New Construction / UK / 2014 / 02-Health and Wellbeing /

Hea 04 – Thermal comfort

Information correct as of 28thOctober 2026. Please see kb.breeam.com for the latest compliance information.

Adaptability for a projected climate change scenario – Winter conditions - KBCN1715

Where future climate change scenario projections in winter indicates a higher temperature and, therefore, more thermally comfortable climate compared to the current winter temperatures, it can be assumed that the winter conditions within the climate change scenario are met based on the thermal modelling of current winter conditions. Justification must be provided for each project confirming that the future winter conditions will be met with the current heating system. In a warming climate the heating system needs to be sized for the beginning of its lifespan, whereas the cooling systems need to be sized for the end of their life span (Ref: CIBSE TM55: 2014)

Air-conditioned spaces - KBCN00035

Air-conditioned spaces are assessed to ensure appropriate thermal comfort levels are achieved. Cooling capacity should be sufficient to comply with the requirements of CIBSE Guide A, however providing sufficient space to install additional capacity to meet the requirements at a later date in line with projected climate change scenarios is also acceptable. In addition, if it can be demonstrated that the air-conditioning system can achieve the thermal comfort criteria in accordance with CIBSE Guide A, Table 1.5, thermal modelling does not need to be carried out. The “time out of range” (TOR) metric should be reported as 0%.  

Approach to thermal model when using BMS - KBCN0169

Where there are smart systems such as BMS in place, modelling must consider normal operating conditions, with the heating and cooling system in operation regardless of the control strategy. In order for the design team to size the heating/cooling plant, they will carry out modelling to calculate the heat/cold loss throughout the year. Results of these calculations must be submitted, with the heating/cooling plant specification which would demonstrate that the building has been designed to ensure internal winter/summer temperatures will not drop below an acceptable level, and that in effect the winter TOR is zero.
14 Apr 2023 Applicability to UK NC2018 and UK/Int V6 confirmed

Assessing industrial spaces – exemptions - KBCN0734

The thermal comfort criteria do not apply to the operational or storage areas typically found in industrial assets or other similar asset types. The criteria is still be applied to the other parts of the asset as appropriate. Operational and storage areas often have function-related thermal requirements determined by operational or storage needs. These functional requirements override the needs of any occupants.
17-Jan-2024 - Scheme applicability updated.
03-Nov-2020 - Issue 2.0 of UK RFO technical manual updated with new CN detailing the above.

Assessing thermal comfort – Residential buildings - KBCN1408

CIBSE TM59 can be used to demonstrate compliance with the thermal comfort requirements for residential and multi-residential buildings (long-term stay), instead of ISO 7730:2005. This is to recognise the most up to date methodology relating to the assessment of homes
26 Jan 2025 - Updated to apply to multi-residential buildings (long-term stay) and scheme applicability extended to account for this.

Building Bulletin 101 - KBCN0786

Within Compliance Note CN4.1, reference is made to the appropriate industry standard for schools being Building Bulletin 101: Ventilation of school buildings (2014). This has been updated to BB101 2018, so either the current version or the specified 2014 standard may be used to demonstrate compliance. If the thermal modelling specialist recommends an alternative standard, for example TM52, then this would be acceptable provided there is a full justification.
11/08/2021 Updated to recognise the current version of the standard

Definition of concourse - KBCN0386

A concourse is an open area within or in front of a public building which is used primarily for circulation, short term waiting, or incidental interaction, analogous to the concourse of a train station. It should not be considered occupied space.  

Future thermal comfort – mechanical ventilation, mixed mode and limited comfort cooling - KBCN1877

Where a building or space incorporates mechanical ventilation systems, including mixed-mode strategies, the selection of future weather files for thermal comfort assessment should be based on the expected service life of the systems installed. This includes systems providing mechanical ventilation, with or without limited comfort cooling, and mixed-mode spaces where natural ventilation is supplemented by mechanical systems within the same space. For the purposes of this guidance, ‘mechanical ventilation with limited comfort cooling’ refers to systems that may provide some degree of cooling or air tempering but are not designed to fully maintain internal conditions to defined air-conditioned setpoints throughout occupied hours. Although these systems do not provide full air conditioning, their presence influences internal environmental conditions and overheating risk. As their performance is dependent on mechanical components with defined service lifespans, the future thermal comfort assessment should be aligned with the expected lifespan of these systems (typically 15 years), rather than the overall building lifespan.  For schemes where free‑running buildings are assessed using a longer lifespan for future climate scenarios, a shorter system lifespan should be used where mechanical systems are present

Occupant control – BMS and degree of control - KBCN0175

A Building Management System controlled set point with local override controls limited to a set range would satisfy the occupant control requirement so long as the temperature range available to building users is confirmed as appropriate for the building type and user profile.

Occupant control – spaces requiring user controls - KBCN0170

This guidance is intended to clarify the types of area for which user controls are required or would be considered beneficial. Zoning is required in all areas of the asset where specified in the assessment criteria. Please refer to the specific requirements of the applicable BREEAM standard to interpret this guidance appropriately. User controls required Spaces where users are expected to have independent control over their environment. User controls not required Spaces where users are not expected to have independent control over their environment.
14-Dec-2022 - KBCN applicability updated to include BIU. Wording clarified, and amended for compatibility with BIU criteria.

PMV and PPD reporting for mixed mode ventilation buildings - KBCN0632

When assessing buildings where both naturally ventilated and air conditioned spaces are included, reporting the PMV and PPD indices is required.

Reporting PPD and PMV Figures - KBCN0867

The PMV (Predicted Mean Vote) and PPD (Predicted Percentage Dissatisfied) values need to be entered into the scoring & reporting tool for data recording purposes. The thermal modelling specialist should be able to provide values for both the PMV and PPD for the asset. The values to report are the observed range of values for PMV and PPD: If the software or calculation method used does not generate these PMV / PPD metrics, they do not have to be provided. [accordion] [accordion_block title="Example"] An asset has the following thermal comfort ranges across its occupied spaces: [/accordion_block] [/accordion]
15.09.22 Wording and example clarified.

Thermal comfort – Changing rooms - KBCN1133

Whilst thermal comfort in changing rooms may be considered as significant, such spaces are, generally, outside the scope of this Issue, as they would not fall within the definition of an 'occupied space'.
17/06/2019 - This supersedes the advice previously provided in this KBCN, which was published in error on 13/06/2018

Thermal comfort – Time-critical requirement - KBCN1801

The requirement for the full dynamic thermal analysis at detailed design stage, is set as this is the optimal stage to achieve the required sustainability outcome. When undertaken at a later stage, opportunities may be missed, options reduced or costs may become prohibitive. therefore the stipulated timeframes for such actions must generally be adhered to. However, if, due to specific circumstances or a non-standard the procurement route being used, the assessor can demonstrate that the aim of the criteria can still be fully met, despite the project having moved into a subsequent work stage, this will be accepted by BREEAM. In such cases, the assessor must justify and demonstrate that the ability to fully meet the aim of the criterion has not been compromised.

Thermal modelling – mechanical ventilation with no heating or cooling - KBCN1579

Where the building services include mechanical ventilation with no heating or cooling element this is considered "free-running". These buildings do not need to follow the air-conditioned building criteria. If the building services do not include any mechanical cooling, then the risk of overheating is down to the use of the building fabric to afford attenuation of the diurnal swings / solar gains. Therefore the adaptive approach to thermal comfort from CIBSE AM10 is the correct approach to define and assess summer overheating /thermal comfort against. Following the Adaptive model is seen as allowing a lot of tolerance for the required indoor conditions. A full DTM assessment will be required to show the predicted summer internal conditions.

Thermal modelling – naturally ventilated buildings with heating for the winter months - KBCN1345

Where naturally ventilated occupied spaces are heated in the winter/heating season, as an alternative to demonstrating compliance with the winter operative temperature ranges in CIBSE Guide A or other appropriate industry standard, such occupied spaces can demonstrate compliance through meeting the Category B requirements for PPD, PMV and local discomfort set out in Table A.1 of Annex A of ISO 7730:2005. Where this alternative compliance route is used, when these naturally ventilated occupied spaces are in ‘free-running mode’ (i.e. outside of the winter/heating season), it is not possible to use the ISO 7730:2005 method and therefore these spaces must demonstrate compliance with the requirements to limit the risk overheating in accordance with CIBSE TM52.

Thermal modelling for large scale projects - KBCN1171

In cases where the scale of the project makes it unfeasible to provide thermal modelling for every space, it is acceptable to demonstrate compliance with a representative sample of floors or rooms, ensuring any worst case scenarios are included.

Thermal modelling – buildings with mixed-mode ventilation - KBCN1346

Where a building has some occupied spaces that are naturally ventilated and some occupied spaces that are air-conditioned, the thermal modelling must demonstrate that the naturally ventilated spaces meet the criteria for naturally ventilated buildings and that the air-conditioned spaces meet the criteria for air-conditioned buildings.

User controls – Thermal comfort - KBCN1813

The requirement for user controls does not mandate a specific type of control; e.g. local manual adjustment. Where control is provided indirectly, e.g. via BMS or central management, the assessor must demonstrate that this approach meets the intent of the user comfort and accessibility criteria and is informed by end-user discussions or relevant design guidance. Please refer to KBCN0170 for clarification of the types of space requiring user controls.

Weather files – 2020s, 2030s and 2050s - KBCN0842

Timescale The weather files for each decade cover a 30-year climatic period around that decade. For example, 2020s weather files cover the period 2010 to 2040. 2020s are in the middle of the three decades (10s / 20s / 30s). NC - 2020s and 2050s New Construction projects assessed under the relevant standards should continue to use the 2020 weather files for mechanical ventilation, and the 2050 weather files for natural ventilation. CIBSE weather files are available here: CIBSE Weather Data RFO - 2030s and beyond When published, the original intent for RFO projects was for future thermal comfort to be based on projected climate change 15 years after completion.   NOTE: For BREEAM standards published before September 2025, the 2016 CIBSE Weather Data may still be used.  
15-Oct-2025 - Note added to clarify version requirements for CIBSE weather data. 
08-Jan-2024 - Added clarification on RFO 2030s data.
18-Dec-2024 - Merged with KBCN000006. Prometheus link updated. Title updated.
04-Jul-2024 - Clarified that 2020 and 2050 weather files are still valid for the applicable standards and guidance applied to all relevant UK standards. Applicability to international standards removed and link to CIBSE weather data added.
19-Sept-2025 - Applicability to RFO projects added.
 

Weather files – 50th percentile - KBCN0117

For the thermal simulation of climate change environments, where this not specified in the manuals, the 50th percentile weather file is used in all cases. This applies also to the use of any alternative weather files or formats which are not listed in the manual. See KBCN1182.
18-Dec-2024 - Title updated for clarity. Scheme applicability updated. Link to KBCN1182 added.

Weather files – alternative format or location - KBCN1182

If they achieve the aim of the credit, alternative weather file formats not listed in the manuals can be used instead of those referenced in the manual. Format - current climate The alternative weather files must include same variables as the specified weather files for each hour of the year e.g.: - Dry bulb & wet bulb temperature, - Wind speed & direction, - Solar altitude & azimuth, - Cloud cover etc. For example, TMY (Typical Meteorological Year) is an accepted alternative format for BREEAM, meeting the requirements above. The assessor or design team must verify this and ensure that meeting the BREEAM criteria does not become easier by using the alternative weather file. Format - projected climate These alternative files must be based on climate projections with equal or higher temperatures than those specified in the relevant criteria, setting an equally or more robust standard for overheating. Where there are no suitable weather files available for projected climate change, use any one of the following: To modify weather data for existing climates into the relevant future climate change scenarios required in the criteria. Alternative location Where the weather file for the nearest location for the project is not representative of the actual location’s climatic conditions, the project team can use the weather file from another nearby location which is more representative. This can take account of the climatic influences of altitude, prevailing wind, proximity to climate-moderating features, or heat island effect.
19-May-2025 - Added example alternative format. Added links to future climate change resources.
18-Dec-2024 - Merged with KBCN1013. Scheme applicability updated.

[Withdrawn] – 2030s weather files - KBCN000006

Merged with KBCN0842. The Exeter University Prometheus project contains future weather files which cover the 2030s. These can be found here: https://emps.exeter.ac.uk/engineering/research/cee/research/prometheus/downloads/
18-Dec-2024 - Merged with KBCN0842 and withdrawn.
13-Sep-2024 - Hyperlink to Prometheus project updated. Applicability to BREEAM International schemes removed - (see  KBCN0732)

[Withdrawn] – Weather file location - KBCN1013

Content merged with KBCN1182. In accordance with the guidance provided in CIBSE AM11, in instances where the weather file for the nearest location does not represent the most appropriate climatic conditions for the actual location, it is permissible to use the weather file from another, nearby location, which more closely matches the climate at the actual location. This can take account of the climatic influences of height above sea level, a coastal location or other local, climate-moderating features such as mountains, woodland, lakes, prevailing wind direction or urban heat island effect.
18-Dec-2024 - Content merged with KBCN1182.

Information correct as of 28thOctober 2026. Please see kb.breeam.com for the latest compliance information.