UKNC: Residential (HQM) / UKNC: Residential V6.1 / B - My home /
4 Comfort
Information correct as of 22ndOctober 2026. Please see kb.breeam.com for the latest compliance information.
Communal ventilation system - KBCN1388
A communal ventilation system is acceptable as long as it meets the requirements in the HQM manual.
In terms of maintenance, if it is not possible for the home occupants to carry out system maintenance themselves due to the type of system installed we would need a statement from the professional designing the system stating this. Instead, any specified ventilation system requiring maintenance must be designed to allow building services engineers to easily complete the work in a safe manner in accordance with manufacturer’s instructions and any other safety regulations, to prevent systems becoming redundant or being unable to function to their designed intention.
30-Oct-2025 - Applicable to HQM V6 and UKNCR V6.1
Compliant test body – alternative compliance route using a Suitably Qualified Acoustician - KBCN1412
Where acoustic testing and measurement has not been performed by an organisation or individual that meets the definition of a compliant test body, compliance with this requirement can still be demonstrated where a Suitably Qualified Acoustician has reviewed the relevant test report(s).
The test report must:
a) Be countersigned or authorised by a Suitably Qualified Acoustician
b) Include a clear statement that the acoustic testing and measurements have been carried out in accordance with the BREEAM or HQM testing requirements
AND
c) Include evidence that the verifier meets the definition for a Suitably Qualified Acoustician within the relevant BREEAM or HQM technical manual
30-Oct-2025 - Applicable to HQM V6 and UKNCR V6.1
Emissions from products – scope of assessment - KBCN0212
General
This issue covers any product installed or applied inside the inner surface of the building’s infiltration, vapour or waterproof membrane.
Where this membrane is not present, it applies to the inside of the building envelope’s interior-facing thermal insulation layer.
Only products that are installed or applied in parts of the building where their emissions are likely to affect indoor air quality need to be assessed.
Paints and coatings
Any decorative paints and varnishes that occupants are exposed to should be assessed.
This is likely to include paints and coatings applied to walls, ceilings, floors, doors, etc.
Whole products
A finish applied to a product in the factory is assessed as a whole product, and not separately as a paint or coating.
For instance, a wood panel has a finish applied in the factory. The whole panel, including all the elements that make up that panel, would need to comply with the requirements set for wood panel products in this issue.
The finished product as a whole must meet the performance requirements / emission limits set in the manual.
30-Oct-2025 - Applicable to HQM V6 and UKNCR V6.1
11-Oct-2022 - Title amended for clarity and consistency. Content merged with KBCN0871.
10-Oct-2022 - Wording simplified. Scheme applicability updated.
16-Jun-2017 - Title and general principle amended to extend the applicability of the KBCN to all finishes. Paints specified for specialist applications covered in KBCN0872.
Emissions from products – specialist paints and coatings - KBCN0872
Where a paint or coating falls within:
- A category in Annex II of the EU Directive 2004/42/CE or,
- A category in the relevant product emission table of the technical manual,
then the paint or coating must be assessed.
Specialist paints and coatings are exempted from meeting the VOC content and emission limits where there are no alternative products available that can perform the function, and still meet the emission limits.
This must be clearly evidenced.
30-Oct-2025 Applicable to HQM V6 and UKNCR V6.1
02-Oct-2025 Reference to 'VOC content' added and KBCN applied to UKNC V7 and INC V7 to clarify CN2.1
27-Oct-2022 Wording clarified. New compliance principle added from UKNC V6.
10-Oct-2022 Title amended for clarity. Scheme applicability updated.
13-Mar-2020 KBCN amended to clarify exceptions and applicability.
16-Jun-2017 Content merged with KBCN0212.
Erratum-Projected climate change environment-Emissions scenario missing from manual - KBCN1742
The CIBSE future climate weather files should also use the following emission scenarios.
For naturally ventilated buildings - Medium.
For mechanically ventilated or mixed mode buildings - High.
GN22 Recognised schemes for emissions from construction products - KBCN0719
Latest version: v3.2, July 2026
Within the Health and Wellbeing category of several BREEAM schemes, credits are awarded for specifying materials that minimise emissions from building products of formaldehyde and volatile organic compounds (VOCs). The criteria involve meeting emission level performance requirements in accordance with compliant performance and testing standards.
Guidance Note 22 (GN22) lists schemes that show equivalent or better performance than the current BREEAM and HQM criteria and therefore can be used to demonstrate compliance with the criteria. This document should be read in conjunction with the relevant assessment issue guidance provided in the appropriate BREEAM or HQM technical manual.
The guidance note contains two tables:
- Table 1 is for use with BREEAM schemes that were first released before December 2015.
- Table 2 is for use with BREEAM (and HQM) schemes that were first released from December 2015 onwards (post-November 2015).
Download Guidance Note 22
View all Guidance Notes on BREEAM Projects (licensed assessors only)
Applying for inclusion in GN22
The list of approved schemes is based on those which have made a successful application to BREEAM. As such, there may be other operational schemes that could potentially be recognised.
To be considered for inclusion, the scheme operator must complete an application form, providing full details of the scheme, and submit this to BRE Global for technical approval. A flat rate charge is payable to cover the costs of administering and reviewing the application. GN22 will be updated following the approval of any schemes via this process.
The application form (BF1648) provides full details of the application process, and licensed BREEAM assessors can request a copy by submitting a technical query using the
webform. Other parties may request a copy by contacting:
breeam@bregroup.com
15-Jul-2026 - Release of GN22 3.2
25-Mar-2026 - Release of GN22 3.1
30-Oct-2025 - Applicable to HQM V6 and UKNCR V6.1
25-Sep-2025 - Updated to provide details of the approval process and title updated.
30-Jan-2025 - Release of GN22 3.0
30-Sep-2024 - Release of GN22 2.9
01-Feb-2024 - Release of GN22 2.8
31-Jan-2023 - Release of GN22 2.7
10-Oct-2022 - This KBCN merged with KBCN0646. Title amended to align with standard KBCN naming format for clarity and consistency. Made applicable to UK and International NC V6.
25-Jan-2019 - Link to Guidance Note updated
12-Mar-2018 - Link to Guidance Note updated
Information sign provided via a QR code - KBCN1875
A QR code securely fixed to the rear of a boiler, meter, or airing‑cupboard door that, when scanned, provides the required digital information for Crit 1 is acceptable as an alternative to a physical information sign.
Where a QR code is provided, crit 1.f. is not applicable.
Where a QR code is provided, information detailing how to request a hard copy must also be provided for those occupants who cannot access the information digitally as they do not have a smart device with an internet connection..
Minimum ventilation rate above boost flow rate - KBCN1364
Where a ventilation system has the capacity to meet the minimum ventilation rate (Criteria '03 Ventilation rates') and where this is above the boost flow rate, then the boost flow rate can be deemed to have been met by default.
30-Oct-2025 - Applicable to HQM V6 and UKNCR V6.1
Sound Insulation testing for Cupboards - KBCN1299
A cupboard (even built in) does not constitute a room and does not need to be assessed for the 'Sound insulation levels for internal walls and floors' credits as it is not permanent (part of the home's fabric) and also non-habitable.
30-Oct-2025 - Applicable to HQM V6 and UKNCR V6.1
Sound testing between rooms - KBCN1303
Only lab tests carried out in accordance with Part E of the building regulations are accepted as evidence to show compliance with the requirements sound insulation between rooms ( 02 Sound insulation levels for internal walls and floors - HQM ONE). In-situ testing and software calculations are not acceptable ways of showing compliance.
30-Oct-2025 - Applicable to HQM V6 and UKNCR V6.1
Ventilation air intakes CIBSE TM21 compliance - KBCN0669
As TM21 largely contains general guidance, rather that strict rules, it is expected that the designer or services engineer would be familiar with the requirements within TM21 and be able to determine which sections are relevant for the development in question.
The main areas to consider in relation to TM21 are:
• Provision of filtration
• Positioning inlets to minimise impacts of traffic pollution
• Positioning inlets to minimise impacts of other local sources of pollution
• Positioning inlets to minimise recirculation from ventilation exhausts
Confirmation is required that each of these items (and anything else the designer/engineer deems relevant) has been considered in determining the location of air intakes. Suitable evidence may for example be in the form of a short report with diagrams indicating the proposed location of intakes, with respect to sources of pollution and with reference to the relevant parts of TM21.
30-Oct-2025 - Applicable to HQM V6 and UKNCR V6.1
VOC product emission certificates – validity - KBCN1689
Where it can be demonstrated that construction product emission certificates were valid either at the time of specification, or at time of purchase, they may contribute to awarding credits.
BREEAM is primarily trying to encourage designers to take construction product emissions into consideration when specifying or selecting products and as such it is not necessary for certification to be valid at the time of design or post-construction stage submissions.
30-Oct-2025 - Applicable to UKNCR V6.1
Information correct as of 22ndOctober 2026. Please see kb.breeam.com for the latest compliance information.