that the above aim is met.
21-Jul-2026 - Scheme applicability updated. Title updated for clarity and consistency.
Car sharing – calculation of priority spaces - KBCN0282
The calculation of priority spaces for car sharers should account only for the car parking capacity that is dedicated to the staff working in the building, without considering spaces for customers or visitors.
Car sharing spaces should be clearly segregated from customer / visitor parking areas.
21-Jul-2026 - Scheme applicability updated.
06-Sep-2023 - Title updated to align with naming protocol.
23-Mar-2017 - Note added clarifying requirement for segregation.
Car sharing – location of priority parking - KBCN0796
Priority spaces for car sharers need to be located in the nearest available parking area to the main building entrance or to an entrance regularly used by the car sharers.
For refurbishment projects, this applies regardless of whether external works or changes to car parking areas are within the scope of works.
Assigning and clearly marking out the location of priority parking spaces is a measure that can be taken by any project regardless of scope, provided there are suitable external parking areas.
21-Jul-2026 - Scheme applicability updated. Wording expanded to clarify how KBCN applies to refurbishment projects. Title updated for consistency.
22-Sep-2022 - Applied to UK NC 2018.
Car sharing – speculative projects - KBCN0878
This measure will generally be unavailable to speculative projects.
To fully implement the car sharing option, the building occupants need to be known and signed up to a car sharing scheme in line with the criteria.
21-Jul-2026 - Scheme applicability updated. Title updated for clarity.
Community transport schemes in rural areas - KBCN00013
In rural areas, where scheduled public services are insufficient to gain credits via the calculation of the Accessibility Index, community transport schemes, including 'on-demand services', can be used to achieve the 'dedicated bus service' option. In such cases evidence must be provided to demonstrate:
- It serves a rural area
- It is available to all potential users
- The service is established at the time of the assessment being submitted
- The service is of an appropriate scale for the community it serves
Content reworded to highlight the availability of the on-demand service to all potential users. 24/04/2017
Cycle spaces – Minimum and maximum requirements - KBCN0637
These remain applicable where the 50% reduction allowed for building locations with a high level of public transport accessibility is in effect.
This means that, for instance, a large retail will still need to provide at least ten customer cycle storage spaces and could meet compliance with a maximum of fifty.
22-Nov-2023 Scheme applicability updated.
18-May-2017 Previous KBCN on large retail adapted to include any minimum requirement for cycle storage spaces.
Cycle spaces – Compliant types of storage - KBCN0257
Due to the number of different types of cycle storage facility available and the variation in site conditions, BREEAM New Construction is less prescriptive about the dimensions and type of cycle parking which can be used to demonstrate compliance. The Assessor is expected to exercise their professional judgement to determine whether the cycle parking spaces meet the aims of the Issue and the requirements listed in the compliance notes.
BREEAM is used to certify buildings, not products. Cycle parking systems cannot, therefore, be considered inherently 'BREEAM compliant'. These must be assessed in context with reference to their location and the intended user profile.
29/01/2024-made applicable to HQM
Cycle Spaces – Electric cycle charging stations - KBCN1238
Electric charging stations can be considered as compliant, provided they also meet the criteria for cycle storage spaces.
However, where these are dedicated spaces, (ie they are not available for non-electric cycles), these should not constitute more than 10% of the provision required for compliance.
Cycle spaces – Folding bicycles and scooters - KBCN00024
The provision of cycle storage that is only suitable for folding bicycles or scooters is not compliant.
Providing reduced storage space for folding bicycles or scooters in place of compliant cycle storage may limit future travel options.
14 03 2018 Wording clarified and reference to scooters included.
Cycle spaces – Large retail - KBCN0528
For large retail developments that provide at least 50 customer cycle storage spaces, this meets the requirement for customer spaces. The requirement of one cycling space every 10 staff needs to be met in addition to this.
Cycle spaces – Prominent location - KBCN00053
The requirement to provide cycle storage facilities in a prominent location on site, within view of building users, is intended to encourage use through advertising their presence to building users. Providing these facilities inside the assessed building, such as in the basement, may be compliant so long as there is prominent signage to indicate their location to all building users.
Cycle spaces – Provision for extensions - KBCN0707
When assessing an extension to a building, partial refurbishment or a stand-alone building, which extends an existing facility to be occupied by the same building users (such as a classroom block in an existing school), a site-wide approach should be used to determine the number of new, compliant cycle spaces required.
In such instances a stand-alone approach cannot generally ensure that the new cycle spaces for the assessed extension would be dedicated and available to the occupants of the assessed extension, refurbishment or building. This can only be used where it can be demonstrated that the use of the new cycle storage can be effectively restricted to only those using the assessed extension, either by effective positioning and or management.
Cycle spaces – Provision for regular, large visitor numbers - KBCN0546
Where there are large numbers of visitors on a regular basis, provision of cycle storage for visitors should be based on the maximum number at any given time.
This is to ensure that at peak times enough cycle storage is provided.
Cycle spaces – Public cycle spaces - KBCN1057
Existing public cycle spaces cannot contribute to compliance in BREEAM UK schemes
These are outside the influence of the design team and building operator and it cannot, therefore, be guaranteed that these will be available to building users.
Cycle spaces – Similar buildings assessments - KBCN0570
Where cycle storage and/or facilities are provided for individual units, a site-wide approach cannot be used to include all units. If, however, these are a shared facility, provided in a suitably-located communal area, this may be acceptable.
When assessing using the 'similar buildings' approach, each of the similar buildings has to be assessed separately and credits have to be awarded, based on the worst performing building.
14 03 2018 Clarified to account for suitable shared facilities
Cycle spaces – Small retail – multiple units - KBCN0187
In a development of multiple small retail units, to achieve credit, 10 compliant cycle storage spaces in total are required where it can be shown that these are accessible to all units. However, where such developments consist of multiple units over a large area or are separated by barriers such as roads, the assessor should ensure that the provision is both adequate and conveniently located for all units.
The 50% reduction allowed for building locations with a high level of public transport accessibility is not applicable in this case.
17/11/2016 Note related to the 50% reduction added.
14/03/2018 Note added regarding multiple units over a large area or separated by barriers.
Cycle spaces – Timing of installation in phased projects - KBCN00015
Where cycle storage cannot be installed at construction stage, due to phasing and / or pending demolition works, compliance may still be demonstrated provided:
- Clarification and justification is given for why the storage is not currently available.
- A written contractual agreement is in place to provide BREEAM compliant storage within a clear timescale.
- Alternative storage is provided in the meantime that allow bikes to be easily stored and removed, with the ability to be locked securely against a fixed structure.
The methodology above applies to cycle storage only, and cannot be applied to provision of cyclist facilities (such as showers and lockers) which must be assessed as normal.
This is to allow flexibility within the project programme for the installation of the final, permanent BREEAM-compliant cycle storage whilst still ensuring adequate cycle storage is available during the construction phase.
Cycle spaces and facilities – Rounding calculations - KBCN0445
The calculation for the required cycle spaces and facilities must always be rounded up. If the calculation works out as 5.3 cycle spaces, 6 cycle spaces must be provided.
To determine the requirements for developments with multiple types of building user, calculate the requirement for each user group separately (rounding up to the determine the number of spaces) and then add the number of cycle spaces for each user group together.
04/10/2018 Wording amended to clarify the correct calculation method for developments with multiple user groups.
Cycle spaces – Determining compliant provision where occupancy is unknown - KBCN1741
Where occupancy is unknown, the default occupancy rates given in the table in the Additional Information section of BREEAM issue ‘Tra 04 - Maximum car parking capacity’ can be used to help determine a default number of users.
Alternatively, the number of building occupants in an existing development of similar type and size can be used. The assessor must justify the methodology and number of spaces provided in their certification report
Cycle storage – new spaces in the public domain - KBCN1410
Where it is not possible to locate short-term visitor/customer cycle storage spaces within the assessment boundary, these may be provided in a suitable and convenient location within the public realm.
The assessor must be satisfied that there is legal agreement and a long-term commitment to the provision of the spaces.
All relevant criteria must be met, however, where justified, the requirement for overhead covering can be waived.
BREEAM accepts that for cycle storage spaces within the public realm, there may be restrictions on the ability to provide overhead covering.
Cycle storage accessible through staircase - KBCN0639
While BRE does not rule out the possibility for cycle storage to be accessed via a staircase, health and safety considerations must be made, especially with regards to wet, icy and dark conditions.
On reflection of the above, the assessor should be satisfied that the cycle storage location is easily accessible.
Cyclists’ facilities – Adequately sized lockers - KBCN0961
The requirement for adequately sized lockers is so that cyclists have a dedicated space to store their cycling equipment and clothes. It is not compliant for the space requirement to be met by providing two or more inadequately-sized lockers for each cyclist.
Requiring cyclists to separate their equipment into different lockers/storage spaces could create a barrier to uptake of commuting by bicycle.
Cyclists’ facilities – Combining different facilities - KBCN0683
Cyclists' facilities can be combined, provided that all relevant compliance requirements are met and it is demonstrated that there is no conflict impacting on their use. For example, compliant showers can be combined with compliant lockers in one room, subject to the principle below.
For combined facilities to count as multiple facilities, they must be capable of being used independently of each other at the same time (where relevant) with reference to any space requirements, access, gender and privacy issues.
11 Jan 2023 - Applicability to BIU V6C confirmed
10 Feb 2022 - Updated to clarify that facilities can be combined where there is no conflict.
Cyclists’ facilities – Matching additional cycle spaces - KBCN00093
The minimum number of showers/lockers/changing facilities required for BREEAM compliance is determined by the minimum number of compliant bicycle spaces required, not by how many total compliant bicycle spaces have been provided. Where more than the minimum number of compliant cycle spaces has been provided, there is no requirement to provide more than the minimum number of showers/lockers/changing facilities.
01 Feb 2022 - Wording clarified and applicability to BIU V6C confirmed
Cyclists’ facilities – Multi-residential / residential institutions - KBCN0967
Where there is a BREEAM requirement for residents, compliant facilities within their accommodation can be considered as cyclists' facilities. Separate facilities for staff must be provided as required to achieve compliance.
22 Aug 2023 Applicability to BIU V6 Commercial confirmed.
Cyclists’ facilities – Provision of only one shower - KBCN0566
Where only one shower is provided, this needs to cater for users of both genders.
For a changing facility to count as an additional amenity, it must be capable of being used independently of any showers, otherwise it could not be considered as two facilities.
A shower which is a mixed gender facility must be capable of being used privately. As such, it requires adequate private changing space associated with it.
Amended to provide further clarification and to add the general principle.
10/11/2016
Cyclists’ facilities – Shell only/shell & core assessments - KBCN0882
Cycle parking must be provided as part of the base-build for all assessment types.
Where compliance is sought for additional cyclists’ facilities, the developer should provide all aspects of the installation which fall within the scope of their work and facilitate the future completion of any aspects which do not.
For shell & core assessments, if additional facilities, such as showers and drying space, are not provided in core areas and internal walls are not provided to tenanted areas, these must be indicated on design drawings and all relevant services provided. This would include capped-off supplies and electrical points as necessary in order to facilitate the completion of the compliant facilities by the tenant.
Where internal walls are within scope, a compliant changing area must be provided, however for lockers, compliance can be achieved by providing a design drawing showing that there is an adequately sized and suitably located space for the required number of compliant lockers.
The developer should do as much as they can, within the scope of their work, to facilitate the future installation of compliant facilities and should not do anything which would make future installation more onerous.
01 Oct 2024 - Addition paragraph added to clarify the approach for changing areas and lockers.
25 May 2018 - Wording amended to clarify the intent.
Cyclists’ facilities – Shower provision for male and female users - KBCN0536
Where a deviation from the guidance for a 50:50 split can be fully justified, (for example, based on actual occupancy data from a similar development of the same building type) this can be deemed as compliant by the assessor.
If such justification cannot be provided but design teams wish to provide a flexible arrangement for showers to suit the anticipated building occupancy, providing unisex showers accessible to all building users would be acceptable.
Cyclists’ facilities – Visitors - KBCN00014
Where the cycle spaces requirement is based on the number of staff plus visitors, customers or patients, the number of cyclist facilities required to demonstrate compliance is based on the number of cycle spaces for staff only.
Visitors, customers or patients would not be expected to have access to showers and lockers within a building.
Cyclists’ facilities – Within toilet facilities - KBCN00050
To comply with the criteria for cyclist facilities, showers should not obstruct the use of other facilities. Where a shower is located in a room with a WC, this cannot be considered compliant, unless it can be unequivocally demonstrated that the WC is provided over-and-above the requirements of relevant standards or regulations for general and disabled WCs.
To ensure that there is no conflict between the use of general or disabled WCs and the use of cyclist facilities.
25.10.18 KBCN reworded to improve clarity.
Dedicated transport service - KBCN1823
A dedicated transport service, such as a dedicated bus, coach, or minibus, provided or managed by the building owner or management, can be considered for any building type with a fixed usage pattern. The dedicated transport must provide a transfer to the local population centre or public transport interchange, or it may be a door-to-door service.
Generally, a dedicated service must be available to all regular building users. However, for primary and secondary schools, a dedicated service available to students only can be considered compliant
Demand-based bus services in AI calculation - KBCN1338
Demand-based bus services operated by public transport providers can be included in the calculation of the Accessibility Index. The project team will need to determine an average number of stops per hour to allow input into the AI tool.
Education – Boarding schools - KBCN00089
The number of cycle spaces and facilities should be calculated based on the number of day pupils and boarders and these should be available to pupils and staff as appropriate.
For boarders, the cycle storage and cyclists' facilities requirement may depend upon a number of factors, such as the age of the pupils/students, distance of the residential accommodation from the school buildings and the school’s policy on cycling. Therefore, the assessor is required to calculate the appropriate number of cycle storage spaces and facilities for pupils and staff based on the relevant criteria.
Calculations, justification and supporting evidence should be provided in the assessment report.
14 03 2018 - Heading and wording clarified and amended to remove requirement for assessors to submit a technical query prior to certification.
Education – Different age ranges and/or non-acute SEN - KBCN0224
For a combined school campus the number of cycle storage spaces and compliant facilities will need to be calculated individually for each user-group of the building; e.g. the number of facilities for nursery schools, primary schools and secondary schools should be calculated as per the criteria defined for each of these education types and totalled.
Where this includes non-acute SEN facilities and the unusual structure of the classes prevents standard assessment, the assessor should use their judgement to determine whether to apply the pre-school criteria or base on the total number of staff and students.
While within the scoring and reporting tool the dominant education building type category will be selected, calculations need to be provided as supporting evidence, with the assessor's comments/notes used to clarify the calculation used to demonstrate compliance.
14 03 2018 - clarified and key information incorporated from KBCN0424
Education – Primary schools - KBCN1056
Cycle spaces:
Cycle parking spaces are intended for the use of pupils and staff and are calculated based on the number of form groups per year as per the technical guidance.
Additional facilities:
Compliance for pupils can be based on the provision of adequate space in a cloakroom to store outdoor clothing and cycle helmets.
The number of additional facilities for staff should be calculated based on 1 locker per 10 members of staff and 1 shower per 10 lockers’, subject to a minimum of one shower being provided.
In a primary school, pupils are not expected to have access to private showers or other cyclists’ facilities.
22/11/2019: Clarification added regarding the number of additional facilities.
Education – Secondary schools - KBCN0119
Cycle spaces:
Cycle parking spaces may be shared between students and staff, and are calculated based on the total number of staff and students as per the technical guidance.
Students:
Compliance for students can be based on the provision of compliant lockers only based on the following logic:
• Where secondary schools have sports facilities, compliance shall be based on the provision of compliant lockers only. The provision of showers or changing spaces is assumed to be included with the sports facilities are do not need to be assessed.
• Where secondary schools do not have sports facilities, cyclist facilities are assessed as per the technical guidance.
Secondary schools will, in almost all cases, will already have sports facilities including enough showers and adequate changing facilities to meet the BREEAM requirements by default. For most students however, the most important facility is likely to be adequate locker storage rather than showers or changing facilities.
Staff:
Separate shower and changing facilities must be provided for staff. Locker facilities may be shared with students if appropriate, but staff lockers should be suitably located in relation to the other staff facilities.
The number of showers for staff should be based on the total number of staff and one shower for every 100 staff*, subject to a minimum of one shower being provided.
*This is based on 1 cycle storage space per 10 staff, and 1 shower per 10 cycle storage spaces.
10 03 2020 Further clarification of the intent
14 03 2018 Heading and wording clarified
Electric Vehicle (EV) Charging – Shared Parking for New Buildings, Extensions, and Phased Developments - KBCN1827
The required number of EV charging points must be based on the total number of parking spaces that
serve the assessed building. This total includes both
existing spaces and
any new spaces associated with the project.
Where parking is shared across a wider site, the “associated” number of spaces refers to the amount of parking the assessed building is expected to rely on for its occupants. A
proportional allocation calculation must be used to determine this number.
Example:
If a project sits on a site with 1,000 shared spaces but the new building’s occupancy requires only 100 spaces, the EV requirement is calculated based on
100 spaces, not the full 1,000.
- General Requirements
- Defining the parking that counts. Use a proportional allocation method to determine how many spaces in a shared car park are associated with the project.
- Short-stay exclusion: Short-stay spaces with a maximum stay of 15 minutes (e.g., pick-up/drop-off bays) are excluded from the EV calculation.
- EV Charging points location: EV charging points should be installed as close as possible to the building’s main entrance to ensure convenient access for the building users.
- Existing infrastructure: Existing EV charging points in a shared car park can only be counted when:
- They exceed the BREEAM requirement for the buildings they were originally installed to serve,
- They meet current BREEAM requirements, and
- They form part of the new project’s allocated parking.
- No “legacy” exclusions: Existing parking spaces cannot be excluded simply because they predate the BREEAM assessment. If the spaces serve the assessed building, they are in scope.
- Operational policy. It is recommended, but not mandatory, that building management implement operational measures (e.g., signage, permits, digital access controls) to help ensure that EV spaces are used by the intended building users.
- New Buildings on a Site or Extensions
- Calculation basis for new buildings or extensions, EV requirements must be based on the total parking demand associated with the project, including both existing associated spaces and any new spaces created.
- Proportional allocation formula
- Determine the project’s share of the total site parking using either GIA or occupancy.
- Allocated project parking = Total site parking × (Project GIA ÷ Total GIA), OR
- Allocated project parking = Total site parking × (Project occupancy ÷ Total occupancy)
- Phased Development
- Current Phase: The EV calculation should be based on the parking demand of the phase under assessment, including the existing infrastructure and any new parking spaces delivered in that phase.
- Existing Infrastructure: EV charging provision installed in previous phases may count towards compliance where it meets the required threshold for the current phase
- Future Phases: Provisions in future phases may be counted only if secured by a legally binding commitment (such as a signed contract or planning obligation) with a confirmed delivery timeline.
Electric vehicle (re)charging stations/points/spaces - KBCN0934
For BREEAM purposes, a vehicle charging station/space includes a facility that is dedicated to charging vehicles. Provision of a mains-powered electrical socket will not be deemed compliant.
13 October 2023 - Title and wording updated to align with terminology used elsewhere in our guidance.
Electric vehicle charging stations - KBCN0684
As per the 'Alternative transport measures' criteria, the percentage requirement for electric charging stations should be based on the total car parking capacity for the building.
Where the assessment covers only part of a building or development this must be based on the total car parking capacity unless the parking for the assessed development is clearly segregated and available only for the use of its building users.
23 03 17 Reference to car sharing spaces removed. See also KBCN0282
Electric vehicle charging stations (EVCS) – Priority spaces - KBCN1429
The current criteria for EVCS do not address provision for priority spaces, such as those allocated to disabled use and car sharing.
The assessor and design team should, therefore, take a pragmatic approach to this and, where the overall number of required EVCS permits, an appropriate proportion of these should be provided for priority spaces. This will not be deemed as 'double-counting' as the number of EVCS required should be considered independently of other requirements.
The intent is that electric vehicle charging spaces are available to all building users (where possible).
Electric vehicle charging stations – shell & core assessments - KBCN1247
For BREEAM NC shell only/shell & core, RFO Parts 1 and 2 only and partially-fitted residential assessments, compliance can be demonstrated by installing all the necessary infrastructure, (i.e. capacity in the connection to the local electricity distribution network and distribution board, as well as sub-surface ductwork to receive cabling to parking spaces), to enable the simple installation and activation of charging points at a future date.
18/10/2021 Applicability to BREEAM Scheme and Assessment Type clarified, in line with the intent.
15/11/2019 Incorrect reference to pre-installation of 'cabling' removed.
Future transport nodes - KBCN0966
Where a transport node is currently inactive but will become active soon after project completion, it can be included when calculating the existing AI.
To demonstrate this, confirmation of the start of service date and service frequency from the appropriate public transport authority or company will be required.
Greater Manchester Accessibility Level (GMAL) - KBCN1394
The Greater Manchester Accessibility Levels (GMAL) method has been created to provide a way of measuring the density of public transport provision at any location within the Greater Manchester region. It is derived from the Public Transport Accessibility Level (PTAL) approach used by Transport for London. As such, the Greater Manchester Accessibility Index (GMAI) scores generated by the GMAL method can be used as evidence of compliance against the BREEAM and HQM Accessibility Index requirements. Please note that project teams must ensure that they use the version of the GMAL dataset that is current at the time the transport assessment is undertaken. This is available from the data.gov.uk website (
https://data.gov.uk/dataset/d9dfbf0a-3cd7-4b12-a39f-0ec717423ee4/gm-accessibility-levels-gmal).
02 08 2022 - Updated to clarify that the dataset used must be current at the time of the transport assessment, but this does not need to be updated at post-construction stage
Hotels and other short stay accommodation – cycle storage unit of measure - KBCN0676
The cycle storage requirement for hotels and other short‑stay accommodation is
1 space per 10 staff. Guests or visitors staying at the hotel are excluded from the calculation.
Where a hotel includes on‑site facilities such as conference spaces, restaurants, or gyms, visitors to these facilities should also be included in the cycle-storage calculation:
1 space per 10 guests.
Specific Note for Refurbishment and Fit Out International 2015
Table 36 in the technical manual incorrectly refers to “1 staff and 1 visitor, or 1 bed.” Please ignore this error and follow the guidance above.
16-Feb-2026 - Wording update to be applicable across multiple BREEAM Schemes
20-Oct-2025 - Guidance clarified and updated to align with all current BREEAM scheme guidance.
23-Jul-2018 Wording added to include clarification on what to base the calculation of cycle spaces on.
Technical manual to be updated accordingly in next re-issue.
ModeScore Sustainable Transport certification - KBCN1705
Achieving
ModeScore Gold or Platinum certification may be used as supporting evidence
to award credits for the Transport issues listed in the table below. This alignment is permitted
provided that the BREEAM technical criteria are demonstrably met.
| Scheme |
Issues |
Credits Achievable via ModeScore |
| BREEAM International NC 2016 and V6 |
Tra 03a Alternative modes of transport |
2 + Exemplary credit |
| Tra 03b Alternative modes of transport |
2 + Exemplary credit |
| Tra 04 Maximum car parking capacity |
1 |
| BREEAM UK NC 2018 and V6 * |
Tra 02 Sustainable transport measures |
10 |
| BREEAM Int RFO 2015 |
Tra 01 Sustainable transport solutions |
5 |
| Tra 04 Maximum car parking capacity |
2 |
| BREEAM UK RFO 2014 |
Tra 01 Sustainable transport solutions |
3 |
| Tra 03 Cyclist facilities |
2 |
| Tra 04 Maximum car parking capacity |
2 |
| BREEAM In Use Commercial and Residential (International and USA) |
Tra 01 Alternative modes of transport |
8 |
| Tra 02 Proximity to public transport |
3 |
| Tra 04 Pedestrian and cyclist safety |
2 |
| BREEAM UK NC Residential V6.1* |
1.1 Public transport availability |
3 |
| 1.2 Sustainable transport options |
17 |
Evidence Requirements
To award credits using this route, the Assessor must:
- Submit the ModeScore Certification and Assessment Report.
- Provide a mapping statement demonstrating how the targeted BREEAM criteria have been met using the relevant ModeScore criteria.
- Provide any Supplementary Evidence identified through the mapping process.
Scheme-Specific Provisions*
- BREEAM UK New Construction (2018 & V6) – Tra 02
Credits may be awarded provided the prerequisite for a Transportation Assessment and Travel Plan (Criterion 1) has been met.
- BREEAM UK New Construction Residential V6.1 Issue 1.2
Credits may be awarded provided the prerequisite for Home Information (Criterion 1) has been met.
About ModeScore Sustainable Transport certification:
ModeScore assess and certifies sustainable transport facilities and services in buildings. ModeScore encompasses ActiveScore within its assessment criteria, covering four pillars of sustainable transportation while incorporating accessibility into each:
- Public Transportation
- Environmentally-Friendly Private Vehicles
- Active Transportation
- Site-Wide Mobility
ModeScore evaluates the connectivity potential of any building, anywhere, offering four levels of certification and a total scorecard of 120 points. ActiveScore (Travel Facilities) counts for 10 points:
- Certified (0-39%)
- Silver (40-59%)
- Gold (60-79%)
- Platinum (80-100%)
See more information and details at https://modescore.com/
20/04/2026 - Update including BREEAM Residential 6.1
No car parking provision - KBCN00059
Where the assessment criteria are applicable to a building that has no car parking spaces and where there are no parking spaces accessible to building users, the benchmarks can be considered to be met. If, however, parking is shared with other buildings or parking spaces are available on a campus-type site then the provision must still be assessed.
No data for AI at Design Stage - KBCN0551
If there is insufficient data for a future transport service to include this in the calculation of the AI at the Design Stage, it should not be accounted for.
If at Post Construction stage the data is available, this can be incorporated.
Whilst certain Design Stage requirements can be based on commitments to achieve a certain performance, this must be based on verifiable data.
16/04/18 Wording amended to clarify that this applies to future services and to allow applicability to UK NC 2018
Obligation to provide a minimum number of car parking spaces exceeding BREEAM requirements - KBCN0401
Where it can be demonstrated (by documentary evidence) an obligation to meet a ’minimum car parking requirement’ which exceeds the BREEAM benchmarks is imposed by the planning authority, as long as no more than the stipulated minimum spaces are provided, a single credit can be awarded.
Occupancy calculation – Buildings with shift patterns - KBCN0431
In buildings with shift patterns, as shifts may overlap, the building users calculation should be based on the maximum occupancy of the building at any given time.
Occupancy rates – 24-hours consulting or treatment rooms - KBCN1258
The default occupancy rate for 24-hour consulting or treatment areas in hospitals and care homes is 0.07.
Published pending reissue of the technical manual UKNC2014/REISSUE UKNC2018/REISSUE
03.11.2021 Issue 2.0 of the UK RFO technical manual amended.
On-demand public bus services - KBCN1404
These can be recognised as follows:
- The location of the transport node should be determined as the nearest available pick-up point to the assessed building
- The frequency of the service should be considered as the published maximum wait time (or actual average wait time, if the service is established and this data is available)
- Such services, whilst they may serve multiple destinations, should be considered as a single route
- It must be demonstrated that information on the availability and how to access the service is made available to building users
This is limited to genuine on-demand bus services, which are operated as public transport with multiple pick-up and drop-off points and does not extend to private hire, taxi or other similar operations.
Park and Ride Schemes - KBCN0754
'Park and ride' bus services run from one or more car parks to a city centre or other destination to allow travellers to park their car at a convenient location and complete their journey by bus. These generally stop at transport nodes en route to allow passengers to board or alight.
Provided the service meets the aim of the Issue with reference to the guidance, they can be considered for this Issue in the same way as any other bus service.
Parking integral to development’s use - KBCN1145
Dedicated on-site parking which is integral to the function of the development can be excluded from the calculation of parking capacity. Examples could include, but are not limited to:
- Dedicated bays for police vehicles at a police station
- Parking for delivery vehicles at an industrial warehouse
- Holding bays for damaged vehicles at a vehicle repair centre
The spaces are only to be used for this purpose, and must have appropriate signage and / or markings.
Parking spaces with electric car recharging stations - KBCN00044
Electric car spaces should be included in the total number of car parking spaces calculation for maximum car parking capacity.
Whilst electric cars provide benefits in terms of reduced emissions, they do not directly reduce congestion which is one of the aims of this issue.
PTAL report supporting evidence - KBCN0230
For developments in Greater London where a Public Transport Accessibility Level (PTAL) report is provided, this report does not need to be supplemented by additional evidence to demonstrate compliance with criteria. The assessor should be satisfied that the PTAL report is current and accurately relates to the assessed site.
Public car parks - KBCN00092
Any public car parks in the vicinity of the assessed building, for which the building owners/operator are not providing some form of subsidy or an agreement with the car park operators to provide priority spaces for building staff, can be excluded from the assessment.
Public Transport Access Index (PTAI) – Buildings in Greater London - KBCN1149
For projects in Greater London, the Public Transport Access Index (PTAI) should be derived directly from the TfL WebCAT platform. When this tool is used, the BREEAM Tra 01/02 PTAI/AI calculation is not required.
Requirements:
- Baseline: Assessors must use the PTAL version that is current at the time the Transport Assessment is undertaken (Concept Design).
- Post-Construction Consistency: Once the design-stage PTAI is established, it does not need to be updated at the Post-Construction stage, even if the local transport network or WebCAT data has changed in the interim.
- Location: Access data via TfL WebCAT.
- Procedure: Follow the below technical guide to extract the specific Accessibility Index (AI) value from the WebCAT CSV export (Cell G3) for entry into the BREEAM Platform.
Locating-PTAI-via-TfL-WebCAT
04 03 2026 - Updated to clarify requirements and adding instruction for locating PTAI or AI via TfL WebCAT
03 08 2022 - Updated to clarify that the version used must be current at the time of the transport assessment, but this does not need to be updated at post-construction stage
Rounding the number of parking spaces - KBCN0602
Where the calculated number of car parking spaces is a fraction of a whole number, this should be rounded down to the next whole number to assess the issue.
Fewer parking spaces are preferable as the more sustainable solution.
Safe pedestrian routes – Definition, measurement and verification - KBCN0238
Definition
Safe pedestrian routes include pavements and safe crossing points, which may be controlled or, for example, be identified by tactile paving, a crossing island or a dropped kerb. An element of judgement may be required, in which case justification should be provided.
Measurement
Distances could be measured, for example, along a pavement, across a road at a safe crossing point and along the pavement on the other side. The distance should not be measured diagonally across a road, following the most direct route.
Verification
The assessor’s site inspection is an important aspect of the assessment and may help to confirm that all relevant information is current and can include photographs of any key areas. This can also help to identify safe crossing points or hazards which may not be apparent from a desktop study. Alternatively, web-based map data may be used to satisfy the evidence requirements at both Design and Post-Construction Stage, provided that the assessor is satisfied that this clearly demonstrates compliance and that the evidence is robust and up to date.
Where web-based navigation maps (e.g. Google Maps/Street View) are used as evidence, this must include:
• Dated and marked-up site plan or a web-based navigation map viewer highlighting:
• Current location and type of transport nodes and local amenities.
• Current route and distance from the building via a safe pedestrian route.
• Plan or map scale.
When relying on web-based evidence for post-construction stage, the assessor must, additionally, provide verification that the information provided for the nodes/amenities is still accurate and up to date.
16 Sep 2025 - Wording relating to verification updated to clarify the intent.
29 Aug 2025 - Approach to web-based map data at post-construction stage updated and related wording amended accordingly
07 Mar 2024 - No changes have been made. This appears as 'updated' due to an administrative error.
11 Jan 2024 - Wording re-structured for clarity
19 Dec 2023 - Applicability to BIU V6 confirmed
Total credits available - KBCN00095
The number of credits available is determined by building type, as detailed in the table. Where the maximum score for the Accessibility Index (AI) is not achieved, additional credits can be awarded up to that maximum for the Alternative transport measures listed in the following table.
This approach is intended to recognise the relative importance of sustainable transport solutions to different building types.
Tram services - KBCN000004
Tram services are classified as train services when assessing transport accessibility.
Visitor car parking spaces for Other Buildings (Transport type 2) - KBCN0242
For developments such as hotels and visitor centres, which have a relatively small number of staff and large visitor numbers, the guest/visitor car parking spaces do not need to be assessed for this Issue where these are separate from the staff parking spaces. However, if the staff and visitor’s spaces are combined (and not clearly segregated) then all spaces must be accounted for within the calculation for maximum car parking capacity.
The aim of this Issue, 'To encourage the use of alternative means of transport...' is intended to apply to those commuting to the building on a regular basis.
21 06 2017 Wording amended to clarify the type of building and building-user covered by this KBCN.
[KBCN withdrawn] ~ Cycle storage spaces for all range schools and non-acute SEN - KBCN0424
This KBCN has been withdrawn and is no longer valid. Please see
KBCN0224 for relevant guidance.
This is due to duplication of guidance.
KBCN withdrawn 14 03 2018:
Where assessing an all range school, the appropriate criteria should be applied for each age range. Where this includes non-acute SEN classes and the unusual structure of the classes prevents standard assessment, the assessor should use their judgement to determine whether to apply the pre-school criteria or base on the total number of staff and students. The approach taken should be fully justified.
To encourage a sensible application of the criteria in meeting the aim of the Issue
Information correct as of 19thOctober 2026. Please see kb.breeam.com for the latest compliance information.