Refurbishment and Fit Out / UK RFO 2014 / 02 - Health and Wellbeing /
HEA 06 - Safety and Security
Information correct as of 28thNovember 2026. Please see kb.breeam.com for the latest compliance information.
Designing out crime officer (DOCO) - KBCN000005
As stated in the ‘Secured by Design (SBD) New Homes 2014 Application and Checklist’ form, the Crime Prevention Design Adviser (CPDA) or Architectural Liaison Officer (ALO) has been renamed to Designing Out Crime Officer (DOCO) therefore correspondence or a copy of the report/feedback from the DOCO is acceptable as evidence for this issue.
Late appointment of SQSC/SQSS - KBCN0339
Provided the appropriate security specialist confirms that the implementation of security measures has not been restricted due to the later stage at which their involvement was sought, i.e. everything that would have been recommended can be still be implemented, then the credits can still be awarded (provided all other compliance requirements met).
Considering the security requirements at an early stage of a project should ensure that the full range of security options is still available to the project, leading to the best solution. If advice is sought later but this does not restrict the options available, then the intent of the issue can still be met.
Part 4 first fit-out assessment - KBCN0945
For a Part 4 assessment of a first fit-out to a shell & core development, where access controls and security features are already in place, compliance can be demonstrated where the suitability of existing security is reviewed and any adaptations that may be required are implemented. The SQSS who carries out the review must meet the requirements set in the manual.
Secure Government sites – Security criteria (2011-2014 schemes) - KBCN0785
Government security procedures, such as those for MoD sites, may take precedence in dealing with security risk. Therefore, the Secured by Design criteria under which this issue is assessed may not be appropriate.
However, BREEAM requires that a Suitably Qualified Security Specialist/Consultant (SQSS/C), such as the MoD security consultant, should be consulted during or prior to the Concept Design stage or equivalent, and the final design must embody the recommendations / solutions of the MoD security consultant, in line with the security criteria.
Evidence requirements
Where it is confirmed that, due to security issues, the assessor cannot provide complete evidence of the security assessment and implementation of the recommended measures, the following can be accepted:
A written statement or report from the SQSS confirming:
- Justification of why the evidence requirements cannot be met
- Details confirming their status as SQSS for the project
- Dates of their consultations and inspections
- Confirmation that all the recommended security measures have been implemented
06/07 Mar 2024 - Title updated and minor clarifications to wording. Additional paragraph on 'Evidence requirements' added
Secured by Design certificate - KBCN0772
The Secured by Design (SBD) consultation process, when undertaken in-line with the BREEAM criteria, may provide an appropriate framework for demonstrating compliance, however achieving SBD certification is not a specific requirement of BREEAM.
27/02/17 Amended to clarify that SBD framework may comply but BREEAM criteria must be met
Security – Change of SQSS and recommendations - KBCN1044
If the SQSS working on the project changes during the assessment, the recommendations of the original SQSS can be modified if the new SQSS can provide justification for this.
15 Nov 24 Made applicable to UK RFO 2014.
Security needs assessment (SNA) – Formal consultation with relevant stakeholders - KBCN1470
Providing the SQSS can provide evidence of reasonable attempts to obtain feedback from relevant stakeholders, this aspect of the SNA requirements will be satisfied.
In the event that a relevant stakeholder does not provide a response when consulted (e.g. if they do not respond following a reasonable period, or they confirm that are unable to deal with the enquiry), it would be expected that SQSS consider alternative sources of information. For example, the SQSS may decide to refer to freely-available crime data on the
Police UK website, and include a summary or analysis of this in their SNA.
13 Sep 2021 Applicability to HQM confirmed
Third party licensing or registration scheme - KBCN0902
A specialist registered with a BREEAM recognised third party licensing or registration scheme for security specialists can be considered a Suitably Qualified Security Specialist for the purposes of compliance with BREEAM Hea 06.
The following are currently recognised as a third party licensing or registration scheme for an SQSS;
• SABRE Registered Professional
Only SABRE Registered Professionals holding the designation ‘SQSS’ are recognised. A live list of SABRE Registered Professionals and their designations can be found on
www.redbooklive.com. Further information regarding the SABRE Registered Professional can be found on the SABRE website (
www.bregroup.com/sabre).
(21/03/2018) Updated to include applicability to BREEAM UK NC 2011
(19/07/2018) Updated to clarify recognition of SABRE
(03/11/2021) Issue 2.0 of the UK RFO technical manual has be amended to include this information. The information is still relevant to previous versions of the manual.
Verification of Security Needs Assessments/Security Risk Assessments - KBCN1770
Where the author of a Security Needs Assessment [‘Security Risk Assessment’ in BIU] does not meet the BREEAM competency requirements, compliance can still be achieved where the report is reviewed and verified by a qualified SQSS [‘Competent Person’ in BIU], who confirms in writing that it is accurate, appropriate and in line with industry best practice.
In these circumstances, the SQSS or ‘Competent Person’ is expected to verify and take ownership of the report and accept professional responsibility for its content.
Visual audit of site and surroundings - KBCN0685
The method of conducting the visual audit of the site and its surroundings required for a Security Needs Assessment (SNA) is at the discretion of the Suitably Qualified Security Specialist (SQSS). It can be carried out as a site visit, or through the review of relevant project information and drawings, provided the SQSS is satisfied that these are sufficient to inform their SNA & associated security recommendations.
The approach should be justifiable in terms of the scale, complexity, location and any other specific aspects of the assessed development.
24/06/22 - Applicability to UK NC2018 confirmed
Information correct as of 28thNovember 2026. Please see kb.breeam.com for the latest compliance information.