Refurbishment and Fit Out / UK RFO 2014 / 09 - Pollution /

POL 03 - Flood Risk Management and Reducing Surface Water Run-off

Information correct as of 29thNovember 2026. Please see kb.breeam.com for the latest compliance information.

Addition of question into Initial Details Section: ‘Could any issues within the scope of the assessment have an impact on flood management, surface runoff, or the pollution of watercourses?’ - KBCN1720

Previously, if there were any drainage issues identified in the building, that were not within the scope of the assessment/intended fit out then the criteria would be applicable. Therefore, this new question has been added to the initial details section. Where the answer is No, then Pol 03 will be filtered out of the assessment. When the answer is Yes, the Pol 03 credits will be applicable. This change applies to both the UK RFO scheme and the International RFO scheme. 
In the case of P3-4 assessments where the new question is answered as yes, Pol 03 will show 2 credits are available for flood risk management. Therefore, those 2 credits are still applicable and are not filtered out of the assessment.
Please note that where the answer to the question is no, detailed documentary evidence demonstrating that there is no impact in line with the requirements of this exception must be referenced within the Initial Details, with applicable assessor commentary provided. Where this is not included, NCs could be raised delaying the certification process. Where the answer is yes, the usual evidence and justification will suffice, and no further confirmation is needed.

Adoption of road in the development - KBCN0331

Where a development includes roads, these are often adopted by a statutory authority (for example the Highways agency or the local authority in the UK). Where the authority will be taking responsibility for the roads, the following guidance should be followed to determine if the water run-off from the roads needs to be considered as part of the assessment: Where the authority will NOT be taking responsibility for the roads, the BREEAM criteria should be followed for all drainage on site.  

Erratum-Evidence requirements for Criteria 7 at Design stage - KBCN1691

'Calculation of the 5mm rainfall event from the relevant areas.' is not required as evidence to demonstrate criterion 7 has been met.

Flood risk – Site situated across numerous flood zones - KBCN0532

Where a site is situated across more than one flood zone, the flood zone with the highest probability of flooding, i.e. the worst case scenario, must be considered for the purpose of the BREEAM assessment. An exception to this would be where the areas in the higher probability zone include only soft landscaping and it can be demonstrated that access to the building will be maintained in a flooding event. This is to ensure that the site has adequately managed the worst case scenario level of flood risk associated with the site's location. 
22/07/2022 Applicability to HQM One confirmed
07/03/2018 Updated to include circumstances where an exception may apply.

Flood Risk Assessment older than five years - KBCN1744

This sentence appears in the definition of 'Flood Risk Assessment': Where more than five years have passed since the FRA was carried out, evidence would be required to demonstrate that the basis of the FRA has not changed in that time. The requirement for evidence that the basis of the FRA has not changed where more than five years have passed is applicable only at Design Stage. It is not required at Post Construction Stage where a compliant FRA was undertaken at Design Stage and the development was carried out in accordance with that design.

Flood risk assessments to National Planning Policy Framework - KBCN0901

The National Planning Policy Framework (NPPF) is made up of a number of Planning Practice Guidance (PPG) documents.  This means that flood risk assessments that confirm they follow the NPPF can be accepted as being compliant to all relevant PPGs (for example PPG Flood Risk and Coastal Change).

FRA more than 5 years old - KBCN1580

Where more than five years have passed since the FRA was carried out, to be able to use the FRA in your assessment evidence would be required to demonstrate that the basis of the FRA has not changed in that time.

Minimising water course pollution – no water courses present - KBCN0550

The credit for 'minimising water course pollution' has to be assessed even in cases where no water courses are in close vicinity to the site under assessment. This is because the aim of this credit is to encourage developments to minimise water course pollution by restricting the discharge of potentially contaminated water from entering the public sewer. Minimising water course pollution does not focus on water directly entering water courses.

No discharge for up to 5mm rainfall - KBCN0599

The criterion requires no run-off to leave the developed site into the local watercourse(s) for a storm event that results in rainfall depths up to 5mm.  It is not acceptable to collect the rainfall within an attenuation tank and allow the runoff to be released from the site at a restricted rate. This simply slows the rate at which it is released to the watercourse(s). Compliance should be based upon zero runoff from the first 5mm rainfall for 80% of events during summer and 50% in winter.  This is in line with the recommendations within Chapter 24.8 of The SuDs Manual (C753), CIRIA 2015. The 5mm rainfall event is considered one of the most common rainfall events and, therefore, a system should be designed to prevent this run-off leaving the site thus protecting a receiving watercourse from pollution. Where ground conditions prohibit the use of SuDs techniques to manage the rainfall onsite or it is not be possible for the first 5mm of rainfall to be prevented from leaving a site completely.  An appropriately qualified professional must explain comprehensively why this criterion cannot be fully met and design a system to meet the intent of this criterion as far as possible. Where this can be justified and all other relevant criteria have been achieved, the credit can still be awarded.
16.08.2024 Clarification added on calculation requirements and text from KBCN1059 now included.

Scope of different parts – Error in compliance note - KBCN1261

CN3 Includes the following error:
Technical manual to be updated accordingly in next reissue.

Watercourse pollution from indoor parking - KBCN0545

If the design team can demonstrate that there will be absolutely no run-off from the indoor parking then the intent of the credit will be met. However, such proof would also have to demonstrate that no hydrocarbon spillage from vehicles found its way into the watercourse/sewer. It is likely that there would be water ingress from outside or that internal parking areas would have drains fitted and be cleaned regularly. In such conditions, the criteria are still applicable. The intent of this criteria is to ensure no hydrocarbons run off to any watercourse.

[KBCN withdrawn] ~ Flood risk – Environment Agency (EA) confirm the site is in ‘low flood risk’ area This KBCN has been withdrawn and is no longer valid. This is because its content was created on the basis of a very specific case and should not be applied generally. EA confirmation is no more robust or detailed than reference to flood maps, which are not in themselves compliant without a FRA.
KBCN withdrawn on 17/03/17:

If the EA have confirmed, in writing, that the site has a low flood risk and that a Flood Risk Assessment (FRA) is not required then this is acceptable and the two credits can be awarded. The EA's written confirmation is a sufficient indication that an appropriate level of flood risk assessment has been completed. Please note that the use of the EA flood maps without this additional confirmation is not acceptable.