Amenities – Community facility – Collaborative work areas (shared workspace) - KBCN1918
For appropriate building types, a collaborative work area can qualify as a
community facility where it is demonstrated that:
- It provides a relevant amenity for users of the assessed building.
- It is fit for purpose.
- It is suitably sized for the number of building users (accounting for any public access, where relevant).
- It is available to building users at appropriate times.
Amenities – Pharmacy within a hospital or health centre - KBCN0321
To meet the requirements of 'Over the counter services associated with a pharmacy', a dispensary within a health centre or hospital can be considered as meeting the intent, provided it is publicly accessible and also offers the type of over-the-counter services associated with a stand-alone pharmacy, such as non-prescription medication and health products.
Note: This is a change to the approach outlined in the previous KBCN wording, therefore, for assessments registered before this update, where it can be demonstrated that the the assessor has advised the project team based on the previous wording, this can be accepted:
Superseded guidance:
A publicly accessible pharmacy would typically be required in order to constitute a suitable amenity. If it can be confirmed that an internal pharmacy (in Northern Ireland this may also include an onsite controlled medical dispensary) will provide prescribed medicines for building users, this is acceptable.
18 June 2025 - Title updated and wording amended to clarify the intent. Applied to NC V6 standards.
Safe pedestrian routes – Definition, measurement and verification - KBCN0238
Definition
Safe pedestrian routes include pavements and safe crossing points, which may be controlled or, for example, be identified by tactile paving, a crossing island or a dropped kerb. An element of judgement may be required, in which case justification should be provided.
Measurement
Distances could be measured, for example, along a pavement, across a road at a safe crossing point and along the pavement on the other side. The distance should not be measured diagonally across a road, following the most direct route.
Verification
The assessor’s site inspection is an important aspect of the assessment and may help to confirm that all relevant information is current and can include photographs of any key areas. This can also help to identify safe crossing points or hazards which may not be apparent from a desktop study. Alternatively, web-based map data may be used to satisfy the evidence requirements at both Design and Post-Construction Stage, provided that the assessor is satisfied that this clearly demonstrates compliance and that the evidence is robust and up to date.
Where web-based navigation maps (e.g. Google Maps/Street View) are used as evidence, this must include:
• Dated and marked-up site plan or a web-based navigation map viewer highlighting:
• Current location and type of transport nodes and local amenities.
• Current route and distance from the building via a safe pedestrian route.
• Plan or map scale.
When relying on web-based evidence for post-construction stage, the assessor must, additionally, provide verification that the information provided for the nodes/amenities is still accurate and up to date.
16 Sep 2025 - Wording relating to verification updated to clarify the intent.
29 Aug 2025 - Approach to web-based map data at post-construction stage updated and related wording amended accordingly
07 Mar 2024 - No changes have been made. This appears as 'updated' due to an administrative error.
11 Jan 2024 - Wording re-structured for clarity
19 Dec 2023 - Applicability to BIU V6 confirmed
Information correct as of 19