Waste storage provision for catering

As the manual states, the additional 2m2 per 1000 m2 of waste storage area provided for catering is measured against the “net floor area where catering is provided” and NOT the floor area of the catering facility.

Generally, a catering facility will serve building users throughout the building. If it can be demonstrated that this is not the case, for example if part of the development is subject to a separate tenancy, not served by the catering facility, the area calculation can be adjusted accordingly.

Where the net floor area is not indicative of the actual occupancy, the default values may not be appropriate. In such cases, the predicted waste streams should be calculated based on the actual occupancy and waste streams generated.

This requirement accounts for the increase in waste produced by building based on the likely number of building users served by the catering facility. Please note that these default calculations are only intended for use where it is not possible to determine accurately what provision should be made based on predicted waste streams. 

15 06 2017 Wording updated to clarify