Acceptable alternative strategies to sub-metering by floor plate - KBCN00071
An alternative sub-metering strategy, not based on a by-floor-plate basis, would be acceptable provided that:
- it provides an equivalent, or more useful level of detail than sub-metering by floor plate.
- it divides the assessment in a logical manner which provides useful information to building management re: energy use.
- the approach does not conflict with requirements for sub-metering other functional areas.
The intent of sub-metering by floor plate is to allow a large homogenous function (such as office space) to be split up into smaller areas that will allow building management to monitor, identify and influence areas of high energy use. Alternatives that also meet this intent are also acceptable.
Accessibility of energy metering systems - KBCN0580
Energy metering systems should be accessible and the energy consuming end uses visible to building users, such as the facilities manager, where present, and/or other building occupants responsible for the management of the building.
Alternatives to BEMS - KBCN0149
It is acceptable for sub-meters to connect (or have potential to connect) to automated meter readers (AMR's) or similar systems, as an alternative to BEMS .
The core intent of issue Ene 02 is the monitoring of energy use, therefore if an alternative system can achieve this,it would be considered acceptable provided this could be demonstrated.
Combined sub-metering – electric space / water heating and small power - KBCN00068
For bedrooms and associated spaces in:
- Multi-residential or residential institution building types (New Construction).
- Hospitality or supportive housing asset types (BREEAM In-Use).
It is acceptable for an electric space or water heating system to be combined with lighting and small power, provided that sub-metering is provided for each floor plate or other appropriate sub-division.
For these asset types, sub-metering electric heating in multiple bedrooms may be costly and technically challenging. Where occupants have individual control but are not responsible for paying the utility bills, the building manager may have little influence on their energy consumption. Therefore, sub-metering electric heating would provide little or no benefit in meeting the aim of the issue.
06-Mar-2024 - Scheme applicability extended to V6.
15-Dec-2023 - Title updated to clarify that this approach can be applied to both space heating and domestic hot water heating, where appropriate.
Combined system for heating / cooling and domestic hot water - KBCN0329
It is permissible to have combined metering for a shared on-site or district system that combines heating / cooling, and domestic hot water generation.
In all cases, justification is provided in the QA report for the combined metering, and explains why it is not technically feasible to provide separate meters.
21-Sep-2022 Applicability of KBCN added to BIU V6. Amended to include district heating and cooling networks.
Communal Laundry Facilities – Commercial Sized Tumble Dryers - KBCN0555
Tumble dryers should be taken in to account when calculating the total annual unregulated energy consumption of communal laundry facilities with commercial sized appliances.
Heat recovery from a commercial sized tumble dryer exhaust can be used as an alternative to the solutions listed within the Ene 08 credit issue provided it will achieve a meaningful reduction of energy demand, and justification can be given as to why this method has been implemented over those recommended in the manual.
The list of equipment types and compliance requirements is not intended to be exhaustive, however where alternative solutions are proposed, the design team must provide justification and evidence as outlined above, to the satisfaction of the assessor.
Communal Laundry Facilities – Domestic or Commercial Washing Machines - KBCN0613
The table provided in the manual highlights the criteria for an appliance to be considered domestic or commercial. However, for multi-residential projects (or other building types containing laundry facilities), the BREEAM assessor should use their judgement to determine whether the appliance is commercial or domestic, and justification of the category selected must be provided. For instance, commercial and domestic sized washing machines can be defined based on load size or power rating.
Deemed to comply solutions – alternative proposals - KBCN1214
The solutions listed for each category in the Table are examples deemed to comply with the requirements, without further justification or calculations to demonstrate a meaningful reduction in unregulated energy consumption.
If an alternative solution is proposed, justification and/or calculations are required to demonstrate this.
District heating systems – fuel mix - KBCN0885
Where the feasibility study is considering connection to a district heating system and this burns a mixture of fuels, only the proportion of output generated from second generation bio-fuels (or waste incineration that complies with BREEAM requirements) can be considered for this issue.
For instance, a system burning a 25/75 mix of compliant biofuel vs fossil fuel can only count 25% of its output towards a meaningful reduction in CO2 emissions (where relevant to the BREEAM scheme) against the baseline building.
As fuel mixes may vary over time, at least one year or more of historical information must be provided to balance out any seasonal variations. Where the system is new or proposed, robust evidence must be provided of the anticipated fuel mix.
The fuel mix must be calculated based on the energy content of the input fuels in kWh.
19/12/2017 Wording clarified
Drying space in hotel/ hostel projects - KBCN0174
The Drying space issue is not applicable to projects where occupancy is transient, such as hotel or hostel type developments, but does apply to long term residential buildings.
There is little potential in reducing the energy from drying clothes in hotel and hostel bedrooms compared to long term residential buildings.
Emergency lighting - KBCN0185
Maintained systems featuring emergency light fittings which are also used for normal operation, are assessed for this issue.
Non-maintained lighting which is only activated in an emergency can be excluded from the assessment.
NC / RFO / BIU V6 Ene 17: The aim of these credit(s) is to encourage and recognise energy-efficient fittings. Non-maintained emergency lighting will very rarely be activated and in such extremes the emergency requirements must not be compromised.
BIU V6 Hea 05: Flicker is eliminated from maintained systems only.
24-Jan-2024 - Scheme applicability updated to include BIU V6.
Energy efficient laboratories – scope - KBCN1254
This Issue is also applicable to 'Offices with Research and development areas' and other buildings with research and development facilities that contain laboratory space and containment devices/areas.
Technical manual to be updated accordingly in next reissue.
Energy sub-metering – Single occupancy & function - KBCN0491
In large buildings of single occupancy/tenancy where there is only one homogeneous function (e.g. hotel bedrooms, offices), sub-metering should be provided per floor plate.
Escalators or moving walks – variable speed drive - KBCN1621
The requirements refer to 'a load sensing device that synchronises motor output to passenger demand through a variable speed drive'.
The intent is that the inverter must operate full-time to moderate output based on passenger demand.
Evacuation lifts - KBCN0437
Evacuation lifts, which will be used during an emergency only, can be excluded from the relevant BREEAM criteria. However, if these lifts are used during the normal operation of the building, then they still need to be assessed.
Extending a lift shaft - KBCN0802
Where the scope of works regarding a lift only includes extending the lift shaft to other floors, then assessment of this lift is not appropriate. Where changes are made to the lift system, then assessment is required.
Where changes to lift systems are made, these lifts need to be included in the assessment to encourage specification of energy efficient transport systems.
External lighting inside wider building - KBCN0906
Where a building undergoing assessment is located inside of another building, for example a retail unit within a shopping centre, Ene 03 External lighting and Pol 04 Reduction of night time light pollution should be assessed as follows;
Ene 03
'External lighting' that is inside of the wider building, using the example above the lighting is external of the retail unit itself but inside of the wider shopping centre, criteria relating to the luminous efficacy should be applied as presented within the manual. For the criteria relating to controlled for prevention of operation during daylight hours and presence detection in areas of intermittent pedestrian traffic, however, instead of demonstrating that the lighting is not operational during daylight hours, it should be demonstrated that the lighting is not operational outside of the operational hours of the wider shopping centre. Any external lighting within the scope of works being assessed that is located outside of the wider shopping centre, for example if the retail unit had an entrance or exit that leads on to the street outside, this would need to be assessed against the criteria presented within the manual.
Pol 04
If the building undergoing assessment has no external lighting that is outside of the wider building, it can be considered that the building has no external lighting. However, as above, any external lighting within the scope of works of the assessment that is located outside of the wider building will need to be assessed as the criteria is presented within the manual.
10/05/2019 Reference to specific criteria numbers removed and made applicable to UK NC2018
Feasibility study – comparison with connection to existing LZCs - KBCN0563
In carrying out a feasibility study (covering all the areas required as stated in the manual) the primary intent is to demonstrate to a reasonable level of certainty that the chosen LZC is the most appropriate of all those available.
Some of the options (for example community heating/cooling schemes) may not allow for a simple like for like comparison but a comparison can be made overall across many factors. For example in a community heating scheme the life cycle costing estimate might need to be simply the cost of using and maintaining the system for the measuring period, if upfront costs and payback period information is not available. Similarly for an existing community scheme, planning would not be a barrier but land use and noise impacts could be compared.
The feasibility study must include a comparison of all criteria and for it to show that each has been factored into the final option being made. While some options may provide information in different formats and differing levels of detail making direct comparisons not straightforward, a comparison can still be made and this should aim to be as comprehensive and representative as possible. This will serve to demonstrate with reasonable certainty that the chosen option is the most appropriate.
Head-end systems for smart meters - KBCN0933
As the central component in an Advanced Metering Infrastructure (AMI), head end systems allow data communication and collation from a large and disparate set of smart meters.
Where smart energy meters and sub-meters are to be installed, a head-end system is required for any strategy utilising this technology to be considered for compliance.
Individual and shared drying facilities in larger developments - KBCN0260
Individual bedrooms: an adequate internal or external space with posts and footings, or fixings capable of holding:
- Two metres of drying line per bedroom where drying facilities are provided in each room, OR;
- Two metres of drying line per bedroom for the first 30 bedrooms, plus one metre of drying line for each additional bedroom where drying facilities are shared.
This is to avoid over-provision of shared drying facilities in larger developments.
Laboratory facilities not restricted to building type - KBCN1340
In order to allow buildings with appropriate laboratory facilities to assess the energy performance of their labs, all assessments containing laboratory space and containment areas will be able to assess Issue ‘Energy efficient laboratory systems’, even where the relevant technical manual confirms that the Issue is not applicable to this building type. The Issue remains not applicable to primary and secondary school buildings given the limited scale of their laboratories.
Assessments registered prior to 1 July 2019 have the choice to follow the guidance as stated in the technical manual. They can exclude laboratories by responding negatively to the questions regarding laboratory facilities. For assessments registered after this date, all projects containing laboratories within the scope of the assessment should include the Issue in the assessment.
LCC – LZC energy sources discounted - KBCN0606
When sufficient information can be provided to justify that LZC energy sources are not appropriate for the development, the LCC analysis, for those LZC sources, do not need to be included in the feasibility study.
The feasibility study (covering all the areas required as stated in the manual) intends to demonstrate, to a reasonable level of certainty, that the chosen LZC is the most appropriate of all those available.
Lifts with speeds 0.15m/s or less - KBCN1146
Lifts with speeds 0.15m/s or less fall outside the scope of ISO 25745 and can, therefore, be excluded from the assessment of this Issue. This applies, for example, to lifts in single dwellings or those installed in other low-rise buildings, specifically for the use of persons with impaired mobility.
LZC feasibility study – timing - KBCN1052
If a feasibility study is undertaken at a stage later than Concept Design, this must include an explanation for any local LZC technologies ruled out because of constraints arising from the late consideration. Compliance may still be achieved if other LZCs are feasible and the criteria are met. If the late completion of the feasibility study resulted in no LZC being installed, the credit must be withheld.
LZC technologies – energy centre or other LZCs connected at a later stage - KBCN0267
If a project specifies LZCs that have been proposed in the feasibility report which reduce emissions, and/or will be connected to a site-wide energy centre operational at a later stage of the phased development, after the Post Construction Stage review has been submitted, the Energy and Pollution issues can be assessed as follows:
In a phased development where the primary heating system will be upgraded at a later stage than the building being assessed, a commitment to install the new heating source must be made in the General Contract Specification (as per the BREEAM requirements). BREEAM does not specify a particular time for phasing as it is difficult to set parameters, however as a rule building users should have to wait the least time possible before they can use the upgraded heating source.
For the quality audit, two Energy model outputs/EPCs must be produced at the final stage - one with the actual interim system installed for building control, and one for the BREEAM assessment which can include the predicted energy from the proposed energy centre. Additionally, the legally binding general contract specification for the new heating source must be submitted with details of the timescales proposed for the completion of the second phase of work. Where this approach is to be followed BREEAM must be consulted in each case to ensure that the arrangements are sufficiently robust to award the credits.
BREEAM seeks to recognise the environmental impacts of a building's energy use throughout its life, therefore temporary arrangements can be accommodated, provided there is robust evidence on future connection to the permanent systems.
24/08/2022 - Applicability to UKNC V6 confirmed
LZC technologies – planning conditions and restrictions - KBCN0535
Where a mandatory planning condition exists (eg to attach to a District Heating Scheme), this will clearly affect the number of options available in a feasibility study. In such cases, compliance can still be achieved where evidence on the planning condition restrictions is provided, and it is clarified how this excludes other technologies from being considered.
The feasibility study will still need to be carried out to cover the remaining energy needs of the building (eg Electrical and lighting load in the case of a district heating scheme).
LZC technologies – shell only feasibility study - KBCN0409
For a shell only project, compliance may be assessed on the built form only i.e. demonstrating that sufficient space and clearance for the installation of future LZCs has been considered, the built form is suitably sited, and that massing and orientation are optimised for the future systems.
New build extension using existing lifts - KBCN0444
Where the assessment is only of a new build extension (and not the existing building), lifts present in the existing building fall outside the scope of Ene 06 and do not need to be assessed. The applies only when the lifts are not being renewed or undergoing a major refurbishment.
New EU energy labels - KBCN1445
Background
In recent years, the market for domestic-scale appliances has seen excellent progress, with increasingly energy-efficient products becoming widely available. Consequently, the A-rated category was extended over time to include A+, A++, and A+++ ratings. Meanwhile, the lower ratings, such as E, F and G have become increasingly rare. It was clear that an adjustment to a new, simpler set of ratings was required.
Statutory Changes
From 1
st March 2021, the European Commission requires new, updated energy labels of A to G for dishwashers, washing machines, fridges and electronic displays.
Lamps will require the new ratings from 1
st September 2021 and requirements for re-labelling tumble dryers are yet to be confirmed.
This means:
- A+ to A+++ will transition mainly to C through to F
- A and B will initially apply to very few products
- G ratings will be phased out, with F ratings to follow
Changes for BREEAM and HQM
As a result of the introduction of the new EU ratings and in order to maintain the original intent of the BREEAM criteria, the approach for our schemes has had to change.
It is not possible to establish direct equivalence between the old and new energy labels, therefore the updated approach will be to recognise the best-performing 25% of each appliance type, based on a comprehensive market sample. The table below shows how this translates into the new EU Energy Labels for different appliance types.
Appliance type
|
Rating required
|
Fridges, fridge-freezers, freezers
|
E
|
Washing machines
|
B
|
Dishwashers
|
D
|
Washer-dryers
|
D - D
|
This approach will ensure that BREEAM continues to drive the energy efficiency of appliances by demonstrating a meaningful reduction in energy consumption. Note that these new requirements will be reviewed from time to time and may be subject to change.
Where assessments have already specified (and can procure) products bearing the old labels, it is acceptable to follow the previous criteria. However, where products bear the new label and for all assessments registered after 31/05/2021, the new criteria must be met.
17 Apr 2023 - Applicability to NC2013 confirmed.
21 Mar 2022 - Confirmation added that washer-dryers require a D rating for both cycles
23 Nov 2021 - Reference to 'freezers' added to appliance types
12 May 2021 - Guidance updated and applicability to HQM One and BREEAM NOR confirmed
Office equipment – mobile devices - KBCN00041
Mobile devices such as smartphones and tablets, which are generally used without connection to an electrical power source, should be excluded from the assessment of the energy efficient equipment issue.
Devices which are not generally connected to an electrical power source when used are excluded from the 'office equipment' definition as they do not directly affect the unregulated energy consumption of the building.
On-site LZC – whole site shared connection - KBCN1424
To be recognised in BREEAM, the on-site Low and Zero Carbon (LZC) technology must have a direct physical connection to the assessed asset.
OR
Where the LZC technology is;
- Located on the same site,
- Is owned and managed by the same organization as the assessed building, and
- Where it is impractical to physically connect the assessed building to the system,
It is acceptable to allocate the renewable energy generated proportionally as a calculation of the asset's predicted energy consumption compared to the total energy consumption of the whole site.
To allocate renewable electricity by proportional consumption:
- Obtain the total annual renewable electricity generated on-site.
- Exclude all renewable electricity which has been exported to the grid.
- Determine the respective electricity consumption of all assets on the whole site (predicted for new builds and measured for existing assets).
Where consumption data is missing, renewable electricity must not be allocated to the assessed asset. In this case, it is assumed that all electricity consumed is sourced from the grid.
17-Jan-2024 - Applicability BIU V6 Ene 13 removed, as this approach is not applicable to assessing the area of PV fitted.
21-Dec-2022 - Applicability to In-Use V6 confirmed.
24-Aug-2022 - Applicability to UKNC V6 confirmed.
Only lifts in building are for persons with impaired mobility - KBCN1330
Where the only lifts, escalators or moving walkways in the assessed development are for persons with imparied mobility with speeds no greater than 0.15m/s, and there are no lifts which fall within the scope of the criteria, the Issue should be filtered out of the assessment. Credits cannot be awarded by default.
Passive design analysis – Modelling the standard building when existing building elements are retained - KBCN1270
In circumstances where an existing building element (e.g. a facade) is being retained it is acceptable to incorporate them into the modelling of the 'standard building' baseline, for the purpose of undertaking passive design analysis.
All other building elements should be modelled with fabric performance equivalent to that of the local Building Regulations Notional Building (or for Scotland, an equivalent compliant building) and without the passive design measures (where feasible i.e. building orientation is likely to be fixed).
Point of use water heaters - KBCN0773
Small 'point of use' water heaters can be excluded from the sub-metering requirements.
Only major energy consuming systems that have a measurable impact on the operational energy consumption need to be included.
Prediction of operational energy consumption – Multiple (similar) buildings assessments - KBCN1479
Sampling is not appropriate to meet the aim of the criteria; it is necessary to model the predicted operational energy consumption of all assessed units.
Credits are awarded for undertaking the detailed modelling, therefore there is no requirement to identify the worst performing unit and KNCN1382 is not applicable.
24/08/2022 - Applicability to UKNC V6 confirmed
Presence detection – illuminated signs - KBCN1671
The requirements for presence detection do not apply to illuminated signs.
In BIU V6, presence detection requirements are included as part of automatic energy saving controls. All other requirements in this criteria must still be met.
Regenerative drives – requirement for specification - KBCN1253
Requirements for the specification of a regenerative drive for lift installations are subject to an analysis of resultant energy savings. However, where it can be demonstrated that this is not financially viable, accounting for payback over the service life of the installation, this option can be discounted.
Please also refer to other scheme-specific guidance relating to this requirement.
RGB LED lighting - KBCN0986
RGB LED lighting must be assessed against the average external lighting efficacy benchmark.
The current criteria do not completely rule out the use of RGB LED lighting as it can potentially be combined with other types of external lighting to meet the average efficacy benchmark.
Scope of energy efficient cold storage - KBCN00029
Technical guidance
The intent of the following wording in the technical manuals is to exclude self-contained refrigeration units.
NC 2018 Ene 05:
“The scope of this issue covers freezer or cold storage rooms which are integral to the building and served by the building’s own refrigeration systems.”
NC 2016 Ene 05:
"If the building contains no refrigeration systems or only refrigeration systems which stand-alone, i.e. are not integral to the building and served by the building services, this issue is not applicable to the assessment.
Clarification
The scope of this issue covers freezer or cold storage rooms which are integral to the building, and includes cooling systems that require commissioning and optimisation for the specific requirements of the cold storage space. This applies whether the cold storage space has a dedicated cooling system serving this space, or one which is connected to wider building cooling services.
"Kitchen and catering facilities", are excluded from this issue. They refer to commercial-sized, but self-contained, off-the-shelf units - these include large freezers, fridges, or stand-alone self-contained walk-in cold storage units. These types of units are manufactured as a self-contained product, and contain their own integral cooling systems - they operate according to manufacturer pre-sets, and do not require commissioning of the cooling system.
For this reason, these are not assessed under this issue, but they may still fall within the scope of the 'Energy efficient equipment' issue.
The guidance will be clarified in future reissues or updates of the technical manuals.
22-Feb-22 Wording clarified.
02-Jun-17 Wording clarified.
02-Dec-16 Wording clarified - no change to approach.
Scope of the criteria for lifts – Small service lifts (dumbwaiters) - KBCN1589
Small service lifts, of the type typically used to transport prepared food and crockery in restaurants (sometimes referred to as 'dumbwaiters'), fall outside the scope of this assessment issue.
Security lighting - KBCN0915
The criteria generally apply to all external lighting, including security lighting. However, due to specific security requirements, there may be situations where a particular aspect of the criteria cannot be met, as they would compromise the development's security. For example, the use of PIR sensors may not be appropriate in high security developments, where continuous night-time CCTV surveillance is required.
In such cases, where this is justified by the security consultant or other appropriate member of the design team, compliance can demonstrated for the security lighting by meeting all other relevant criteria.
BREEAM does not seek to not impose requirements which could potentially compromise the development’s security strategy
10.03.2020 - KBCN amended following review. It has been determined that the criteria for this Issue must be applied to all security lighting, except as described above. KBCN no longer applicable to UK NC2011 as there is no criterion relating to PIR in this scheme.
Self-contained dwellings or units with individual utility meters - KBCN0199
Where self-contained dwellings or units covered by the assessment have their own individual energy supply and utility meter (e.g. water, gas or electricity), this supply can be excluded from the scope of the issue. All shared energy supplies and common areas under the responsibility of building management are still included in the assessment.
For example, if self-contained flats in an assisted living development have individual gas supplies with their own utility meter, this supply will be excluded from the assessment. However, the lighting and small power comes from a shared distribution board on each floor, in which case this shared supply will need to be sub-metered in accordance with the criteria.
This same principle applies to scenarios involving speculative industrial or retail units with capped services, where these units have their own utility meter.
12/09/2018 Applicable to Water Monitoring Issue where appropriate
27/09/2017 The word 'units' added to include a wider range of scenarios falling under this principle.
17/06/2022 Added other industrial / retail situations for further clarity on the applicability of this KBCN.
Single function area and no separately tenanted areas – operational energy monitoring - KBCN00056
Where an asset has:
AND
- no significant energy uses that must be separately metered
AND
- no separately tenanted areas for sub-metering
Provided that the sub-metering by end-use credit is achieved, the sub-metering of ‘high energy load and tenanted areas’ credit can be awarded by default.
12-Aug-2025 - Title and wording clarified.
26-Mar-2024 - Wording clarified. Scheme applicability updated.
Space heating as major energy use - KBCN0939
Where possible, space heating should always be considered as a major energy use for sub-metering purposes.
Where space heating cannot be separated from hot water, this must be fully justified by the design team at QA.
See KBCN0329: Combined system for space heating/cooling and domestic hot water.
Where electric space heating is used, this in itself cannot be used as justification for combining the space heating along with lighting and small power unless there is a clear justification for doing so.
See KBCN00068: Combined sub-metering of electric heating and small power equipment.
Sub-metering at least 90% of each fuel - KBCN0657
In a scenario whereby several energy consuming systems are not sub-metered because they account for less than 10% of the annual energy consumption (see Ene 02 methodology), and this results in less than 90% of the estimated annual energy consumption of that fuel being metered, the M&E consultant should review the metering strategy and advise which of these energy consuming systems would most benefit from sub-metering to make up the 90%.
This may be based on which of the energy consuming systems has the highest annual energy consumption, or which has the most potential for reducing energy consumption as a result of sub-metering. This will not necessarily have to mean that the energy consuming systems chosen have to have their own sub-meter, the M&E consultant may decide they would most benefit from metering alongside another consuming system. However ultimately 90% of each fuel must be metered.
Justification should be given within the metering strategy and the BREEAM assessment report as to which lower energy consuming systems were chosen to be sub-metered to make up the 90%, and how this was done to best suit the development (i.e. individual sub-meters or paired with another consuming system).
Sub-metering by calculation - KBCN0700
For simple sub-metering strategies, it is acceptable to calculate a single end-use by subtraction of known, sub-metered end-uses from the relevant main utility meter reading. For more complex strategies, where a BMS/BEMS is used, the software should be capable of calculating and displaying all required end-uses in line with the criteria.
Sub-metering technologies – Compliance Principle - KBCN1561
Where it can be demonstrated that alternative sub-metering technologies can meet or exceed the capabilities of systems set out in the BREEAM guidance, subject to approval, these can also be considered compliant.
It is the role of the Assessor and the project team to provide evidence and justification in a compliance principle query (see
KBCN1555).
The following metering standards or technologies are currently recognised as alternatives to pulsed output meters:
- M-bus.
I.e. systems that comply with the EN 13757 series of standards.
Also includes systems complying with the OMS (Open Metering System) standards.
Sub-metering using non-intrusive load monitoring (NILM) systems - KBCN1710
Non-intrusive load monitoring (NILM) systems cannot be used to demonstrate compliance for the sub-metering credits within BREEAM. Hardware-based sub-meters must be installed. NILM systems are generally retrofit systems which can be easily removed and are not integral to the building or installed building services.
Thermal modelling for shell only developments - KBCN0784
For shell only developments, in order to achieve criterion 1, thermal modelling can be completed on the basis of a typical notional layout and equipment specification for the particular building type (retail, restaurants, cinema etc.) can be used to demonstrate compliance.
04-Nov-2025 – Applicable to BREEAM NOR NC V6 - N/A to BREEAM NOR NC2016
Towel rails - KBCN00081
Towel rails cannot count towards the drying line requirements.
Clothes drying lines are provided to reduce the need to tumble drying clothes, which uses a lot of energy. Using towel rails to dry clothes would require the potentially damp towels to be stored while the clothes dry. This is inconvenient and therefore means the aim of the credit is less likely to be met.
Transportation analysis carried out by the lift manufacturer - KBCN0232
BREEAM recognises that lift manufacturers / suppliers are often engaged to provide such specialist advice. Where the assessor is satisfied that the analysis has been carried out correctly, the analysis can be submitted as compliant evidence.