New Construction / UK / V6 / 03 Energy /

Ene 01 - Reduction of energy use and carbon emissions

Information correct as of 19thOctober 2026. Please see kb.breeam.com for the latest compliance information.

Accredited energy assessors – directories - KBCN1465

The directory of accredited energy assessors has moved. For England, Wales and Northern Ireland, accredited energy assessors can be found here: https://getting-new-energy-certificate.digital.communities.gov.uk/ For Scotland, accredited energy assessors can be found here: https://www.scottishepcregister.org.uk This will be updated in future manual re-issues.
24 Aug 2022 - Applicability to UKNC V6 confirmed

BRUKL File Upload – HVAC Area Mismatch in UK New Construction V6.1 - KBCN1734

To support quality and accuracy in Ene 01 credit calculations, an additional check has been introduced for UK New Construction V6.1 only. This checks that, in the BRUKL file, the total building area equals the sum of HVAC system areas (notional and actual) and if not, it generates an error message during the upload. These area values are used to calculate the adjusted notional value for Ene 01. We are aware that some approved third-party software (e.g. IES, TAS) may be generating files with floor area discrepancies, even if the energy model is correct. If this affects you: For additional information, please reach out to assessorfeedback@bregroup.com
06 Jun 2025 - Title and wording updated to clarify the intent and scope of the guidance
 

Calculating EPR where there are multiple BRUKL/NCM outputs - KBCN1618

Where more than one NCM output is produced for a development that is registered as a single assessment, an area-weighted average must be used to calculate the number of credits to be awarded. This does not apply where the ‘similar buildings’ approach is used. Projects in England assessed under UKNC V6.0 should submit their BRUKL files to BREEAM and we will calculate the result. Projects assessed under UKNC V6.1 can upload multiple BRUKL.inp files for a single assessment and the platform will perform the calculation.   For projects assessed under BREEAM UK NC2018 and International NC 2013, 2016 and V6, please refer to KBCN1083

Credit requirement for an “Excellent” or “Outstanding” – Connection to district heating is a condition of Planning - KBCN1766

This KBCN applies when a project is required to connect to a district heating system as a condition of planning and this is preventing the project from achieving the number of credits required for a BREEAM Excellent or Outstanding rating. In these situations, an additional brukl.inp file must be generated for the actual building but with an alternative heating system, e.g., a heat pump, that demonstrates that the minimum standard would be achieved if the building didn’t have to connect to district heating. A technical query must be raised citing this KBCN and stating the minimum standard being sought with two brukl.inp file attached, one for the actual building with district heating and one with the alternative with an alternative heating system. Where the brukl.inp documents demonstrate that requirement to district heating is the only thing preventing the project from achieving the required number of credits, the technical team will confirm and arrange for the minimum standard to be waived. However, the number of credits awarded must be based on the building connected to district heating.

Energy consumption and carbon emissions of untreated spaces - KBCN00049

Where the assessment contains a mix of treated and untreated spaces, untreated spaces can be excluded and the performance based on the treated spaces only. Where the entire assessment is untreated, the whole of the structure(s) must be assessed on the basis that this issue is critical for certification. BREEAM is primarily designed to assess permanent, treated and occupied structures. Untreated structures are unlikely to gain many credits when being assessed.
24/08/2022 - Applicability to UKNC V6 confirmed

Energy modelling not required for Building Regulations compliance - KBCN0487

For the purposes of demonstrating BREEAM compliance, it is still necessary to undertake energy modelling to generate the required performance data.
24/08/2022 Applicability to UKNC V6 confirmed
 

Energy performance assessment for part of a whole building - KBCN0596

If the assessment is only covering part of a whole building, the energy performance assessment must be representative of the part of the building being assessed. Simply taking the energy performance assessment of the whole building would not therefore comply, especially if the non-assessed parts of the building were of a different use. A separate energy assessment of the part of the building is likely to be required. The energy performance assessment must be representative of the parts of the building being assessed. This also applies to the predicted energy performance and all energy modelling for the prediction of operation energy consumption. 
24/08/2022 - Applicability to UKNC V6 confirmed
Amended 01/09/2020 to cover UKNC2018 - Prediction of operational energy consumption

GN39 Ene 01 Calculation Methodology – BREEAM UK NC 2018, V6.0, and V6.1 - KBCN1098

Latest version: v3.0, June 2023 Guidance Note 39 describes the calculation methodology for the energy performance criteria (up to 9 credits) in Ene 01 for BREEAM UK New Construction 2018, Version 6.0, and Version 6.1. Download Guidance Note 39 View all Guidance Notes on BREEAM Projects (licensed assessors only)
14-Jun-2023 - Updated for release of UK NC V6.1

LZC technologies – energy centre or other LZCs connected at a later stage - KBCN0267

If a project specifies LZCs that have been proposed in the feasibility report which reduce emissions, and/or will be connected to a site-wide energy centre operational at a later stage of the phased development, after the Post Construction Stage review has been submitted, the Energy and Pollution issues can be assessed as follows: In a phased development where the primary heating system will be upgraded at a later stage than the building being assessed, a commitment to install the new heating source must be made in the General Contract Specification (as per the BREEAM requirements). BREEAM does not specify a particular time for phasing as it is difficult to set parameters, however as a rule building users should have to wait the least time possible before they can use the upgraded heating source. For the quality audit, two Energy model outputs/EPCs must be produced at the final stage - one with the actual interim system installed for building control, and one for the BREEAM assessment which can include the predicted energy from the proposed energy centre.  Additionally, the legally binding general contract specification for the new heating source must be submitted with details of the timescales proposed for the completion of the second phase of work. Where this approach is to be followed BREEAM must be consulted in each case to ensure that the arrangements are sufficiently robust to award the credits. BREEAM seeks to recognise the environmental impacts of a building's energy use throughout its life, therefore temporary arrangements can be accommodated, provided there is robust evidence on future connection to the permanent systems.
24/08/2022 - Applicability to UKNC V6 confirmed

NABERS – Compliance with the requirements of Ene 01 - KBCN1463

Undertaking energy modelling for NABERs (DfP process) can be used to demonstrate compliance for the 4 predicted energy modelling credits and also the 2 exemplary credits for committing to post-occupancy measurement of energy.

On-site LZC – whole site shared connection - KBCN1424

To be recognised in BREEAM, the on-site Low and Zero Carbon (LZC) technology must have a direct physical connection to the assessed asset. OR Where the LZC technology is; It is acceptable to allocate the renewable energy generated proportionally as a calculation of the asset's predicted energy consumption compared to the total energy consumption of the whole site. To allocate renewable electricity by proportional consumption: Where consumption data is missing, renewable electricity must not be allocated to the assessed asset. In this case, it is assumed that all electricity consumed is sourced from the grid.
17-Jan-2024 - Applicability BIU V6 Ene 13 removed, as this approach is not applicable to assessing the area of PV fitted.
21-Dec-2022 - Applicability to In-Use V6 confirmed.
24-Aug-2022 - Applicability to UKNC V6 confirmed.

Parts of the building not subject to national thermal regulations - KBCN0534

Where you have parts of the assessed building which are not subject to national thermal regulations then these should be omitted from the EPR calculation.
24/08/2022 - Applicability to UKNC V6 confirmed

Prediction of operational energy and carbon – PHPP - KBCN1915

In applicable scheme versions (please see above), PHPP (Passive House Planning Package) will be considered as a compliant modelling approach for the prediction of operational energy (and carbon). This applies only to homes and small non-domestic buildings, where the building services are limited to: This methodology cannot be used where the building services include central air handling, mechanical cooling, or air conditioning.

Prediction of operational energy consumption – Multiple (similar) buildings assessments - KBCN1479

Sampling is not appropriate to meet the aim of the criteria; it is necessary to model the predicted operational energy consumption of all assessed units. Credits are awarded for undertaking the detailed modelling, therefore there is no requirement to identify the worst performing unit and KNCN1382 is not applicable.
24/08/2022 - Applicability to UKNC V6 confirmed

Prediction of operational energy consumption – alternative route to Excellent minimum standard - KBCN1336

Where the ‘Prediction of operational energy consumption’ criteria are achieved, the minimum standard for Excellent in Ene 01 is met. This is independent of meeting any minimum credit score in the issue to achieve the Excellent minimum standard. See KBCN1602. Substantial improvement To meet this minimum standard, the asset must show a substantial improvement in operational energy performance, following the ’Prediction of operational energy consumption’ criteria. This 'substantial improvement' is defined as achieving 4 credits using amended metrics generated using the dynamic simulation modelling and for: Amended definitions Performance is calculated based on amended definitions of an actual and a notional building: Amended actual building: Amended notional building: *The notional building servicing system may be replaced with a gas boiler as the heat generation source. Where the performance improvement over the amended notional building does not achieve 4 credits, the BREEAM Excellent standard may still be met. Robust evidence must be provided showing that this level of performance improvement is not possible, based on constraints outside of the control of the project team. Additional notes for UK schemes Projects assessed under UKNC V6.1 can manually input amended figures from the modelling into the platform to demonstrate the 'substantial improvement'. See "DSM Alternative Ene 01 inputs" in BREEAM Projects for this issue. For the energy modelling and reporting criteria, the CO2 metric can be calculated using either:
08-Nov-2023 - Additional wording and link to KBCN1602 added to clarify situation for UK simple buildings.
26-Jun-2023 - Content updated to apply to International schemes. Title and wording clarified. Text on manual errata in NC 2018 3.0 moved to KBCN1602.
14-Jun-2023 - Note added to confirm this is integrated into the platform for UKNC V6.1 in all countries. 
24-Aug-2022 - Content updated and applied to UKNC V6
19-Aug-2019 - Clarification for UKNC 2018 3.0.

Prediction of operational energy consumption – passive design analysis - KBCN1647

The credits for ‘Prediction of operational energy consumption’ in Ene 01 require the project team to have first identified opportunities to implement passive design measures. For Ene 01, it is acceptable for the analysis of potential passive design measures to be completed later than Concept Design if there are still opportunities to implement passive design measures in the project. The intention of including the criterion on passive design analysis in Ene 01 is to ensure passive design features that could reduce the operational energy demand of the building have been considered before credits are awarded for predicting operational energy demand. The analysis must occur when there are still opportunities to influence the design.

Registering assessments to UK NC2018 or UK NC V6 – Version of Part L - KBCN1535

BREEAM UK New Construction 2018 was developed for buildings in England which are demonstrating compliance against Part L 2013. The New Construction V6 version is intended for buildings in England which are demonstrating compliance against Part L 2021. Accordingly, UK NC 2018 will only accept 'inp' files created using Part L 2013 building regulations software for England and UK NC V6 will only accept 'inp' files created using Part L 2021 building regulations software for England.   Assessments already registered to BREEAM UK NC 2018 that must comply with the Part L 2021 of the Building Regulations may follow either of the options below:
  1.  Transfer to the UK NC V6 scheme
  2. Assess under UK NC 2018 and do two Part L models:
New assessments subject to Part L 2021 may register to UK NC V6 or follow Option 2, above.
10 Feb 2023 - Applied to Issue Ene 01 to improve visibility

Shell only – Alternative route to meeting the Minimum Standard for BREEAM Excellent - KBCN1880

The Minimum Standard requirement can be met where it is demonstrated that the fabric performance has been optimised, i.e. where a change in the value of any of the fabric parameters in either direction would lead to either an increase in the total heating and cooling demand, or to no further improvement.

When following this route, the number of credits awarded for Ene 01 Energy Performance must still be based on the building’s energy modelling results.


Shell only – retail glazing not within scope - KBCN0937

Where a retail building envelope is not complete and glazing will be provided by the future tenant/(s), there are two options available: A 'Green fit-out agreement' (see Definition under this Issue in the technical manual) can be used to ensure that the performance level of the glazing used in the energy model is met in the completed building. This must be accompanied by evidence that the performance of the assumed glazing does not impose overly onerous requirements on future tenants and that it falls within the scope of glazing typically used in retail developments. Alternatively, the assessment can be based on worst permissible performance under the relevant national building regulations. In all cases, for shell only assessments, the assessment method detailed in CN1 (for UK New Construction 2014 and International New Construction 2016) and Assessment type specific note 1.3 (for UK New Construction 2018 and UKNC V6) must be followed.
24/08/2022 - Reference and applicability to UKNC V6 added
14 11 2017 Wording amended to clarify the intent

Shell only – zero net regulated carbon emissions - KBCN1101

For Shell only projects, 9 credits can be awarded when the EPRED ratio is 0.90, without the requirement for zero net regulated CO2 emissions applying. Shell only projects only assess the buildings heating and cooling energy demand and so credits are awarded just on this basis.
24/08/2022 Applicability to UKNC V6 confirmed

Shell only – Energy modelling requirements - KBCN1488

For a shell only assessment, only the EPR demand metric is used to determine the energy performance. Therefore, we would not expect to see improvements to equipment and services accounted for in the BRUKL/NCM calculation. It is, therefore, recommended that assessors submit a BRUKL/NCM document incorporating the fabric improvements, but which retains the equipment and services of the notional building with heating and cooling provided by multi-split systems. Credits for shell only assessments are determined by the demand metric alone. The inclusion of more efficient equipment and services may, therefore, lead to lower heat gains, a subsequent increase in demand for space heating and, hence, a lower number of credits being awarded.
28 Aug 2022 - Guidance updated and applied to UKNC V6

Similar speculative developments (Shell and Core) - KBCN1382

For speculative, Shell and Core projects there will be a significant level of uncertainty regarding equipment loads and usage patterns. Project teams should make the best estimates they can based on available data for similar projects, instead of using the National Calculation Methodology occupancy assumptions. Where sites have multiple speculative, Shell and Core buildings it is acceptable for the 'Prediction' work to be the same across all the units. The design team would need to be sure that all the units would have the same type of tenant and be used in the same way. This is in keeping with the aim of the 'Prediction' credits; to predict energy consumption as accurately as possible. If the users are known to be different, this approach would not be acceptable.
24/08/2022 Applicability to UKNC V6 confirmed

Statutory requirements for energy modelling differ from BREEAM - KBCN0127

For the purposes of BREEAM, Issue Ene 01 should be assessed using a BRUKL output based on the prevalent UK country Building regulations applicable to that scheme. This applies even when the building does not need to undertake energy modelling to comply with Building Regulations.

Where a different analysis is required for statutory compliance, due to the location of the project or registration to an earlier or later version of Part L, a different output must be produced for this purpose.

Alternatively, where applicable, the BREEAM registration could be updated to the latest version, so the same energy model output can be used for both purposes. To maintain consistency and comparability for all assessments registered to a scheme.
24/08/2022 Applicability to UKNC V6 confirmed

Use of as-designed BRUKL output for post-construction submission - KBCN0889

Where it is not possible to produce an as-built BRUKL output for the post-construction assessment, it is acceptable to produce an updated as-designed BRUKL output that accurately reflects the constructed building as evidence for the post-construction submission. A justification should be issued to QA clarifying why an as-designed BRUKL was submitted, along with confirmation from the relevant specialist that the model is an accurate representation of the final, as-built specification of the building.
24/08/2022 Applicability to UKNC V6 confirmed

Information correct as of 19thOctober 2026. Please see kb.breeam.com for the latest compliance information.