New Construction / NOR /

V6

Information correct as of 29thNovember 2026. Please see kb.breeam.com for the latest compliance information.

Acceptable alternative strategies to sub-metering by floor plate - KBCN00071

An alternative sub-metering strategy, not based on a by-floor-plate basis, would be acceptable provided that: - it provides an equivalent, or more useful level of detail than sub-metering by floor plate. - it divides the assessment in a logical manner which provides useful information to building management re: energy use. - the approach does not conflict with requirements for sub-metering other functional areas. The intent of sub-metering by floor plate is to allow a large homogenous function (such as office space) to be split up into smaller areas that will allow building management to monitor, identify and influence areas of high energy use.  Alternatives that also meet this intent are also acceptable.

Accessibility Index used to award credits - KBCN1078

Points awarded for Sustainable transport measures: Option 1 must be based on the existing Accessibility Index for the development site. Improvements to the availability of transport services implemented by the project team may be recognised under Option 2.

Accessibility of energy metering systems - KBCN0580

Energy metering systems should be accessible and the energy consuming end uses visible to building users, such as the facilities manager, where present, and/or other building occupants responsible for the management of the building.

Achieving a reduction in noise levels where background levels are low - KBCN1692

Where existing background levels are low, such as during night-time, there is no dispensation or flexibility that can be applied in achieving the requirements.  The aim of the issue is to reduce the potential impact of noise from the assessed building to local noise-sensitive buildings.  Acoustic experts have confirmed that the requirements for the background noise levels are still appropriate where existing levels are low, including where a 5dB reduction is stated within the criteria.

Adaptability for a projected climate change scenario – Winter conditions - KBCN1715

Where future climate change scenario projections in winter indicates a higher temperature and, therefore, more thermally comfortable climate compared to the current winter temperatures, it can be assumed that the winter conditions within the climate change scenario are met based on the thermal modelling of current winter conditions. Justification must be provided for each project confirming that the future winter conditions will be met with the current heating system. In a warming climate the heating system needs to be sized for the beginning of its lifespan, whereas the cooling systems need to be sized for the end of their life span (Ref: CIBSE TM55: 2014)

Additional default values for calculating DELC CO2e - KBCN0195

The following additional default values may be used, where system specific data is not available: Refrigerant recovery efficiency factor (%): - 95% Annual purge release factor (% refrigerant charge):- 0.5 (if the system does not require an annual purge, zero should be used).

AI calculation – changes to public transport services during the assessment - KBCN1527

The AI is calculated as part of the design stage transport analysis and its value relates to the site location and to informing transport-related design decisions. This must be based on current information, including any planned and publicly-notified changes at the time the transport assessment is carried out. This should be used as the AI benchmark for the assessment. Where later, unforeseen changes to public transport availability are implemented before post-construction certification, the AI benchmark should not be updated at post-construction stage. Assessments should not be disadvantaged by, or benefit from such changes.

Alternative calculation method - KBCN0547

Where it is not possible to use the standard approach to determine the building’s total water consumption, the assessment can be completed on an elemental basis. This applies even in cases where the Wat 01 Excel calculator tool has a section for a broader building type, but the defined activity areas do not match the specific project under assessment. For example, although Wat 01 calculator includes a retail calculator, bars and restaurants should be assessed using the alternative calculation method, as no relevant data is available for the specific activity within retail. Where the activity areas of the building under assessment do not allow using the relevant building type’s calculator, then the alternative calculation approach should be used.

Alternatives to BEMS - KBCN0149

It is acceptable for sub-meters to connect (or have potential to connect) to automated meter readers (AMR's) or similar systems, as an alternative to BEMS . The core intent of issue Ene 02 is the monitoring of energy use, therefore if an alternative system can achieve this,it would be considered acceptable provided this could be demonstrated.

Amenities – Assessed building is one of the listed amenities - KBCN0264

Where the assessed building is itself included in the list of amenities, that particular amenity criterion can be deemed to be met, e.g. a supermarket development itself meets the proximity to food outlet required for a Retail type building.

Amenities – Community facility – Collaborative work areas (shared workspace) - KBCN1918

For appropriate building types, a collaborative work area can qualify as a community facility where it is demonstrated that:

Amenities – Enhanced amenities duplicating existing amenities - KBCN1406

Following feedback, BRE accepts that it is unreasonable to expect assessors to determine whether a new amenity is significantly different to all existing amenities in the vicinity. Furthermore, the introduction of any new compliant amenity may increase choice in terms of the amenity itself and its location relative to other facilities and transport nodes. It cannot, therefore, be reasonably argued that this cannot meet the aim of this transport measure, in reducing the need for local car journeys. New (enhanced) amenities may, therefore, be considered on their own merits, without reference to existing amenities.
Approach updated for all assessments 16/09/2021
Previous guidance for reference only:

Where an amenity is already present within the prescribed distance, a new amenity falling under the same category cannot be considered as an enhanced amenity, unless it provides a significantly different offering to the existing one. So, for example, if there was an existing fast food outlet and the development provided a new fast food outlet, this could not be considered, whereas a new grocery store or restaurant may be considered.

Note: This is applicable where the development itself could be considered an enhanced amenity, in line with KBCN0264

Assessors must use their discretion and justify the decision in their assessment report.

Amenities – Pharmacy within a hospital or health centre - KBCN0321

To meet the requirements of 'Over the counter services associated with a pharmacy', a dispensary within a health centre or hospital can be considered as meeting the intent, provided it is publicly accessible and also offers the type of over-the-counter services associated with a stand-alone pharmacy, such as non-prescription medication and health products. Note: This is a change to the approach outlined in the previous KBCN wording, therefore, for assessments registered before this update, where it can be demonstrated that the the assessor has advised the project team based on the previous wording, this can be accepted: Superseded guidance: A publicly accessible pharmacy would typically be required in order to constitute a suitable amenity. If it can be confirmed that an internal pharmacy (in Northern Ireland this may also include an onsite controlled medical dispensary) will provide prescribed medicines for building users, this is acceptable.
18 June 2025 - Title updated and wording amended to clarify the intent. Applied to NC V6 standards.

Amenities – Provided as part of a masterplan - KBCN1432

Where a masterplan scheme, undertaken by the same developer, includes a number of compliant amenities for Tra02, subject to meeting the criteria, these can be considered as 'new amenities' (rather than existing) for building level assessments on the site. A mixed-use masterplan supports the use of local amenities, without the need to travel by car. The ‘existing amenities’ criteria relate more to site selection.

Amenities – Sandwich van as a food outlet - KBCN0557

A food truck/ mobile catering service would not be sufficient to meet the criteria for this issue. The aim of this Issue is to assess the location of the built asset relative to amenities.

Amenities – Vending machine as a food outlet - KBCN0653

A vending machine can be considered as a food outlet if a range of items, as can be reasonably expected, are for sale to meet the needs of the building users and it is confirmed to be a permanent fixture.

Applicability – industrial operational areas - KBCN1342

The aim of this issue is to encourage a healthy internal environment.  For the operational areas of industrial buildings, the internal environment is dictated by health and safety requirements.  This means that the BREEAM requirements should not be made applicable to them, and so the operational areas can be ignored in the assessment of Hea 02.
10-Oct-2022 - Title amended for clarity and consistency. Scheme applicability updated.

Applicable amenities for different building types - KBCN1269

The guidance for Healthcare buildings does not identify childcare facilities or a school as an applicable amenity. Where these can be demonstrated to be of benefit to the occupants of the assessed healthcare building (staff), this amenity can be considered as applicable. Likewise, if it can be demonstrated that an amenity, not applicable to a particular building type, would provide a tangible benefit to the occupants of the assessed building, please submit details and justification to BREEAM for review.

Applying internal partition sound insulation criteria to internal doors - KBCN0665

Where sound insulation criteria apply to internal partitions the calculations do need to include any doors which are part of the wall in question. While sound insulation performance of a typical door will be lower than for a typical wall, with careful design, specification and detailing, this can be overcome. 

Applying the requirements to shell only + shell and core assessments - KBCN00075

A Suitably Qualified Acoustician (SQA) must carry out a quantifiable assessment of the specification of the built form, construction and any external factors that are likely to affect the indoor ambient noise levels. From this assessment, the SQA must confirm that the developer’s scope of works will enable a future tenant utilising a typical fit-out and specification to meet the levels required to demonstrate compliance with the BREEAM criteria. Where the specific room functions and areas within the building are yet to be defined, the acoustician’s assessment should demonstrate that the criteria for the most sensitive room type likely to be present in the building is capable of being achieved. Where the typical fit out would include a range of requirements (e.g. offices with a mix of open plan, cellular offices, meeting rooms and breakout areas; or retail with sales floor, stock/storage, office and staff rest areas), the acoustician should make an assessment based on a speculative layout and outline specification to determine whether the requirements of the relevant best practice standard are achievable and include examples of the most sensitive room types. Where the majority of a building’s floor plan will require high performance acoustic environments (e.g. classroom/seminar buildings), then the BREEAM requirements must be achieved for the entire shell where specific layouts are not determined by the built form. Post-construction testing is not required subject to confirmation from the project team that the built form, construction and any external factors have not changed from those used in the SQA's assessment.
14-Feb-2024 - Scheme applicability updated. Clarified applicability to shell only assessments. Title updated.
09-Aug-2019 - Updated applicability to UK NC 2018
08-Dec-2017 - Clarification added regarding post-construction evidence.
   

Assessing industrial spaces – exemptions - KBCN0734

The thermal comfort criteria do not apply to the operational or storage areas typically found in industrial assets or other similar asset types. The criteria is still be applied to the other parts of the asset as appropriate. Operational and storage areas often have function-related thermal requirements determined by operational or storage needs. These functional requirements override the needs of any occupants.
17-Jan-2024 - Scheme applicability updated.
03-Nov-2020 - Issue 2.0 of UK RFO technical manual updated with new CN detailing the above.

Bamboo, cork and other non-timber forest products – Responsible sourcing - KBCN1768

Non-timber forest products, such as bamboo and cork should be responsibly sourced to minimise the environmental impacts and protect local ecosystems. However, as they are not timber or timber-based products, these fall outside the scope of the Prerequisite. Where such products are integrated into a building, they should, nonetheless, be assessed and included in the calculator under ‘Other materials’.

BREEAM Advisory Professional (AP) – Retrospectively applying AP status - KBCN1080

The AP status cannot be applied retrospectively. The purpose of using an AP on a project is that they can advise and steer the development from the outset to maximise its BREEAM and sustainability performance for the least cost/risk. If early AP appointment and involvement does not occur then the aims and criteria of this BREEAM issue are not being met.

BREEAM AP – Achieving the design credit at the Post Construction Assessment - KBCN0215

Where a project will be undertaking a post construction stage assessment only (no interim assessment), to demonstrate that the criteria were met at the design stage a "BREEAM credit monitoring report" should be provided when the assessment is submitted, which shows that at the design stage of the project the building was still on target for the proposed BREEAM rating. This could be an excel document showing the issues that the design is on target for achieving with a short summary of how the BREEAM AP is steering the project for the correct rating. As long as the criteria are met and the correct information can be gathered for your evidence, a design stage certification is not required.

BREEAM AP – Change of BREEAM APs/Sustainability champions during project - KBCN0295

Whilst it would generally be preferable to retain the same individual in the role of BREEAM AP/Sustainability champion throughout the design and construction of a particular project for the purposes of continuity, we appreciate that this may not always be feasible. It is therefore entirely appropriate that the three credits available for using BREEAM APs/Sustainability champions can still be awarded where the individual performing the role changes (provided the ongoing involvement of an AP/SC is maintained in accordance with the criteria).  

BREEAM AP/Sustainability Champion appointment timing - KBCN0738

It is acceptable for the BREEAM AP/Sustainability Champion to be appointed later than the required stage, if it can be demonstrated that the AP/Sustainability Champion was appointed at the earliest appropriate time in the project and that the late involvement will not have a detrimental effect on the setting of BREEAM performance targets that need to be formally agreed no later than the concept design stage.

Building LCA tools recognised by BREEAM - KBCN1118

The following document shows the building LCA tools that are recognised by BREEAM for each BREEAM scheme. Only submissions from the tools listed here will be accepted as part of a BREEAM assessment. These recognised tools may be either an IMPACT Compliant tool or another type of building LCA tool that has been evaluated by BREEAM and considered suitable for carrying out building LCA according to BREEAM’s scheme specific requirements. To apply for a new tool to be evaluated, please contact: breeam@bregroup.com Where more than one version of the same tool is listed for a given scheme version, the most recent version of the tool (that is available at the point building LCA work commences on the project) should be used. It is acceptable to use subsequent, more recent releases/versions of a recognised tool (that have the same name as shown in the table). View Building LCA tools recognised by BREEAM.      
Table updated to new downloadable format, with new layout and new recognised LCA tools and corrections added 01/03/2024
Table updated to include new recognised LCA tools and corrections 10/11/2023
Table updated to include new recognised LCA tools and corrections 22/07/2022
Table updated to include new recognised LCA tools 12/03/2021
KBCN updated for clarity regarding subsequent tool versions on 10/03/2021

Campus with multiple building assessments - KBCN0597

If a campus development project has multiple building assessments being built in conjunction with each other, each building should be assessed independently.  Where there are noise sensitive buildings; including any new buildings in the process of being built, the criteria requirements must still be met.

Car sharing – aim and principles - KBCN1510

Aim The aim of this measure is that the asset’s management establishes, promotes and administers a process which encourages building users to share private car journeys to and from work, reducing the number of cars used for this purpose. Principles A car sharing group will, generally: A car sharing group is not: The criteria do not prescribe what terms and conditions should be implemented and, whilst the above principles should generally be followed, specific arrangements may vary. Evidence and justification must always be provided to demonstrate that the above aim is met.
21-Jul-2026 - Scheme applicability updated. Title updated for clarity and consistency.

Car sharing – calculation of priority spaces - KBCN0282

The calculation of priority spaces for car sharers should account only for the car parking capacity that is dedicated to the staff working in the building, without considering spaces for customers or visitors. Car sharing spaces should be clearly segregated from customer / visitor parking areas.
21-Jul-2026 - Scheme applicability updated.
06-Sep-2023 - Title updated to align with naming protocol.
23-Mar-2017 - Note added clarifying requirement for segregation.

Certificate validity – EMS - KBCN1401

The requirement for the principal contractor to operate an EMS relates to the duration of operations on site. Certification against ISO 14001/EMAS must be valid at the Design Stage and Post Construction Stage submissions and cannot be expired, pending or applied retrospectively.
07/05/2021: Clarification on Design and Post Construction Stage added

Combined sub-metering – electric space / water heating and small power - KBCN00068

For bedrooms and associated spaces in: It is acceptable for an electric space or water heating system to be combined with lighting and small power, provided that sub-metering is provided for each floor plate or other appropriate sub-division. For these asset types, sub-metering electric heating in multiple bedrooms may be costly and technically challenging. Where occupants have individual control but are not responsible for paying the utility bills, the building manager may have little influence on their energy consumption. Therefore, sub-metering electric heating would provide little or no benefit in meeting the aim of the issue.
06-Mar-2024 - Scheme applicability extended to V6. 
15-Dec-2023 - Title updated to clarify that this approach can be applied to both space heating and domestic hot water heating, where appropriate.

Combined system for heating / cooling and domestic hot water - KBCN0329

It is permissible to have combined metering for a shared on-site or district system that combines heating / cooling, and domestic hot water generation. In all cases, justification is provided in the QA report for the combined metering, and explains why it is not technically feasible to provide separate meters.
21-Sep-2022 Applicability of KBCN added to BIU V6. Amended to include district heating and cooling networks.

Commercial dishwasher appropriate data - KBCN0687

If the component is present in the building but the appropriate data is unavailable from the manufacturer's product information i.e. uses a different unit of measurement, then the baseline performance level for the specified component should be used in the WAT 01 calculator. BRE Global is unable to provide a calculation method to convert data in to the correct unit for the WAT 01 calculator tool.

Commissioning – Monitor and specialist commissioning manager - KBCN00051

The commissioning monitor is typically a project team member who will monitor the systems commissioning and testing programme for the building. The individual may combine that role with that of the specialist commissioning manager to deal with complex systems if they have the necessary knowledge. However, if the building has several specialist systems it is unlikely that the same person would be able to carry out all of the commissioning and more than one specialist would most likely be required.

Communal Laundry Facilities – Commercial Sized Tumble Dryers - KBCN0555

Tumble dryers should be taken in to account when calculating the total annual unregulated energy consumption of communal laundry facilities with commercial sized appliances.  Heat recovery from a commercial sized tumble dryer exhaust can be used as an alternative to the solutions listed within the Ene 08 credit issue provided it will achieve a meaningful reduction of energy demand, and justification can be given as to why  this method has been implemented over those recommended in the manual.  The list of equipment types and compliance requirements is not intended to be exhaustive, however where alternative solutions are proposed, the design team must provide justification and evidence as outlined above, to the satisfaction of the assessor.

Communal Laundry Facilities – Domestic or Commercial Washing Machines - KBCN0613

The table provided in the manual highlights the criteria for an appliance to be considered domestic or commercial. However, for multi-residential projects (or other building types containing laundry facilities), the BREEAM assessor should use their judgement to determine whether the appliance is commercial or domestic, and justification of the category selected must be provided. For instance, commercial and domestic sized washing machines can be defined based on load size or power rating.

Community transport schemes in rural areas - KBCN1082

In rural areas, where scheduled public services may be limited, community transport schemes, including 'on-demand services', should be noted in the 'Transport assessment and travel plan', however unscheduled services cannot be accounted for when calculating the AI. The provision of new a community transport scheme may be recognised under 'Sustainable transport measures' as a 'dedicated service', provided that:

Compactor/baler requirement – Tenant obligation - KBCN1920

Where the installation of a waste compactor is applicable, but it is demonstrated that this will be a tenant obligation, the compactor itself does not have to be provided. Instead, an appropriately sized space and services or infrastructure to accommodate the relevant facilities must be provided.  This must be an identified, dedicated and suitable space, and evidence must be provided to demonstrate that this will be a tenant obligation. Suitable evidence of this includes: 

Compactor/baler/organic waste storage requirements – Speculative/Shell only/Shell and core - KBCN1662

For Shell only/Shell and core assessments and speculative developments, where the scope of works does not include the installation of such facilities but the building function suggests that they will be required, appropriately sized space, services and infrastructure for the relevant facilities must be provided. The facilities themselves do not necessarily need to be provided or installed to demonstrate compliance.
01 Oct 2024 - Title and wording updated to clarify that this approach can be applied for shell only and shell and core, as well as speculative projects. Applied to International NC.

Control of glare from sunlight – adjacent buildings - KBCN1248

It is acceptable to account for surrounding buildings, structures or other permanent environmental features when using simulation modelling to assess the risk of glare, provided this accounts for both direct sunlight and reflected glare from glazing or reflective surfaces.
This KBCN aligns with KBCN1211 from UKNC 2014

Control of glare from sunlight – hotel rooms - KBCN1087

The primary function attributed to hotel rooms is that of a bedroom and as such, lighting and resultant glare are not considered to be problematic for these spaces. The only exception to this is where designated additional office space is provided. In these circumstances it is the role of the assessor to determine if individual spaces should be determined as ‘relevant building areas’ in accordance with guidance provided. Glare control criteria apply to building areas where lighting and resultant glare could be problematic for users.
01 Nov 2023 - Applicability to BIU V6 Commercial confirmed
This KBCN aligns with KBCN0666 from UKNC 2014

Control of glare from sunlight – roof lights - KBCN1091

Where roof lights are present, they must be considered when demonstrating that the glare control strategy provides adequate control/measures for minimising glare in that space. All sources of glare need to be considered when designing out the potential for disabling glare.
This KBCN aligns with KBCN0319 from UKNC 2014

Control of glare from sunlight – types of glare - KBCN1043

Assessors should ensure that the design team has considered the possibility of glare from all sources, including direct sunlight, reflected sunlight and contrast glare.

Control of glare from sunlight- no windows in relevant areas - KBCN1088

Where a ‘relevant area’ as defined in the manual does not include any windows, the glare control criteria can considered as met for this area. Note that the view out and daylight criteria would not be achieved in rooms with no windows. Where there are no windows in a room there would be no potential for disabling glare, so the aim of the credit would be achieved.
This KBCN aligns with KBCN0146 of UKNC 2014

Cycle spaces – Minimum and maximum requirements - KBCN0637

These remain applicable where the 50% reduction allowed for building locations with a high level of public transport accessibility is in effect. This means that, for instance, a large retail will still need to provide at least ten customer cycle storage spaces and could meet compliance with a maximum of fifty.
22-Nov-2023 Scheme applicability updated.
18-May-2017 Previous KBCN on large retail adapted to include any minimum requirement for cycle storage spaces.

Cycle spaces – Compliant types of storage - KBCN0257

Due to the number of different types of cycle storage facility available and the variation in site conditions, BREEAM New Construction is less prescriptive about the dimensions and type of cycle parking which can be used to demonstrate compliance. The Assessor is expected to exercise their professional judgement to determine whether the cycle parking spaces meet the aims of the Issue and the requirements listed in the compliance notes. BREEAM is used to certify buildings, not products. Cycle parking systems cannot, therefore, be considered inherently 'BREEAM compliant'. These must be assessed in context with reference to their location and the intended user profile.  
29/01/2024-made applicable to HQM

Cycle spaces – Folding bicycles and scooters - KBCN00024

The provision of cycle storage that is only suitable for folding bicycles or scooters is not compliant. Providing reduced storage space for folding bicycles or scooters in place of compliant cycle storage may limit future travel options.
14 03 2018 Wording clarified and reference to scooters included.

Cycle spaces – Large retail - KBCN0528

For large retail developments that provide at least 50 customer cycle storage spaces, this meets the requirement for customer spaces.  The requirement of one cycling space every 10 staff needs to be met in addition to this.

Cycle spaces – Maximum number of stadium visitors - KBCN0323

To calculate the required provision, the sliding scale of compliance should be used for the staff and up to 5000 stadium visitors.

Cycle spaces – Prominent location - KBCN00053

The requirement to provide cycle storage facilities in a prominent location on site, within view of building users, is intended to encourage use through advertising their presence to building users. Providing these facilities inside the assessed building, such as in the basement, may be compliant so long as there is prominent signage to indicate their location to all building users.  

Cycle spaces – Provision for regular, large visitor numbers - KBCN0546

Where there are large numbers of visitors on a regular basis, provision of cycle storage for visitors should be based on the maximum number at any given time. This is to ensure that at peak times enough cycle storage is provided.

Cycle spaces – Similar buildings assessments - KBCN0570

Where cycle storage and/or facilities are provided for individual units, a site-wide approach cannot be used to include all units. If, however, these are a shared facility, provided in a suitably-located communal area, this may be acceptable. When assessing using the 'similar buildings' approach, each of the similar buildings  has to be assessed separately and credits have to be awarded, based on the worst performing building.
14 03 2018 Clarified to account for suitable shared facilities
 

Cycle spaces – Small retail – multiple units - KBCN0187

In a development of multiple small retail units, to achieve credit, 10 compliant cycle storage spaces in total are required where it can be shown that these are accessible to all units. However, where such developments consist of multiple units over a large area or are separated by barriers such as roads, the assessor should ensure that the provision is both adequate and conveniently located for all units. The 50% reduction allowed for building locations with a high level of public transport accessibility is not applicable in this case.
17/11/2016 Note related to the 50% reduction added.
14/03/2018 Note added regarding multiple units over a large area or separated by barriers. 


Cycle spaces – Timing of installation in phased projects - KBCN00015

Where cycle storage cannot be installed at construction stage, due to phasing and / or pending demolition works, compliance may still be demonstrated provided: - Clarification and justification is given for why the storage is not currently available. - A written contractual agreement is in place to provide BREEAM compliant storage within a clear timescale. - Alternative storage is provided in the meantime that allow bikes to be easily stored and removed, with the ability to be locked securely against a fixed structure. The methodology above applies to cycle storage only, and cannot be applied to provision of cyclist facilities (such as showers and lockers) which must be assessed as normal. This is to allow flexibility within the project programme for the installation of the final, permanent BREEAM-compliant cycle storage whilst still ensuring adequate cycle storage is available during the construction phase.

Cycle spaces and facilities – Rounding calculations - KBCN0445

The calculation for the required cycle spaces and facilities must always be rounded up. If the calculation works out as 5.3 cycle spaces, 6 cycle spaces must be provided. To determine the requirements for developments with multiple types of building user, calculate the requirement for each user group separately (rounding up to the determine the number of spaces) and then add the number of cycle spaces for each user group together.
04/10/2018 Wording amended to clarify the correct calculation method for developments with multiple user groups.

Cycle storage – new spaces in the public domain - KBCN1410

Where it is not possible to locate short-term visitor/customer cycle storage spaces within the assessment boundary, these may be provided in a suitable and convenient location within the public realm. The assessor must be satisfied that there is legal agreement and a long-term commitment to the provision of the spaces. All relevant criteria must be met, however, where justified, the requirement for overhead covering can be waived. BREEAM accepts that for cycle storage spaces within the public realm, there may be restrictions on the ability to provide overhead covering.

Cyclists’ facilities – Adequately sized lockers - KBCN0961

The requirement for adequately sized lockers is so that cyclists have a dedicated space to store their cycling equipment and clothes. It is not compliant for the space requirement to be met by providing two or more inadequately-sized lockers for each cyclist. Requiring cyclists to separate their equipment into different lockers/storage spaces could create a barrier to uptake of commuting by bicycle.

Cyclists’ facilities – Combining different facilities - KBCN0683

Cyclists' facilities can be combined, provided that all relevant compliance requirements are met and it is demonstrated that there is no conflict impacting on their use. For example, compliant showers can be combined with compliant lockers in one room, subject to the principle below. For combined facilities to count as multiple facilities, they must be capable of being used independently of each other at the same time (where relevant) with reference to any space requirements, access, gender and privacy issues.
11 Jan 2023 - Applicability to BIU V6C confirmed
10 Feb 2022 - Updated to clarify that facilities can be combined where there is no conflict.

Cyclists’ facilities – Matching additional cycle spaces - KBCN00093

The minimum number of showers/lockers/changing facilities required for BREEAM compliance is determined by the minimum number of compliant bicycle spaces required, not by how many total compliant bicycle spaces have been provided. Where more than the minimum number of compliant cycle spaces has been provided, there is no requirement to provide more than the minimum number of showers/lockers/changing facilities.
01 Feb 2022 - Wording clarified and applicability to BIU V6C confirmed
 

Cyclists’ facilities – Multi-residential / residential institutions - KBCN0967

Where there is a BREEAM requirement for residents, compliant facilities within their accommodation can be considered as cyclists' facilities. Separate facilities for staff must be provided as required to achieve compliance.
22 Aug 2023 Applicability to BIU V6 Commercial confirmed.

Cyclists’ facilities – Provision of only one shower - KBCN0566

Where only one shower is provided, this needs to cater for users of both genders. For a changing facility to count as an additional amenity, it must be capable of being used independently of any showers, otherwise it could not be considered as two facilities. A shower which is a mixed gender facility must be capable of being used privately. As such, it requires adequate private changing space associated with it.
Amended to provide further clarification and to add the general principle.
10/11/2016

Cyclists’ facilities – Shell only/shell & core assessments - KBCN0882

Cycle parking must be provided as part of the base-build for all assessment types. Where compliance is sought for additional cyclists’ facilities, the developer should provide all aspects of the installation which fall within the scope of their work and facilitate the future completion of any aspects which do not. For shell & core assessments, if additional facilities, such as showers and drying space, are not provided in core areas and internal walls are not provided to tenanted areas, these must be indicated on design drawings and all relevant services provided. This would include capped-off supplies and electrical points as necessary in order to facilitate the completion of the compliant facilities by the tenant. Where internal walls are within scope, a compliant changing area must be provided, however for lockers, compliance can be achieved by providing a design drawing showing that there is an adequately sized and suitably located space for the required number of compliant lockers. The developer should do as much as they can, within the scope of their work, to facilitate the future installation of compliant facilities and should not do anything which would make future installation more onerous.
01 Oct 2024 - Addition paragraph added to clarify the approach for changing areas and lockers.
25 May 2018 - Wording amended to clarify the intent.

Cyclists’ facilities – Visitors - KBCN00014

Where the cycle spaces requirement is based on the number of staff plus visitors, customers or patients, the number of cyclist facilities required to demonstrate compliance is based on the number of cycle spaces for staff only. Visitors, customers or patients would not be expected to have access to showers and lockers within a building.

Cyclists’ facilities – Within toilet facilities - KBCN00050

To comply with the criteria for cyclist facilities, showers should not obstruct the use of other facilities. Where a shower is located in a room with a WC, this cannot be considered compliant, unless it can be unequivocally demonstrated that the WC is provided over-and-above the requirements of relevant standards or regulations for general and disabled WCs.

To ensure that there is no conflict between the use of general or disabled WCs and the use of cyclist facilities.
25.10.18 KBCN reworded to improve clarity.
 

Daylighting – Changing rooms - KBCN1132

The daylighting criteria are not applicable to changing rooms.

Daylighting – requirements differing by area - KBCN0176

Where areas within a building have different daylighting requirements for the same credit, all relevant areas must meet the requirements to award the daylighting credit(s). The aim is to improve daylight conditions in all applicable area types of an assessed building.

Daylighting – studio flats - KBCN0808

In the case of studio flats, the minimum area of compliance for the average daylight factor requirement is based on the combined area of kitchen, living room, bed and study area. Circulation areas do not need to be included in the calculation.

Deemed to comply solutions – alternative proposals - KBCN1214

The solutions listed for each category in the Table are examples deemed to comply with the requirements, without further justification or calculations to demonstrate a meaningful reduction in unregulated energy consumption. If an alternative solution is proposed, justification and/or calculations are required to demonstrate this.

Default occupancy rates by building type - KBCN1496

The values given in the table, 'Default occupancy rates by building type' are sourced from the Activity Database of Simplified Building Energy Model (SBEM). For certain building types, the occupancy rates produced may be unrealistic. In such cases, the assessor should refer to: 'Methodology > Number of building occupants unknown'.

Definition – Critical value - KBCN1006

Critical value aims to maximise whole life value of the building based on client requirements, and differs from minimising life cycle cost. This is a more specific analysis of how the building's ongoing maintenance and operation can impact business needs. For instance:  

Demand-based bus services in AI calculation - KBCN1338

Demand-based bus services operated by public transport providers can be included in the calculation of the Accessibility Index. The project team will need to determine an average number of stops per hour to allow input into the AI tool.

Dementia care homes - KBCN0820

For dementia care homes, there may be instances where the resident profile, and hence design and use, result in some BREEAM criteria being considered inappropriate or not applicable. Where this is the case assessors should seek confirmation from BREEAM through the technical query service, providing a clear justification for why specific criteria cannot be met. Before submitting a query, however, please review the BREEAM Knowledge Base under the relevant Scheme and Issue, to check for a specific, published compliance note. Assessors will be required to provide evidence. This could be from suitable individuals/organisations regarding the specific project, detailing how the criteria is not relevant for the individual project.

Design team meetings via conference call - KBCN0201

Design team meetings can be conducted via conference calls.

Conference calls may provide a more convenient and sustainable way to conduct meetings. 


Designed-out or integrated finishes - KBCN1066

The requirements for this credit are met when either: This issue recognises avoiding unnecessary waste of materials.
16-May-2023 - Merged with KBCN0046. Scheme applicability updated. Name updated for clarity.
 

District cooling – Used in combination with local cooling - KBCN1634

Where district cooling can be considered outside the scope of the assessment, either in accordance with the Methodology section of the technical manual or in line with KBCN0759, compliance must be based on calculating the DELC for all systems. However, where the district cooling system is exempt from assessment, as described above, this should be based on a GWP of zero for the district cooling system.

District heating systems – fuel mix - KBCN0885

Where the feasibility study is considering connection to a district heating system and this burns a mixture of fuels, only the proportion of output generated from second generation bio-fuels (or waste incineration that complies with BREEAM requirements) can be considered for this issue. For instance, a system burning a 25/75 mix of compliant biofuel vs fossil fuel can only count 25% of its output towards a meaningful reduction in CO2 emissions (where relevant to the BREEAM scheme) against the baseline building. As fuel mixes may vary over time, at least one year or more of historical information must be provided to balance out any seasonal variations. Where the system is new or proposed, robust evidence must be provided of the anticipated fuel mix. The fuel mix must be calculated based on the energy content of the input fuels in kWh.
19/12/2017 Wording clarified

Domestic hot water supplied by a circulation loop - KBCN1017

Where a circulation loop is used on the domestic hot water supply, it is acceptable to only sub-meter the cold water supply. Sub-metering such systems may be impractical and the occupant can use the cold water meter readings as a proxy for overall water usage in relevant areas.

Drying space in hotel/ hostel projects - KBCN0174

The Drying space issue is not applicable to projects where occupancy is transient, such as hotel or hostel type developments, but does apply to long term residential buildings. There is little potential in reducing the energy from drying clothes in hotel and hostel bedrooms compared to long term residential buildings.

Education – Different age ranges and/or non-acute SEN - KBCN0224

For a combined school campus the number of cycle storage spaces and compliant facilities will need to be calculated individually for each user-group of the building; e.g. the number of facilities for nursery schools, primary schools and secondary schools should be calculated as per the criteria defined for each of these education types and totalled. Where this includes non-acute SEN facilities and the unusual structure of the classes prevents standard assessment, the assessor should use their judgement to determine whether to apply the pre-school criteria or base on the total number of staff and students. While within the scoring and reporting tool the dominant education building type category will be selected, calculations need to be provided as supporting evidence, with the assessor's comments/notes used to clarify the calculation used to demonstrate compliance.
14 03 2018 - clarified and key information incorporated from KBCN0424

Electric Vehicle (EV) Charging – Shared Parking for New Buildings, Extensions, and Phased Developments - KBCN1827

The required number of EV charging points must be based on the total number of parking spaces that serve the assessed building. This total includes both existing spaces and any new spaces associated with the project. Where parking is shared across a wider site, the “associated” number of spaces refers to the amount of parking the assessed building is expected to rely on for its occupants. A proportional allocation calculation must be used to determine this number. Example: If a project sits on a site with 1,000 shared spaces but the new building’s occupancy requires only 100 spaces, the EV requirement is calculated based on 100 spaces, not the full 1,000.
 
  1. General Requirements
    • Defining the parking that counts. Use a proportional allocation method to determine how many spaces in a shared car park are associated with the project.
    • Short-stay exclusion: Short-stay spaces with a maximum stay of 15 minutes (e.g., pick-up/drop-off bays) are excluded from the EV calculation.
    • EV Charging points location: EV charging points should be installed as close as possible to the building’s main entrance to ensure convenient access for the building users.
    • Existing infrastructure: Existing EV charging points in a shared car park can only be counted when:
      • They exceed the BREEAM requirement for the buildings they were originally installed to serve,
      • They meet current BREEAM requirements, and
      • They form part of the new project’s allocated parking.
    • No “legacy” exclusions: Existing parking spaces cannot be excluded simply because they predate the BREEAM assessment. If the spaces serve the assessed building, they are in scope.
    • Operational policy. It is recommended, but not mandatory, that building management implement operational measures (e.g., signage, permits, digital access controls) to help ensure that EV spaces are used by the intended building users.
  2. New Buildings on a Site or Extensions
    • Calculation basis for new buildings or extensions, EV requirements must be based on the total parking demand associated with the project, including both existing associated spaces and any new spaces created.
    • Proportional allocation formula
      • Determine the project’s share of the total site parking using either GIA or occupancy.
      • Allocated project parking = Total site parking × (Project GIA ÷ Total GIA), OR
      • Allocated project parking = Total site parking × (Project occupancy ÷ Total occupancy)
  3. Phased Development
    • Current Phase: The EV calculation should be based on the parking demand of the phase under assessment, including the existing infrastructure and any new parking spaces delivered in that phase.
    • Existing Infrastructure: EV charging provision installed in previous phases may count towards compliance where it meets the required threshold for the current phase
    • Future Phases: Provisions in future phases may be counted only if secured by a legally binding commitment (such as a signed contract or planning obligation) with a confirmed delivery timeline.

Electric vehicle charging stations (EVCS) – Priority spaces - KBCN1429

The current criteria for EVCS do not address provision for priority spaces, such as those allocated to disabled use and car sharing. The assessor and design team should, therefore, take a pragmatic approach to this and, where the overall number of required EVCS permits, an appropriate proportion of these should be provided for priority spaces. This will not be deemed as 'double-counting' as the number of EVCS required should be considered independently of other requirements. The intent is that electric vehicle charging spaces are available to all building users (where possible).

Electric vehicle charging stations – Availability - KBCN1128

This option requires the number of electric vehicle recharging stations (EVCS) to be based on a percentage of the total car parking for the building. To meet compliance, the intent is that recharging stations be available to all building users, including customers and visitors. However, where overall parking numbers are low, it may be difficult to effectively distribute the EV charging spaces between general users and priority groups. In such cases, the design team must provide evidence that this aspect has been considered when locating the EV spaces, however, the decision on how to distribute these may be made by the client or, for speculative development, by an appropriate member of the design team. In situations where parking is limited to priority spaces only, the above guidance still applies.
11 Jan 2023 - Applicability to BIU V6C confirmed
17 Sep 2022 - Updated to allow more flexibility in relation to how EV spaces are allocated

Electric vehicle charging stations – shell & core assessments - KBCN1247

For BREEAM NC shell only/shell & core, RFO Parts 1 and 2 only and partially-fitted residential assessments, compliance can be demonstrated by installing all the necessary infrastructure, (i.e. capacity in the connection to the local electricity distribution network and distribution board, as well as sub-surface ductwork to receive cabling to parking spaces), to enable the simple installation and activation of charging points at a future date.
18/10/2021 Applicability to BREEAM Scheme and Assessment Type clarified, in line with the intent.
15/11/2019 Incorrect reference to pre-installation of 'cabling' removed.

Electric vehicle charging stations – Short-term visitor spaces - KBCN1735

Where it can be demonstrated that parking spaces for visitors will only be used for short-term parking (a maximum of 15 minutes), these spaces can be excluded from the calculation for EV spaces. This exclusion will typically apply to certain types of retail outlet, where visitors are, for example, collecting or dropping off orders. However, other situations can be considered, where justified.

Emergency lighting - KBCN0185

Maintained systems featuring emergency light fittings which are also used for normal operation, are assessed for this issue. Non-maintained lighting which is only activated in an emergency can be excluded from the assessment. NC / RFO / BIU V6 Ene 17: The aim of these credit(s) is to encourage and recognise energy-efficient fittings. Non-maintained emergency lighting will very rarely be activated and in such extremes the emergency requirements must not be compromised. BIU V6 Hea 05: Flicker is eliminated from maintained systems only.
24-Jan-2024 - Scheme applicability updated to include BIU V6.

Emissions – measuring heating demand - KBCN0182

Emissions for all heat sources should be measured under normal operating conditions which are when all heat sources from the building plant are operating to their maximum design heat outputs to meet the building's heating demands. Where plant is designed to operate below maximum capacity, for example multiple or modular systems or standby boilers,the emissions should still be calculated for the plant operating to meet the building’s heating demand. Any redundant capacity or standby plant should not be included.  

Emissions from products – EU CLP Regulation and Category 1A/B carcinogen emission limits - KBCN1280

The European Regulation (EC) No.1272/2008 on classification, labelling and packaging of substances and mixtures (‘the CLP Regulation’ or ‘CLP’) applies to all EU Member States. CLP requires manufacturers, importers, downstream users and distributors to communicate the identified hazards of a substance or mixture to the other parties in the supply chain, including to consumers. The regulation requires products with hazardous properties to be labelled in accordance with CLP before being placed on the market. CLP requires products containing any ingredients that have been classified as Category 1A and 1B carcinogens to be labelled as carcinogenic. Therefore, with respect to the BREEAM Category 1A and 1B carcinogens emission limit criteria, for products marketed in EU Member States, if a product’s safety information (e.g. safety data sheet) or a manufacturer’s declaration confirms that that the product does not need to be labelled as a Category 1A or 1B carcinogen in accordance with CLP, then this information would be an acceptable form of evidence for demonstrating compliance with the criteria.
10-Oct-2022 - Title amended to align with standard KBCN naming format for clarity and consistency. Made applicable to UK and International NC V6.

Emissions from products – installations manufactured off-site - KBCN0137

Internal finishes to installations manufactured off-site such as elevators need to be assessed for the emissions from products criteria. The specification of internal finishes (regardless of whether they are installed on site or in the factory) will impact on VOC emissions. By specifying low VOC finishes, design teams will be encouraging manufacturers to consider the environmental impacts of their products.
10-Oct-2022 - Title amended to align with standard KBCN naming format for clarity and consistency. Made applicable to UK and International NC V6.
 

Emissions from products – manufacturers’ calculations for paints and varnishes - KBCN0452

Manufacturers' calculations of VOC content, based on the constituent ingredients, can be used to demonstrate compliance with the testing requirement for paints and varnishes.

10-Oct-2022 - Title amended to align with standard KBCN naming format for clarity and consistency. Scheme applicability updated.

Emissions from products – scope of assessment - KBCN0212

General This issue covers any product installed or applied inside the inner surface of the building’s infiltration, vapour or waterproof membrane. Where this membrane is not present, it applies to the inside of the building envelope’s interior-facing thermal insulation layer. Only products that are installed or applied in parts of the building where their emissions are likely to affect indoor air quality need to be assessed. Paints and coatings Any decorative paints and varnishes that occupants are exposed to should be assessed. This is likely to include paints and coatings applied to walls, ceilings, floors, doors, etc. Whole products A finish applied to a product in the factory is assessed as a whole product, and not separately as a paint or coating. For instance, a wood panel has a finish applied in the factory. The whole panel, including all the elements that make up that panel, would need to comply with the requirements set for wood panel products in this issue. The finished product as a whole must meet the performance requirements / emission limits set in the manual.
30-Oct-2025 - Applicable to HQM V6 and UKNCR V6.1
11-Oct-2022 - Title amended for clarity and consistency. Content merged with KBCN0871.
10-Oct-2022 - Wording simplified. Scheme applicability updated.
16-Jun-2017 - Title and general principle amended to extend the applicability of the KBCN to all finishes. Paints specified for specialist applications covered in KBCN0872.
 

Emissions from products – specialist paints and coatings - KBCN0872

Where a paint or coating falls within: then the paint or coating must be assessed. Specialist paints and coatings are exempted from meeting the VOC content and emission limits where there are no alternative products available that can perform the function, and still meet the emission limits. This must be clearly evidenced.
30-Oct-2025 Applicable to HQM V6 and UKNCR V6.1
02-Oct-2025 Reference to 'VOC content' added and KBCN applied to UKNC V7 and INC V7 to clarify CN2.1 
27-Oct-2022 Wording clarified. New compliance principle added from UKNC V6.
10-Oct-2022 Title amended for clarity. Scheme applicability updated.
13-Mar-2020 KBCN amended to clarify exceptions and applicability.
16-Jun-2017 Content merged with KBCN0212.

Energy efficient laboratories – scope - KBCN1254

This Issue is also applicable to 'Offices with Research and development areas'  and other buildings with research and development facilities that contain laboratory space and containment devices/areas.
Technical manual to be updated accordingly in next reissue.

Energy sub-metering – Single occupancy & function - KBCN0491

In large buildings of single occupancy/tenancy where there is only one homogeneous function (e.g. hotel bedrooms, offices), sub-metering should be provided per floor plate.  

Environmental management – Timing of obtaining ISO 14001/EMAS certification - KBCN0229

The contractor must be in possession of the ISO 14001/EMAS certification prior to starting works on the development under assessment. This is to ensure that the aim of the issue, to ‘encourage construction sites managed in an environmentally sound manner’, can be achieved. To uphold the robustness of BREEAM, the date of certification to ISO 14001/EMAS must be prior to initial works starting on the site.  

EPD for systems of products always installed together - KBCN1102

Where an EPD is for a system of products, from the same manufacturer, that are always installed together, this system of products shall be considered a single product for the purposes of assessment in BREEAM. Examples of this include:

EPDs’ validity - KBCN0798

EPDs which have expired or are pending verification at the time the relevant product was specified, cannot contribute to awarding credits. However, it is not necessary that they are valid at the time of the design or post-construction stage submissions. BREEAM is primarily trying to encourage designers to take EPDs into consideration when specifying products.  
04/11/2019 Confirmed applicability to UK NC2018
27/03/2020 Added applicability to Green Guide ratings and ISO 14001 certificates
27/05/2020 Reference to ISO 14001 removed - Whilst the same principle applies, the wording relating to product specification does not - See KBCN1401.
12/08/2021 Clarification regarding the validity of EPDs during QA submission and removal of reference to Green Guide ratings

Erratum – Commissioning and handover – Shell only assessments - KBCN1591

There is an error in the assessment scope of Man 04 under Shell only. 'Ref 1.1' does not apply to Shell only assessments This will be corrected in the next re-issue

Escalators or moving walks – variable speed drive - KBCN1621

The requirements refer to 'a load sensing device that synchronises motor output to passenger demand through a variable speed drive'. The intent is that the inverter must operate full-time to moderate output based on passenger demand.

Evacuation lifts - KBCN0437

Evacuation lifts, which will be used during an emergency only, can be excluded from the relevant BREEAM criteria. However, if these lifts are used during the normal operation of the building, then they still need to be assessed.

Existing travel plan - KBCN1068

If an up to date organisational travel plan, that is BREEAM compliant, exists for a site on which an assessed building is located, it can be used to meet the relevant criteria. All building users (in existing and new buildings) and additional travel resulting from users of the new building need to be taken into account.  

Extending a lift shaft - KBCN0802

Where the scope of works regarding a lift only includes extending the lift shaft to other floors, then assessment of this lift is not appropriate.  Where changes are made to the lift system, then assessment is required. Where changes to lift systems are made, these lifts need to be included in the assessment to encourage specification of energy efficient transport systems.

Extension to existing buildings - KBCN1039

Facilities within the existing building can be used to assess compliance. These facilities must cater for the total volume of predicted recyclable waste arising from the new extension and existing buildings.

Extensions – Retaining existing heating plant - KBCN0336

When assessing an extension where existing heating plant is retained, the current emissions output should be used to determine compliance. The emissions should not be taken from the original manufacturers information at the time of installation.  

Extensions and infill developments - KBCN1055

When assessing a new extension or infill development on an existing site, only new lighting specified as part of the assessed works needs to be considered.

External lighting – architectural façade lighting - KBCN0650

Architectural façade (or other decorative) lighting, which does not provide users with lighting to perform tasks outdoors, does not need to be included in the assessment of external lighting. This Issue seeks to ensure that lighting levels are appropriate for tasks which building users will be undertaking outdoors.

External lighting inside wider building - KBCN0906

Where a building undergoing assessment is located inside of another building, for example a retail unit within a shopping centre, Ene 03 External lighting and Pol 04 Reduction of night time light pollution should be assessed as follows; Ene 03 'External lighting' that is inside of the wider building, using the example above the lighting is external of the retail unit itself but inside of the wider shopping centre, criteria relating to the luminous efficacy should be applied as presented within the manual. For the criteria relating to controlled for prevention of operation during daylight hours and presence detection in areas of intermittent pedestrian traffic, however, instead of demonstrating that the lighting is not operational during daylight hours, it should be demonstrated that the lighting is not operational outside of the operational hours of the wider shopping centre. Any external lighting within the scope of works being assessed that is located outside of the wider shopping centre, for example if the retail unit had an entrance or exit that leads on to the street outside, this would need to be assessed against the criteria presented within the manual. Pol 04 If the building undergoing assessment has no external lighting that is outside of the wider building, it can be considered that the building has no external lighting. However, as above, any external lighting within the scope of works of the assessment that is located outside of the wider building will need to be assessed as the criteria is presented within the manual.
10/05/2019 Reference to specific criteria numbers removed and made applicable to UK NC2018

Feasibility study – comparison with connection to existing LZCs - KBCN0563

In carrying out a feasibility study (covering all the areas required as stated in the manual) the primary intent is to demonstrate to a reasonable level of certainty that the chosen LZC is the most appropriate of all those available. Some of the options (for example community heating/cooling schemes) may not allow for a simple like for like comparison but a comparison can be made overall across many factors. For example in a community heating scheme the life cycle costing estimate might need to be simply the cost of using and maintaining the system for the measuring period, if upfront costs and payback period information is not available. Similarly for an existing community scheme, planning would not be a barrier but land use and noise impacts could be compared. The feasibility study must include a comparison of all criteria and for it to show that each has been factored into the final option being made. While some options may provide information in different formats and differing levels of detail making direct comparisons not straightforward, a comparison can still be made and this should aim to be as comprehensive and representative as possible. This will serve to demonstrate with reasonable certainty that the chosen option is the most appropriate. 

Fire hydrants and sprinklers – Leak detection - KBCN0680

Where it is confirmed by an appropriate project team member that it is not possible to fully meet the leak detection criteria for fire hydrants or sprinklers, an alternative approach can be implemented for these systems. This must demonstrably meet the aim of the issue by detecting and alerting the building management to major water leaks.   Previous guidance - superseded on 30 May 2024 To meet BREEAM compliance, emergency systems such as fire hydrants and sprinklers need also to be covered by a leak detection system. The leak detection system must cover all mains water supply between and within the building and the ‘site boundary'.
11 Sep 2024 - Applicability to BIU V6 confirmed - QN-75509-C8H8V1
30 May 2024 - New guidance introduced to clarify that BREEAM compliance should not compromise the operation of building safety-critical systems. Applicability to NC V6 standards confirmed.

Flood resilience – Third party feature acting as flood defences - KBCN1022

There are many landscape feature defences, owned by third parties, which due to their location act as a flood defence by default, e.g. motorway, railway embankments, walls etc. It can be assumed that such embankments will remain in place for the lifetime of the development, unless the assessor or project team have reason to believe otherwise. For walls, assurance must be sought that the wall is likely to remain for the design life of the building.

Flood risk – Site situated across numerous flood zones - KBCN0532

Where a site is situated across more than one flood zone, the flood zone with the highest probability of flooding, i.e. the worst case scenario, must be considered for the purpose of the BREEAM assessment. An exception to this would be where the areas in the higher probability zone include only soft landscaping and it can be demonstrated that access to the building will be maintained in a flooding event. This is to ensure that the site has adequately managed the worst case scenario level of flood risk associated with the site's location. 
22/07/2022 Applicability to HQM One confirmed
07/03/2018 Updated to include circumstances where an exception may apply.

Flood Risk Assessment older than five years - KBCN1744

This sentence appears in the definition of 'Flood Risk Assessment': Where more than five years have passed since the FRA was carried out, evidence would be required to demonstrate that the basis of the FRA has not changed in that time. The requirement for evidence that the basis of the FRA has not changed where more than five years have passed is applicable only at Design Stage. It is not required at Post Construction Stage where a compliant FRA was undertaken at Design Stage and the development was carried out in accordance with that design.

Flow control devices – combining flow control - KBCN1034

Flow control devices are not required for each individual fitting and may control one or more WC area, such as adjacent male and female toilets within a core. However, when using a single device to control the supply to multiple areas, the strategy must account for the occupancy and function of each space, to ensure that the aim of the criterion is met. Combining multiple cores with varying occupancy using a single flow control device has the risk that faults in infrequently used sanitary facilities could continue to leak undetected.

Flow control devices – Use of devices on individual sanitary fittings - KBCN1550

The intent of the requirement for flow control devices is to minimise the impact of undetected wastage and leaks from sanitary fittings and supply pipework. The use of flow control devices on individual sanitary fittings alone does not, therefore, fully meet this aim.

Flow control devices for multiple blocks - KBCN1186

The criteria are set to encourage isolation of the water supply to each WC block when it is not being used. If a single flow control device, for example one programmed time controller, is adequate to switch the water on at predetermined times that suit the usage patterns of more than one WC blocks or facilities, this can be used to demonstrate compliance. Please note that if only one timed controller is used for a large area/number of facilities, the assessor must justify that this is appropriate to the usage patterns within the building and confirm that multiple timers would be redundant (i.e. they would all be set to the same time).  Consideration should be given of any facilities that may be open longer than others, requiring these timers to be programmed differently in different areas. As long as the aim of the credit (‘to reduce the impact of water leaks that may otherwise go undetected’) can be achieved through the specification of an appropriate number of flow control devices, the credit may still be achieved if timers cover more than one WC area/facility to prevent minor water leaks.
14 Apr 2023 - Applicability to BIU V6 Commercial confirmed.

Flow control devices on rainwater supply for toilets - KBCN0868

Flow control devices will be required on water supplied from rainwater and serving the toilet facilities. Rainwater tanks are topped up by mains water and leaks could reduce levels of stored water and hence increase the use of mains water. The leak detection requirements apply to all relevant water systems, regardless of the water source.

Flow control devices – Prison cells - KBCN1709

Flow control devices in WC areas or facilities are not required in residential areas of long-term residential accommodation. This can be applied to prison cells with ensuite facilities on the basis that they are long-term residential accommodation. It does not apply to holding cells, other short-term accommodation, staff areas or other non-residential areas of a cell block.

Flow rate for a mixture of taps - KBCN0173

Whichever is the higher of the 'average flow rate' or the 'proportionate flow rate' should be used within the Wat 01 Calculator.  

Flow restrictors - KBCN0976

If a flow restrictor is demonstrated to effectively reduce the flow of water and it is integral to the fitting or supply pipework (i.e. not easily removed by the building occupant), this can be accounted for in the calculations for this issue. These must be proprietary flow restrictors and fit for purpose. Partly closed isolation valves, for example, are not an acceptable solution.
19 Oct 2026 Wording updated to clarify.

Formaldehyde E1 emissions requirements – Untreated solid wood - KBCN1881

Testing for formaldehyde is not required for untreated solid wood where no formaldehyde containing binders, resins, adhesives, coatings, or chemical treatments have been used in the processing or manufacture. In such cases, a formaldehyde emissions test report is not required. However, the assessor must obtain confirmation from the manufacturer/supplier that:

Freestanding commercial fridges and freezers - KBCN0577

Freestanding commercial fridges and freezers must be included in the assessment of the Pol 01 issue, even when they are not connected to the building cooling system. Only domestic white goods are excluded from the assessment of this issue.

FSC and PEFC Mixed Sources certified timber - KBCN00091

Products labelled: Meet the BREEAM responsible sourcing requirements. This means any such products: Products carrying the FSC Mix label contain at least 70% FSC certified and recycled material. These products may contain a small proportion of FSC Controlled Wood (KBCN00054). However for BREEAM compliance, the FSC Mix label is sufficient to meet our requirements.
30-Oct-2025 - Applicable to HQM V6 and UKNCR V6.1
14-Mar-2024 - Wording clarified and expanded. Relevant prerequisites and requirements clarified. Scheme applicability updated.

FSC Controlled Wood - KBCN00054

The FSC Controlled Wood label minimises the risk that wood comes from illegal or controversial sources, however it does not eliminate this risk. Therefore, products which are: Do not meet the BREEAM definition of responsibly sourced. Where FSC Mix labelled products contain FSC Controlled Wood, see KBCN00091. This means that any such products:
30-Oct-2025 - Applicable to HQM V6 and UKNCR V6.1
14-Mar-2024 - Wording clarified and expanded. Relevant prerequisites and requirements clarified. Scheme applicability updated.

Future transport nodes - KBCN0966

Where a transport node is currently inactive but will become active soon after project completion, it can be included when calculating the existing AI. To demonstrate this, confirmation of the start of service date and service frequency from the appropriate public transport authority or company will be required.

Glare control – adjacent buildings - KBCN1211

It is acceptable to account for surrounding buildings, structures or other permanent environmental features when using simulation modelling to assess the risk of glare, provided this accounts for both direct sunlight and reflected glare from glazing or reflective surfaces.

Glare control – residential institution and multi-residential bedrooms - KBCN0666

Assuming that occupants are generally elsewhere during daylight hours, lighting and resultant glare are not considered to be problematic for bedrooms in residential institution and multi-residential assessments. The only exception to this is where designated additional office working space is provided. In these circumstances it is the role of the assessor to determine if individual spaces should be determined as 'relevant building areas' in accordance with guidance provided. Glare control criteria apply to building areas where lighting and resultant glare could be problematic for users.

Glare control – use of tinted windows - KBCN0862

Solar control or 'tinted' glazing could potentially support the attainment of this requirement. However, the assessor must be satisfied and provide evidence to demonstrate that the particular glazing type, when used on the assessed building for a given location, is meeting this overarching aim of preventing disabling glare. It should be noted that whilst certain types of glazing, such as low emissivity glazing, may be slightly tinted, they may not necessarily be effective in reducing disabling glare. For facades receiving direct sunlight, tinted windows alone are unlikely to be sufficient in the majority of situations.
21-Jul-2026 - Merged identical content from KBCN1090 [now deleted] to avoid duplication

Glare control for roof lights - KBCN0319

Where roof lights are present, they must be considered when demonstrating that the glare control strategy provides adequate control/measures for minimising glare in that space. All sources of glare need to be considered when designing out the potential for disabling glare.

Glare control in residential areas - KBCN00040

Glare control criteria apply to building areas such as study bedrooms or facility management offices, where work or study will be carried out and where glare would hinder such activities. It does not apply to other residential areas.  

Glare control – Modelling - KBCN1800

The ‘Glare control’ criteria do not require a specific methodology to be used to identify areas at risk of glare, and in most situations, a simple solar path analysis would be suitable. Alternatively, detailed hourly modelling methods, such as DGP and ASE, may be more appropriate. However, in either case, compliance cannot be assumed. Regardless of the methodology used, the modelling must be supported by robust reporting to demonstrate that each aspect of the criteria has been met.

Head-end systems for smart meters - KBCN0933

As the central component in an Advanced Metering Infrastructure (AMI), head end systems allow data communication and collation from a large and disparate set of smart meters. Where smart energy meters and sub-meters are to be installed, a head-end system is required for any strategy utilising this technology to be considered for compliance.

Impact of refrigerant – Refrigerants with low GWP - KBCN1472

Where systems only use refrigerants with GWP ≤ 10 The Pol 01 calculator does not have to be completed. Providing evidence of the compliant systems and refrigerants used is enough to award maximum credits for impact of refrigerant. Mix of systems with GWPs below and above 10 The Pol 01 calculator does have to be completed. The calculator must include systems with GWP ≤ 10 to ensure credits are based on the average value across all systems.
20-Dec-2023 Updated to include scenarios where there is a mix of systems with GWP above and below 10.

Individual and shared drying facilities in larger developments - KBCN0260

Individual bedrooms: an adequate internal or external space with posts and footings, or fixings capable of holding: This is to avoid over-provision of shared drying facilities in larger developments. 

Indoor air quality plan – later consideration - KBCN1544

Where BREEAM has been engaged at a later stage in the project (for instance, at the beginning of a Post-Construction Assessment) the IAQ plan must still be produced. The late stage plan must clearly identify opportunities to improve indoor air quality that: The plan is focused on decisions and actions that can still be practically carried out. The indoor air quality plan is an on-going consideration that extends into the operational life of the asset.

Indoor air quality plan – pre-requisite – no link to later performance - KBCN1541

The indoor air quality plan is a pre-requisite to achieving other credits in Hea 02. However, achieving the pre-requisite does not depend on achieving the other credits in the issue: The pre-requisite requirement is only for a compliant indoor air quality plan to be written.
17-Nov-2022 Wording clarified.

Indoor air quality plan – scope - KBCN0294

Where possible, the indoor air quality plan must cover all items in the criteria. This means the plan must be completed for: Within these requirements, there is flexibility for the design team to use their professional judgement to determine what is appropriate to meet the criteria. Any exclusions must be clearly evidenced and justified. As the basis for effective asset management, the indoor air quality plan must be written in a consistent and comprehensive manner. The report must address relevant aspects as fully as possible within the scope of the development.
11-Oct-2022 Title updated for clarity. Wording clarified. Content merged with KBCN0556. Reference to KBCN1544 added. Scheme applicability updated.

Laboratory facilities not restricted to building type - KBCN1340

In order to allow buildings with appropriate laboratory facilities to assess the energy performance of their labs, all assessments containing laboratory space and containment areas will be able to assess Issue ‘Energy efficient laboratory systems’, even where the relevant technical manual confirms that the Issue is not applicable to this building type. The Issue remains not applicable to primary and secondary school buildings given the limited scale of their laboratories. Assessments registered prior to 1 July 2019 have the choice to follow the guidance as stated in the technical manual. They can exclude laboratories by responding negatively to the questions regarding laboratory facilities. For assessments registered after this date, all projects containing laboratories within the scope of the assessment should include the Issue in the assessment.

Land reclaimed from the sea - KBCN0558

Land reclaimed from the sea cannot be considered as previously developed land. It has not been occupied by a permanent structure and any associated fixed surface infrastructure (please refer to the Additional information section).

Landscape and Habitat Management Plan – SQE involvement - KBCN0564

Even if not stated explicitly, it is implied and expected that the Suitably Qualified Ecologist (SQE) does verify the content of the Landscape and Habitat Management Plan to ensure that it is consistent with the whole site ecological strategy.
19 Nov 2021 Applicability to UK NC2018 confirmed

LCC – LZC energy sources discounted - KBCN0606

When sufficient information can be provided to justify that LZC energy sources are not appropriate for the development, the LCC analysis, for those LZC sources, do not need to be included in the feasibility study. The feasibility study (covering all the areas required as stated in the manual) intends to demonstrate, to a reasonable level of certainty, that the chosen LZC is the most appropriate of all those available.

Leak detection – compliance principle – alternative technologies - KBCN1566

Where it can be demonstrated that alternative leak detection technologies can meet or exceed the capabilities of systems set out in the BREEAM guidance, subject to approval, these can also be considered compliant. It is the role of the Assessor and the project team to provide evidence and justification in a compliance principle query (see KBCN1555). The following alternative solutions are currently recognised:
06-Jul-2026 - Title updated for consistency. Scheme applicability updated. Principle also applied to refrigerant leak detection.

Leak detection – extent of responsibility - KBCN0688

For the credit to be awarded, all the pipework in a development that the owner/occupier has responsibility for must meet the leak detection criteria.  In situations where third party organisations place restrictions on the pipework that can be metered, the scope of works (and hence placement of a meter for the use of leak detection) will start immediately after this point.  For instance where the utility company's meter is placed midway between the boundary and the building, the scope of leak detection for BREEAM purposes will be between utility meter and the building, not to the boundary (as stated in the guidance). The scope of the BREEAM criteria is only on pipework that the owner/occupier has control over.

Leak detection – inseparable building and site boundary - KBCN0388

Where there is no distinction between the site boundary and the building; the utility meter being either located on the boundary or within the building, the leak detection criteria apply to the mains water supply within the building only. The BREEAM criteria apply to the pipework that the owner/occupier has responsibility for.  

Leak detection – recycled water use - KBCN0433

The leak detection requirements still apply to all relevant water systems where water recycling systems are specified for WCs and urinals. Recycled water should be considered as a valuable resource as it replaces potable water use and, in many instances, recycling systems will still incorporate a mains-water back up.    

Leak detection – system notification - KBCN0245

So long as the compliant system alerts the appropriate person to the leak so they are able to respond immediately, the assessor can judge if the aim of the issue is being met by a reliable, robust and fail-safe means of notification.
13-Jul-2026 - Title updated for consistency. Scheme applicability updated. Principle extended to refrigerant leak detection, allowing refrigerant leak detection systems to notify a person to initiate shutdown in line with this principle.
   

Leak detection – using a BMS - KBCN0439

A BMS can be used for leak detection if it can be shown that its integrated or add-on features meet all the requirements for a leak detection system.
07-Feb-2022 - Applicability to BIU V6C confirmed.
06-Jul-2026 - Scheme applicability updated, and applied also to refrigerant leak detection across all relevant schemes.

Leak detection between building and utilities meter - KBCN1116

For all pipework which is the responsibility of the building owner or occupier leak detection is generally required between the building and the utilities water meter. This requirement is applicable regardless of the length of the pipework. However, for campus type developments or those with multiple buildings on the same site served by common pipework, leak detection is required both within the building and externally for the length of pipework that exclusively serves that building. Where it can be demonstrated that it is not physically possible for a meter to be installed on the pipework outside the building, the requirement for leak detection between the building and the utilities meter can be considered not applicable, and the credit awarded based on the leak detection within the building.
02 Jul 2024 - Updated to account for campus type developments. Applicability to UK NC V6 and INC V6 confirmed.

Leak detection system based on pressure changes - KBCN0326

A system that uses pressure changes to detect leaks is not necessarily compliant. To be deemed compliant the leak detection system would need to monitor the refrigerant pressure and the operating conditions to address the problem of natural fluctuation.

Legally harvested and traded timber – Examples - KBCN0956

The following examples are considered compliant for BREEAM: Legally harvested:
  1. Evidence of compliance with the UK government Timber Procurement Policy (see here, timber bought inside the UK only)
  2. FSC, PEFC, SFI or GiB certification
  3. Evidence of compliance with the EUTR (timber bought inside the EU only)
  4. Risk assessment/due diligence documentation demonstrating a low risk of non-compliance with the ‘legally harvested’ requirements given in the manual.
Legally traded:
  1. Evidence of compliance with the UK government Timber Procurement Policy (see here, timber bought inside the UK only)
  2. FSC, PEFC, SFI or GiB certification
  3. Risk assessment/due diligence documentation demonstrating a low risk of non-compliance with the ‘legally traded’ requirements given in the manual.
04-Dec-2025 - Examples updated to include Grown in Britain (GiB) certification. Previous reference to 'CPET' clarified as 'UK government Timber Procurement Policy'.
KBCN applied more widely to all relevant scheme issues in BREEAM and HQM

Life cycle cost – Multiple assessments on the same site - KBCN000003

Where there are multiple assessments on a site and a single life cycle cost (LCC) plan will be carried out, it is acceptable to use this plan as evidence provided that the results of the LCC plan can be applied to all of the assessed buildings and therefore may have a positive influence on the material specification of such buildings. Where the design of some assessments differ to the extent that the LCC plan cannot reasonably be applied, a separate LCC plan is necessary to achieve credits for this issue. Where multiple assessments are covered under a single LCC plan, there must be sufficient detail for each building to enable them to be adequately assessed. 

Lifts with speeds 0.15m/s or less - KBCN1146

Lifts with speeds 0.15m/s or less fall outside the scope of ISO 25745 and can, therefore, be excluded from the assessment of this Issue. This applies, for example, to lifts in single dwellings or those installed in other low-rise buildings, specifically for the use of persons with impaired mobility.

Low or no ecological value to manage and maintain - KBCN1383

The purpose of the criteria is to recognise projects that are positively contributing to local ecological value by managing and protecting it as part of the site being assessed. If there is no ecological value to maintain or manage on the site, the purpose of the criteria is not being met and credits cannot be awarded by default. For sites with low ecological value to begin with, the criteria encourage projects to consider ways to create ecological features that support local biodiversity as part of the development (e.g. habitat creation as part of the ecology issues focused on ecological enhancement).
30-Oct-2025 - Applicable to HQM V6 and UKNCR V6.1

LZC feasibility study – timing - KBCN1052

If a feasibility study is undertaken at a stage later than Concept Design, this must include an explanation for any local LZC technologies ruled out because of constraints arising from the late consideration. Compliance may still be achieved if other LZCs are feasible and the criteria are met. If the late completion of the feasibility study resulted in no LZC being installed, the credit must be withheld.  

LZC technologies – energy centre or other LZCs connected at a later stage - KBCN0267

If a project specifies LZCs that have been proposed in the feasibility report which reduce emissions, and/or will be connected to a site-wide energy centre operational at a later stage of the phased development, after the Post Construction Stage review has been submitted, the Energy and Pollution issues can be assessed as follows: In a phased development where the primary heating system will be upgraded at a later stage than the building being assessed, a commitment to install the new heating source must be made in the General Contract Specification (as per the BREEAM requirements). BREEAM does not specify a particular time for phasing as it is difficult to set parameters, however as a rule building users should have to wait the least time possible before they can use the upgraded heating source. For the quality audit, two Energy model outputs/EPCs must be produced at the final stage - one with the actual interim system installed for building control, and one for the BREEAM assessment which can include the predicted energy from the proposed energy centre.  Additionally, the legally binding general contract specification for the new heating source must be submitted with details of the timescales proposed for the completion of the second phase of work. Where this approach is to be followed BREEAM must be consulted in each case to ensure that the arrangements are sufficiently robust to award the credits. BREEAM seeks to recognise the environmental impacts of a building's energy use throughout its life, therefore temporary arrangements can be accommodated, provided there is robust evidence on future connection to the permanent systems.
24/08/2022 - Applicability to UKNC V6 confirmed

LZC technologies – planning conditions and restrictions - KBCN0535

Where a mandatory planning condition exists (eg to attach to a District Heating Scheme), this will clearly affect the number of options available in a feasibility study. In such cases, compliance can still be achieved where evidence on the planning condition restrictions is provided, and it is clarified how this excludes other technologies from being considered. The feasibility study will still need to be carried out to cover the remaining energy needs of the building (eg Electrical and lighting load in the case of a district heating scheme).  

LZC technologies – shell only feasibility study - KBCN0409

For a shell only project, compliance may be assessed on the built form only i.e. demonstrating that sufficient space and clearance for the installation of future LZCs has been considered, the built form is suitably sited, and that massing and orientation are optimised for the future systems.

Majority of water demand from rainwater harvesting - KBCN0860

If the majority of water use is supplied by sources other than mains or private water, for example rainwater harvesting, and this use will be monitored, additional metering of the smaller water demand that is masked by the larger demand is not necessary.

Manual watering - KBCN0553

Where the design team can justify that manual watering provides a reduction in unregulated water consumption, this can be considered as an acceptable method for reducing unregulated water use.

Measuring the flow rate of domestic components - KBCN0641

On site testing can be carried out by an appropriate professional to determine the flow rate and capacity of domestic components. This must be overseen by the client’s facilities manager and as-built drawings must be provided to confirm the presence and location of the components and any flow restrictors. Note that the conditions under which the testing is completed must be recorded, e.g. the pressure and the temperature of the water for taps. The assessor could conduct the test provided they are able to carry it out accurately.
15/02/2021: amended to cover all component types.

Metering recycled water - KBCN0658

Water-consuming plant or building areas consuming 10% or more of the building’s total water demand need to be sub-metered. This applies to recycled water, such as rainwater, grey water or process water as well as mains water. The aim of the Issue is to encourage reductions in water consumption, which is beneficial, regardless of its source. Monitoring the use of recycled water, may also help to reinforce the benefits of doing so and encourage further reductions.

Minimising watercourse pollution – Green roofs - KBCN1026

Rain that falls onto the surface of green roofs can contribute to this requirement. Evidence,however, still needs to demonstrate that the 5mm rainfall from all impermeable surfaces on-site is being dealt with.

Multi-Residential: Internal recyclable waste container if waste is sorted off site - KBCN0354

Where the Local Authority or waste management company for the scheme provide evidence confirming that recyclable waste will be sorted after they have collected it from site, it is acceptable to provide one internal storage bin of a minimum capacity of 30 L rather than 3 separate internal bins. The relevant recycling scheme must collect at least 3 of the following materials; paper, cardboard, glass, plastics, metals or textiles.    

Multi-residential: Waste storage shared by more than six bedrooms - KBCN0856

Where multi-residential buildings contain communal facilities shared by more than six bedrooms, the requirement for total waste storage can be increased on a pro-rata basis to demonstrate compliance. For instance, if the standard requirement is 30L for six bedrooms, this equates to 5L per bedroom. Where assessing a flat with eight bedrooms, this requirement increases to 40L (8 x 5L). The minimum size of individual containers remains unchanged as per the criteria.

Multiple assets on a wider site - KBCN1065

For one or more buildings / units assessed as part of a wider site or campus, compliance can be demonstrated through either: In all cases the waste storage solution must have the capacity to accommodate the recyclable waste material generated from all buildings and their activities.
30-Mar-2026 - Added text to align with KBCN0696. Scheme applicability updated.
26-Mar-2018 - Published.

Multiple buildings on the same site - KBCN0559

The areas of hard landscaping and boundary protection that need to be assessed on a site that contains several developments/buildings depends on the scope of works and scope of the assessment(s) being undertaken. Essentially, the areas that need to be assessed are all the areas of hard landscaping (as defined within the relevant definitions of the credit issue) and boundary protection within the construction zone (again defined within the relevant definitions) that are within the scope of works of the building under assessment. Therefore, if all buildings on one site are being assessed in one BREEAM assessment, then the hard landscaping and boundary protection related to all of these building's scope of works will need to be assessed. If there are several buildings with individual assessments and their own defined scope of works, then the hard landscaping and boundary protection applicable to the scope of works of each individual building will be assessed for each associated assessment. The assessment is concerned with the hard landscaping and boundary protection associated to the project under assessment, i.e. the areas under the control of the project under assessment. 

Multiple developments monitoring construction waste on a site - KBCN00036

Where the same contractor is working on a site with more than one development, a single Site Waste Management Plan (SWMP)/Resource Management Plan (RMP) can be produced to demonstrate compliance, if it can be justified that separation of the waste would be impractical. Where the developments are of a similar nature, such as all new-build or all refurbishment with similar scope, the results from the whole development can be apportioned on the basis of floor area to derive the figures upon which the separate developments will be assessed. Where the buildings are not similar, the design team will need to provide calculations to demonstrate that the waste has been apportioned as accurately as possible according to the project types.
21/11/16 Clarification added in relation to dissimilar projects on the same site.

New build extension using existing lifts - KBCN0444

Where the assessment is only of a new build extension (and not the existing building), lifts present in the existing building fall outside the scope of Ene 06 and do not need to be assessed. The applies only when the lifts are not being renewed or undergoing a major refurbishment.

New EU energy labels - KBCN1445

Background

In recent years, the market for domestic-scale appliances has seen excellent progress, with increasingly energy-efficient products becoming widely available. Consequently, the A-rated category was extended over time to include A+, A++, and A+++ ratings. Meanwhile, the lower ratings, such as E, F and G have become increasingly rare. It was clear that an adjustment to a new, simpler set of ratings was required.

Statutory Changes

From 1st March 2021, the European Commission requires new, updated energy labels of A to G for dishwashers, washing machines, fridges and electronic displays. Lamps will require the new ratings from 1st September 2021 and requirements for re-labelling tumble dryers are yet to be confirmed. This means:

Changes for BREEAM and HQM

As a result of the introduction of the new EU ratings and in order to maintain the original intent of the BREEAM criteria, the approach for our schemes has had to change. It is not possible to establish direct equivalence between the old and new energy labels, therefore the updated approach will be to recognise the best-performing 25% of each appliance type, based on a comprehensive market sample. The table below shows how this translates into the new EU Energy Labels for different appliance types.

Appliance type

Rating required

Fridges, fridge-freezers, freezers
E
Washing machines
B
Dishwashers
D
Washer-dryers
D - D
  This approach will ensure that BREEAM continues to drive the energy efficiency of appliances by demonstrating a meaningful reduction in energy consumption. Note that these new requirements will be reviewed from time to time and may be subject to change. Where assessments have already specified (and can procure) products bearing the old labels, it is acceptable to follow the previous criteria. However, where products bear the new label and for all assessments registered after 31/05/2021, the new criteria must be met.  
17 Apr 2023 - Applicability to NC2013 confirmed.
21 Mar 2022 - Confirmation added that washer-dryers require a D rating for both cycles
23 Nov 2021 - Reference to 'freezers' added to appliance types
12 May 2021 - Guidance updated and applicability to HQM One and BREEAM NOR confirmed

No data for AI at Design Stage - KBCN0551

If there is insufficient data for a future transport service to include this in the calculation of the AI at the Design Stage, it should not be accounted for. If at Post Construction stage the data is available, this can be incorporated. Whilst certain Design Stage requirements can be based on commitments to achieve a certain performance, this must be based on verifiable data.
16/04/18 Wording amended to clarify that this applies to future services and to allow applicability to UK NC 2018
 

No external plant specified - KBCN0931

Where there is no external plant specified and the acoustician confirms that there is no significant noise source, it is acceptable for the acoustician to provide a formal statement in lieu of the noise impact assessment. All other evidence for this issue must be provided as listed in the Evidence table. The formal statement should be produced by a 'suitably qualified acoustician' (as defined in the Relevant Definitions for this issue) and should justify this approach with reference to the specific internal plant to be installed and the proximity of any noise sensitive areas or buildings. The statement must explain clearly how the aim of the issue is being met.
08 Jan 2026 - Applicability to UK RFO 2014 and IRFO 2015 removed - the issue is filtered out where no external plant.

Not enough rows in the Pol 01 calculator - KBCN1274

If additional rows are required in the calculator, it is acceptable to add the specification of multiple models together in one tool, provided they are the same model and have all the same inputs for columns F to M. The weighting of the systems across the building is done by the System Capacity and Total Refrigerant Charge (columns E and F), so you would multiply each of these two figures by the total number of the system specified. This gives the contribution of the systems to the building's cooling capacity and charge. If further rows are still required please submit a query using the webform in BREEAM Projects, attaching a copy of the tool and specify the number of additional rows required.
08/10/21 link to webform added

Occupancy calculation – Buildings with shift patterns - KBCN0431

In buildings with shift patterns, as shifts may overlap, the building users calculation should be based on the maximum occupancy of the building at any given time.

Occupancy rates – 24-hours consulting or treatment rooms - KBCN1258

The default occupancy rate for 24-hour consulting or treatment areas in hospitals and care homes is 0.07.
Published pending reissue of the technical manual UKNC2014/REISSUE UKNC2018/REISSUE
03.11.2021 Issue 2.0 of the UK RFO technical manual amended.

Occupant control – BMS and degree of control - KBCN0175

A Building Management System controlled set point with local override controls limited to a set range would satisfy the occupant control requirement so long as the temperature range available to building users is confirmed as appropriate for the building type and user profile.

Occupant control – spaces requiring user controls - KBCN0170

This guidance is intended to clarify the types of area for which user controls are required or would be considered beneficial. Zoning is required in all areas of the asset where specified in the assessment criteria. Please refer to the specific requirements of the applicable BREEAM standard to interpret this guidance appropriately. User controls required Spaces where users are expected to have independent control over their environment. User controls not required Spaces where users are not expected to have independent control over their environment.
14-Dec-2022 - KBCN applicability updated to include BIU. Wording clarified, and amended for compatibility with BIU criteria.

Off-site waste sorting / no dedicated on-site waste storage - KBCN0696

BREEAM assesses the dedicated space for recyclable waste storage, assessing the asset's physical design and layout without relying on management practices that are subject to change. However, we recognise that in specific cases this is not always possible. Accepted scenarios for off-site waste management Requirements and evidence - NC, RFO and BIU Commercial Using an off-site waste sorting approach must still meet all other relevant assessment criteria for the relevant scheme. This includes:
Requirements  Evidence
Waste stream segregation - If recycling is separated: a minimum of three operational waste streams are segregated using clearly identifiable and labelled containers or bags. - If recycling is mixed: show evidence that the waste is later separated into identifiable recyclable streams. Confirm: - Number of waste streams and collection arrangements. - Post-collection segregation (where applicable). - An on-going waste recycling contract.
Operational waste management - Internal waste storage arrangements, defined on-street collection points and scheduled collection times collectively fulfil the functional role of an operational waste management facility. - Storage arrangements must be suitable for the waste streams generated and be durable, hygienic, and clearly labelled. A waste management plan which: - Outlines how the waste is managed and stored between collections. - Shows interim storage is adequately sized based on the frequency of collection.
Accessibility - Waste storage and transfer arrangements must be reasonably accessible to relevant asset users and allow for safe preparation of waste for collection. - Relevant drawings or documentation.
Compliance for all points above must be demonstrated on a case-by-case basis, and the assessor is responsible for confirming that the intent of the issue — facilitating optimal reuse and recycling of operational waste — is achieved. Additional clarification for BIU Commercial V6 Rsc 02 This BIU issue further segregates operational waste into recyclable waste, construction waste, and reusable construction products.
30-Mar-2026 – Approach updated to clarify and expand on acceptable scenarios where off-site waste collection is accepted. Scheme applicability updated.
22-Jan-2025 - Updated text to allow for permanent external spaces, aligning with KBCN1716. Scheme applicability updated.
18-Nov-2024 - Requirements for BIU projects clarified relating to all answers in Rsc 02. Title clarified.
09-Feb-2024 - Requirements clarified. Applicability updated to include construction waste storage for BIU V6 Rsc 02.
17-Jan-2024 - Scheme applicability updated.
16-Apr-2018 - Wording clarified.

Office equipment – mobile devices - KBCN00041

Mobile devices such as smartphones and tablets, which are generally used without connection to an electrical power source, should be excluded from the assessment of the energy efficient equipment issue. Devices which are not generally connected to an electrical power source when used are excluded from the 'office equipment' definition as they do not directly affect the unregulated energy consumption of the building.    

On site fabrication - KBCN1292

Where concrete (or another construction product) is produced on site, there is no requirement to provide responsible sourcing certification for the end product. As in this case fabrication on site is effectively part of the onsite building process, the certification of the individual products (e.g. aggregates, cement), as delivered to site, shall be used in the assessment instead.

On-demand public bus services - KBCN1404

These can be recognised as follows: This is limited to genuine on-demand bus services, which are operated as public transport with multiple pick-up and drop-off points and does not extend to private hire, taxi or other similar operations. 

On-site LZC – whole site shared connection - KBCN1424

To be recognised in BREEAM, the on-site Low and Zero Carbon (LZC) technology must have a direct physical connection to the assessed asset. OR Where the LZC technology is; It is acceptable to allocate the renewable energy generated proportionally as a calculation of the asset's predicted energy consumption compared to the total energy consumption of the whole site. To allocate renewable electricity by proportional consumption: Where consumption data is missing, renewable electricity must not be allocated to the assessed asset. In this case, it is assumed that all electricity consumed is sourced from the grid.
17-Jan-2024 - Applicability BIU V6 Ene 13 removed, as this approach is not applicable to assessing the area of PV fitted.
21-Dec-2022 - Applicability to In-Use V6 confirmed.
24-Aug-2022 - Applicability to UKNC V6 confirmed.

Only lifts in building are for persons with impaired mobility - KBCN1330

Where the only lifts, escalators or moving walkways in the assessed development are for persons with imparied mobility with speeds no greater than 0.15m/s, and there are no lifts which fall within the scope of the criteria, the Issue should be filtered out of the assessment. Credits cannot be awarded by default.

Operational waste – Additional requirements for multi-residential buildings with individual bedrooms and communal facilities only - KBCN1519

These criteria are intended for situations where occupants of individual rooms have access to shared kitchens, which can be used to prepare food, regardless of whether central catering is also available. In developments where all catering is managed centrally and no communal/shared kitchens are provided, these requirements do not apply. If, for example, catering is managed centrally, but there are small satellite kitchens for staff to sort/reheat food for residents, the assessor must justify whether and to what extent recyclable waste will be generated in these kitchens and demonstrate that adequate recyclable waste storage provided as appropriate.

Operational waste facility – extension of definition – compliance principle - KBCN1716

The original intent in BREEAM was that an operational waste facility is a centralised, on-site permanent enclosed structure or dedicated internal space in the asset. However, this approach is not always suitable for all asset types. Compliance principle The definition of operational waste facility is expanded to include dedicated external spaces. The principles for operational waste facilities are that they: The table below shows how the original principles are adapted for dedicated external spaces. BIU V6 Commercial only This compliance principle also applies to the storage of:
Principle Compliance principle
Dedicated and permanent. This space can be a dedicated and permanent external space.
Adequately sized and equipped. External spaces must still meet relevant requirements for size, required waste processing equipment and water outlets for composting. Where the asset contains multiple tenants or user groups with different needs, the waste facility can be multiple spaces, provided all of them meet the criteria. The minimum size calculation requirement is based on the combined area of all waste facilities.
Appropriate access and accessibility. The external space must meet requirements for size and access for all relevant users and vehicles, Any external spaces must also be adequately lit through a permanent lighting solution that is fit for purpose. Compliance for this could be shown through meeting criteria in other issues relating to external lighting.
Easy to find. As well as permanent signs, external spaces can be marked out through permanent ground markings, bollards, or other permanent features.
Minimises disruption. Any external facilities must: -       Minimise light pollution and disruptive glare to neighbours, if the space is lit at night. -       Minimise any contamination and air quality issues arising from waste stored. -       Minimise disruptive noise during operation. Justification and, where relevant, evidence of mitigation measures must be provided to show how these principles are being met. Evidence from other relevant assessment issues can be used.
04-Nov-2025 – Applicable to BREEAM NOR NC 2016 and V6
   

Operational waste requirement for catering – applicability - KBCN1162

The additional operational waste storage requirement for developments which include catering is generally only applicable where a commercial scale kitchen is present. Where the design team can justify that there will be no significant waste streams from a modest facility, such as a small cafe, selling only drinks and pre-prepared snacks, the additional waste storage area identified in the default values does not need to be provided to meet compliance.
21-Jan-2026 Applied to NC V6 and V7 standards

Operational waste storage sizing - KBCN0560

The dedicated space requirements given in the technical manual are default guidance, for situations where it is not possible to demonstrate the required size based on known waste streams. Compliance can, therefore, be achieved provided that it is clearly demonstrated and evidenced that there is adequate justification for the type of facilities & size of waste storage provided, and that the assessor is satisfied that the sizes and facilities meet the criteria based on the building type, occupancy and the likely waste volumes generated as a result of these.

Park and Ride Schemes - KBCN0754

'Park and ride' bus services run from one or more car parks to a city centre or other destination to allow travellers to park their car at a convenient location and complete their journey by bus. These generally stop at transport nodes en route to allow passengers to board or alight. Provided the service meets the aim of the Issue with reference to the guidance, they can be considered for this Issue in the same way as any other bus service.

Passive design analysis – Modelling the standard building when existing building elements are retained - KBCN1270

In circumstances where an existing building element (e.g. a facade) is being retained it is acceptable to incorporate them into the modelling of the 'standard building' baseline, for the purpose of undertaking passive design analysis. All other building elements should be modelled with fabric performance equivalent to that of the local Building Regulations Notional Building (or for Scotland, an equivalent compliant building) and without the passive design measures (where feasible i.e. building orientation is likely to be fixed).


PMV and PPD reporting for mixed mode ventilation buildings - KBCN0632

When assessing buildings where both naturally ventilated and air conditioned spaces are included, reporting the PMV and PPD indices is required.

Point of use water heaters - KBCN0773

Small 'point of use' water heaters can be excluded from the sub-metering requirements. Only major energy consuming systems that have a measurable impact on the operational energy consumption need to be included.

Post construction noise level testing - KBCN00043

Noise level measurements do not need to be taken at the post construction stage if the acoustician has accurately modelled the noise level from the plant, using manufacturer's literature, and site measurements taken at the design stage. Any attenuation measures specified by the acoustician in their report must be confirmed as being present post construction. If the acoustician has been unable to model the noise level accurately, post construction measurements are needed to demonstrate compliance. Calculations and recommendations from the acoustician are relied on to be accurate and in keeping with best practice; attenuation measures are assumed to be specified and installed correctly.   

Post-construction measurement – formaldehyde / VOC levels exceed limits - KBCN0258

If the measured formaldehyde / VOC concentrations were above the prescribed limits, the appropriate remedial action must be taken, as described in the IAQ Plan. The criterion requires confirmation of 'the measures that have or will be undertaken' however it does not specifically address re-testing. We would expect, however that the IAQ Plan should outline what remedial measures are appropriate depending upon the severity and type of the non-compliance with prescribed limits. Such measures may include re-testing as a matter of 'best practice'. Where levels are found to exceed these limits, the project team confirms the measures that have, or will be undertaken in accordance with the IAQ plan, to reduce the TVOC and formaldehyde levels to within the above limits.
10-Oct-2022 - Title amended to align with standard KBCN naming format for clarity and consistency. Made applicable to UK and International NC V6.

Post-construction measurement – sampling methodology and KPIs - KBCN0380

When testing for VOCs post-completion and pre-occupancy, a representative sample of the building needs to be carried out. Each sample TVOC and formaldehyde measurement needs to achieve the threshold levels individually, either in the initial testing or after remedial measures have been implemented. This ensures that all tested areas of the building are below the limits, and that areas of non-compliance are not ‘averaged out’. 'When providing KPI test results for air quality post-construction / pre-occupancy within scoring and reporting tool, where the limits are exceeded and remediation and re-testing are carried out, the figure should be an average for the whole building post-remediation, as this is the key figure that reflects the building at its certified state'. Where testing is not a requirement of the IAQ Plan and this is not carried out, the original testing figures should be entered and the assessment report should provide details of the remediation measures undertaken to reduce these to within the prescribed limits.
10-Oct-2022 Title amended to align with standard KBCN naming format for clarity and consistency. Scheme applicability updated.
06-Dec-2017 Amended to account for situations where re-testing is not required by the IAQ Plan.

Prediction of operational energy consumption – Multiple (similar) buildings assessments - KBCN1479

Sampling is not appropriate to meet the aim of the criteria; it is necessary to model the predicted operational energy consumption of all assessed units. Credits are awarded for undertaking the detailed modelling, therefore there is no requirement to identify the worst performing unit and KNCN1382 is not applicable.
24/08/2022 - Applicability to UKNC V6 confirmed

Presence detection – illuminated signs - KBCN1671

The requirements for presence detection do not apply to illuminated signs. In BIU V6, presence detection requirements are included as part of automatic energy saving controls. All other requirements in this criteria must still be met.

Previously developed land – temporary structures - KBCN0659

The presence of concrete and hardstanding areas established as temporary structures for enabling works are not considered to be previously developed land on a site. The nature of enabling works are temporary; with the purpose of enabling the delivery of a development and are not constructed to be permanent. Temporary structures of this kind are not included in the definition of previously developed land no matter how long they have been present on a site.

Previously occupied land – Fixed surface infrastructure - KBCN1140

Car parks and other hard-landscaped areas often incorporate small pockets of soft landscaping. Where these are integral to the hard landscaping and constitute a small proportion of the total area, these areas can be considered as part of the fixed surface infrastructure.

Previously occupied land – multi-use games areas (MUGAs) - KBCN1464

For education assessments, playing fields are considered previously occupied land if an equivalent area of playing field is reinstated on land of low ecological value within one year of completing the construction works. Multi-use games areas (MUGA) or similar are also acceptable as replacements for playing fields.

Previously occupied land – multiple assessed buildings - KBCN1093

For sites with multiple assessed buildings, where it is not possible to clearly define separate development footprints for each building, the assessment can be done on a site-wide basis. In this approach, the boundary of the development footprint is considered to be the whole site. This overall result is used to assess compliance for each included BREEAM assessment.
20-Oct-2022 Title amended for clarity. Wording clarified. Scheme applicability updated.

Process water to offset potable water demand - KBCN0586

Where it is demonstrated that it is safe to do so, process water resulting from the building under assessment, can be considered for off-setting potable water demand from components that would otherwise be supplied using potable water, when in line with the criteria requirements for greywater systems. Process water resulting from the building under assessment can be considered as a form of greywater for the purposes of off-setting potable water demand.
21 Dec 2021 Additional wording added, requiring it to be demonstrated that process water is safe to use and KBCN applied to BIU standards.

Protecting vulnerable parts of the building from damage – underground car parks - KBCN1331

Exposed elements, such as columns in an underground car park, should have been designed against structural damage from minor vehicle collision and, therefore, do not require any additional protection to meet compliance for this BREEAM Issue. Assessors should, however, consider whether additional protection is required at the vehicular entrance to underground car parks. The requirements are intended to address the issue of damage to vulnerable parts of the facade, which would require repair/replacement in the event of minor vehicular collisions.

Public transport information system – requirements - KBCN1244

This transport measure requires the provision of a ‘system’, installed in a suitable location, which displays up-to-date information on local public transport systems. This could include a ‘real time’ display or other innovative system which allows building users to plan their travel on a daily basis, based on current transport information. The provision of paper timetables or a notice board cannot be considered compliant for this transport measure. Solutions which rely on smartphone ownership cannot be considered compliant. Whilst smartphone use is widespread, it is not universal, therefore such solutions cannot be considered as meeting the needs of all potential building users.
1st Sep 2023 - Note added regarding smartphone-based solutions.
5th March 2021 - Wording updated to clarify the intent.

Recognised emission certification schemes – Publicly available databases - KBCN1887

Some of the emission certification schemes recognised within GN22 maintain publicly available databases of products certified against their scheme requirements. These databases can be used to help assessors and project teams identify products that are certified under recognised schemes. Examples include: EU Ecolabel – https://environmental-data.ec.europa.eu/ecolabel/index.html GREENGUARD – https://spot.ul.com/ Indoor Advantage – https://www.scsglobalservices.com/certified-green-products-guide Nordic Swan – https://www.svanen.se/en/search-for-ecolabelled-products-and-services/?sortorder=6&producttype=0&qry=&productgroup= Blue Angel – https://www.blauer-engel.de/en eco-INSTITUT – https://www.eco-institut-label.de/en/ M1 – https://ymparisto.rakennustieto.fi/rakennusmateriaalien-paastoluokitus-etsi-m1-luokiteltuja-tuotteita Indoor Air Comfort® / Indoor Air Comfort Gold® – https://www.eurofins.com/iac-certified   Please be aware that these databases may include products that are certified under a recognised scheme, but which fall outside the product categories, BREEAM performance level, or the approved certification level recognised in GN22. Assessors must, therefore, verify that the certification scheme and product category are recognised within GN22 and applicable to the product being assessed. Please also refer to KBCN0719 - GN22 Recognised schemes for emissions from construction products

Recyclable, general and organic waste storage – space, labelling and segregation - KBCN1577

Strategies may vary according to the specifics of each project, their waste streams and collection arrangements. The aim of these requirements is to encourage recycling, ensuring that it is correctly sorted and to prevent cross-contamination of waste streams. Label the recycling area This is required to alert building users and collection agencies to the location of the recycling facility. Label each recyclable waste stream This can be done by labelling the bins or their dedicated space within the recycling facility, or both. Mixed recycling bins and / or spaces are clearly labelled with their constituent waste streams. General or organic waste have their own dedicated spaces Sufficient space for general and, where relevant, organic waste is required in addition to meeting the requirements for recyclable waste. This does not have to be within a separate facility, but if combined with recyclable waste storage, there is greater risk of cross-contamination. The following requirements apply in this situation: If provision of waste bins is out of scope Where the provision of waste bins is outside the scope of the developer, it is clearly not possible to label the bins. In this situation, the following compliance options are available:
21-May-2024 - Link to KBCN0696 removed. Merged with KBCN1380. Minor clarification added on mixed recycling.

Regenerative drives – requirement for specification - KBCN1253

Requirements for the specification of a regenerative drive for lift installations are subject to an analysis of resultant energy savings. However, where it can be demonstrated that this is not financially viable, accounting for payback over the service life of the installation, this option can be discounted. Please also refer to other scheme-specific guidance relating to this requirement.

Relating green roofs to multiple assessments in the same building - KBCN1195

A green roof on top of such buildings can be used to award credits for each assessment for which the Land use and ecology Issues apply. The benefit can be applied to to all assessments undertaken for the building provided all are completed within the appropriate time-frame of a valid ecological survey.
30-Oct-2025 - Applicable to HQM V6 and UKNCR V6.1

Remedial works – timing of acoustic re-testing - KBCN1164

The intent of CN "Remedial works" is that, where these are required, re-testing is carried out prior to handover and occupation. However, it is permissible to carry out the re-testing post-occupation. This is provided any specific guidance for particular building types related test conditions have been met (for instance, it may be that some building specific guidance requires furniture or carpets to not be present during the testing). Compliance cannot be achieved based on a letter from the SQA confirming that the contractor has followed their advice to achieve the required performance.
07.11.18 KBCN amended to allow for re-testing to be carried-out post-handover.

Responsible construction management – corporate registration - KBCN1084

Where credits are awarded for the assessment of the site against a compliant scheme, corporate registration, which assesses the contractor's overall operations and performance across multiple sites, is not in itself recognised. To award considerate construction credits, BREEAM requires the assessment of the specific assessed development, in line with the criteria

Responsible construction practices – Multiple contractors on the same project - KBCN0352

It is the site that must comply with BREEAM issues rather than any individual contractor. Several different contractors may have obligations to meet compliance criteria. One of the contractors and/or site managers may have responsibility for ensuring compliance during site operations. It is ultimately the client/project team's responsibility to determine and demonstrate compliance.

Responsible sourcing certification – validity - KBCN1693

Where it can be demonstrated that the responsible sourcing certificates were valid either at the time of specification, or at the time of purchase, they may contribute to the awarding of the credits. BREEAM is primarily trying to encourage designers to take responsible sourcing into consideration when specifying or selecting products and as such it is not necessary for certification to be valid at the time of design or post-construction stage submissions.
30-Oct-2025 - Applicable to HQM V6 and UKNCR V6.1

Reused in situ – Definition - KBCN1902

A material qualifies as reused in situ where it meets all of the following:   Exclusion Materials that remain in their original location and application throughout the works, including where they undergo minor processing such as cleaning, repair or redecoration, are considered as retained. These must be excluded from the Mat 03 calculator.
KBCN Reinstated 24-Sep-2026

Reversible heat pump (VRF) providing both heating and cooling - KBCN0735

Where a reversible heat pump, which provides heating and cooling on reverse cycle with heat recovery, is used, the cooling capacity only should be used for the Direct Effect Life Cycle CO2e emissions (DELC) calculation. The cooling capacity of heat humps is normally less than the heating capacity, so compliance against the criteria will be based on the more challenging DELC value calculated.

RGB LED lighting - KBCN0986

RGB LED lighting must be assessed against the average external lighting efficacy benchmark. The current criteria do not completely rule out the use of RGB LED lighting as it can potentially be combined with other types of external lighting to meet the average efficacy benchmark.

Risk to Ecologist’s safety - KBCN0704

In some situations a significant safety risk may prevent a suitably qualified ecologist from attending the site to undertake a site survey. In these cases a desktop study can be used to demonstrate compliance, where the ecologist confirms that it is an acceptably robust substitute. In these cases, the assessor must provide evidence to confirm the type of significant safety risk present.
30-Oct-2025 - Applicable to HQM V6 and UKNCR V6.1

Role of the SQE in planning and measures on-site - KBCN1372

The main role of the Suitably Qualified Ecologist for 'planning and measures on-site' is to make recommendations in their Preliminary Ecological Appraisal. It is important that these are incorporated into the project’s scheduling, management and resources and that ultimately, they are implemented in practice. The person coordinating this does not need to be the SQE, as long as this individual has the appropriate level of authority to take the relevant actions and the methodology is followed. At post-construction stage, evidence needs to demonstrate these measures are implemented in practice, through site visits and appropriate evidence. In some cases, the SQE may need to be involved themselves in checking their recommendations are implemented for certain measures, if they consider this is required. However, if this is required, it would be up to the SQE to confirm in their Preliminary Ecological Appraisal.  

Safe pedestrian routes – Definition, measurement and verification - KBCN0238

Definition Safe pedestrian routes include pavements and safe crossing points, which may be controlled or, for example, be identified by tactile paving, a crossing island or a dropped kerb. An element of judgement may be required, in which case justification should be provided. Measurement Distances could be measured, for example, along a pavement, across a road at a safe crossing point and along the pavement on the other side.  The distance should not be measured diagonally across a road, following the most direct route. Verification The assessor’s site inspection is an important aspect of the assessment and may help to confirm that all relevant information is current and can include photographs of any key areas. This can also help to identify safe crossing points or hazards which may not be apparent from a desktop study. Alternatively, web-based map data may be used to satisfy the evidence requirements at both Design and Post-Construction Stage, provided that the assessor is satisfied that this clearly demonstrates compliance and that the evidence is robust and up to date. Where web-based navigation maps (e.g. Google Maps/Street View) are used as evidence, this must include: • Dated and marked-up site plan or a web-based navigation map viewer highlighting: • Current location and type of transport nodes and local amenities. • Current route and distance from the building via a safe pedestrian route. • Plan or map scale. When relying on web-based evidence for post-construction stage, the assessor must, additionally, provide verification that the information provided for the nodes/amenities is still accurate and up to date.  
16 Sep 2025 - Wording relating to verification updated to clarify the intent.
29 Aug 2025 - Approach to web-based map data at post-construction stage updated and related wording amended accordingly
07 Mar 2024 - No changes have been made. This appears as 'updated' due to an administrative error.
11 Jan 2024 - Wording re-structured for clarity
19 Dec 2023 - Applicability to BIU V6 confirmed

Sanitary fittings used in religious practices – updated - KBCN1624

Such fittings should not be included in the scope of this Issue. Please refer also to KBCN0418 This guidance relates to fittings and facilities used in some religious practices, for example, for washing before prayer.
03 Nov 2023 - Updated. Previous guidance was incorrect and contradicted the approach outlined in KBCN0418

Scope of energy efficient cold storage - KBCN00029

Technical guidance The intent of the following wording in the technical manuals is to exclude self-contained refrigeration units. NC 2018 Ene 05: “The scope of this issue covers freezer or cold storage rooms which are integral to the building and served by the building’s own refrigeration systems.” NC 2016 Ene 05: "If the building contains no refrigeration systems or only refrigeration systems which stand-alone, i.e. are not integral to the building and served by the building services, this issue is not applicable to the assessment. Clarification The scope of this issue covers freezer or cold storage rooms which are integral to the building, and includes cooling systems that require commissioning and optimisation for the specific requirements of the cold storage space. This applies whether the cold storage space has a dedicated cooling system serving this space, or one which is connected to wider building cooling services. "Kitchen and catering facilities", are excluded from this issue. They refer to commercial-sized, but self-contained, off-the-shelf units - these include large freezers, fridges, or stand-alone self-contained walk-in cold storage units. These types of units are manufactured as a self-contained product, and contain their own integral cooling systems - they operate according to manufacturer pre-sets, and do not require commissioning of the cooling system. For this reason, these are not assessed under this issue, but they may still fall within the scope of the 'Energy efficient equipment' issue. The guidance will be clarified in future reissues or updates of the technical manuals.
22-Feb-22 Wording clarified.
02-Jun-17 Wording clarified.
02-Dec-16 Wording clarified - no change to approach.

Scope of issue – clarification – fixed installations - KBCN1660

The scope of this issue covers noise from external building services (or 'fixed installations' as written in the manual) serving areas designed for human comfort. The noise impact assessment excludes:

Scope of the criteria for lifts – Small service lifts (dumbwaiters) - KBCN1589

Small service lifts, of the type typically used to transport prepared food and crockery in restaurants (sometimes referred to as 'dumbwaiters'), fall outside the scope of this assessment issue.

Scope of the refrigerant leak detection system - KBCN0530

The refrigerant leak detection system is required to cover any part of the plant or pipework which contains refrigerant.
21/08/17 KBCN amended to include pipework containing refrigerant.

Security lighting - KBCN0915

The criteria generally apply to all external lighting, including security lighting. However, due to specific security requirements, there may be situations where a particular aspect of the criteria cannot be met, as they would compromise the development's security. For example, the use of PIR sensors may not be appropriate in high security developments, where continuous night-time CCTV surveillance is required. In such cases, where this is justified by the security consultant or other appropriate member of the design team, compliance can demonstrated for the security lighting by meeting all other relevant criteria. BREEAM does not seek to not impose requirements which could potentially compromise the development’s security strategy
10.03.2020 - KBCN amended following review. It has been determined that the criteria for this Issue must be applied to all security lighting, except as described above. KBCN no longer applicable to UK NC2011 as there is no criterion relating to PIR in this scheme.

Security lighting - KBCN1029

Light fittings specified to comply with specific security standards, but which conflict with the BREEAM criteria, can be excluded from the assessment of this issue. The assessor must obtain evidence confirming the specific security standards and that they are applicable to the assessed development.

Self-contained dwellings / bedrooms with shared facilities – mixed recycling - KBCN1664

Where there is mixed recycling, the number of recyclables containers can be reduced to match the final waste streams being collected. For example, the standard BREEAM requirement is three recyclables containers per dwelling / communal facility. The total combined storage volume requirements are the same as stated in the manuals. To apply this KBCN, the project team must provide evidence to QA of the waste collection policies that apply to the asset.

Self-contained dwellings or units with individual utility meters - KBCN0199

Where self-contained dwellings or units covered by the assessment have their own individual energy supply and utility meter (e.g. water, gas or electricity), this supply can be excluded from the scope of the issue. All shared energy supplies and common areas under the responsibility of building management are still included in the assessment. For example, if self-contained flats in an assisted living development have individual gas supplies with their own utility meter, this supply will be excluded from the assessment. However, the lighting and small power comes from a shared distribution board on each floor, in which case this shared supply will need to be sub-metered in accordance with the criteria. This same principle applies to scenarios involving speculative industrial or retail units with capped services, where these units have their own utility meter.
12/09/2018 Applicable to Water Monitoring Issue where appropriate
27/09/2017 The word 'units' added to include a wider range of scenarios falling under this principle.
17/06/2022 Added other industrial / retail situations for further clarity on the applicability of this KBCN.
 

Shared ecological enhancements - KBCN0656

A site-wide approach to ecological enhancements can be used on sites where multiple buildings share areas of soft landscaping. The enhancement benefits are applied to the individual building assessments within the site. Similarly, where a building comprises more than one assessment, eg different floor assessments, a green roof on top of that building can be used to award credits for each assessment for which the Land use and ecology issues apply. The benefit can be applied on a site-wide basis provided all developments are completed within the appropriate timeframe of a valid ecological survey.    

Shower with multiple shower heads - KBCN0855

To calculate the water use of a shower with more than one shower head, one of the following should be done:
22 Feb 2024 - Applied to BIU, BREEAM NC and RFO standards

Showers and taps where use is physically time-limited – Calculating flow rates - KBCN1690

Where a timer is used to physically limit the use of showers or taps within a set period of time, this can be used as the basis for calculating a reduced flow rate. For example, where use is limited to 2 minutes, 4 times per hour, for a shower or tap with a flow rate of 8 l/minute, the flow rate can be calculated as follows: 8l/minute x 8 minutes/hour = 64 l/hour = 1.07 l/minute

Single function area and no separately tenanted areas – operational energy monitoring - KBCN00056

Where an asset has: AND AND Provided that the sub-metering by end-use credit is achieved, the sub-metering of ‘high energy load and tenanted areas’ credit can be awarded by default.
12-Aug-2025 - Title and wording clarified.
26-Mar-2024 - Wording clarified. Scheme applicability updated.

Site wide approach to ecological enhancements - KBCN1194

A site-wide approach to ecological enhancements can be used on sites where multiple buildings share areas of soft landscaping. The enhancement benefits are applied to the individual building assessments within the site. The benefit can be applied on a site-wide basis provided all developments are completed within the appropriate timeframe of a valid ecological survey.
16-Apr-2026 - Applicable to NC V7
30-Oct-2025 - Applicable to HQM V6 and UKNCR V6.1

Space heating as major energy use - KBCN0939

Where possible, space heating should always be considered as a major energy use for sub-metering purposes. Where space heating cannot be separated from hot water, this must be fully justified by the design team at QA. See KBCN0329: Combined system for space heating/cooling and domestic hot water. Where electric space heating is used, this in itself cannot be used as justification for combining the space heating along with lighting and small power unless there is a clear justification for doing so. See KBCN00068: Combined sub-metering of electric heating and small power equipment.

Specialist assisted baths in care homes - KBCN0228

Specialist assisted baths in care homes or similar specialist applications can be excluded from the assessment of this issue. Due to the specific access and care needs of users, it may not be possible to reduce the volume of specialist assisted baths.  

Speculative ceiling finishes – Substantial alterations - KBCN1141

The aim of this Issue is to avoid the unnecessary waste of materials, therefore the installation and subsequent removal of speculative finishes should not be permitted. However, BREEAM recognises that incoming tenants may need to adapt ceiling finishes to suit the requirements of their fit-out. Therefore, where ceiling finishes are installed throughout, in line with Criterion 2, the following applies: A tenancy agreement, applied to the first tenancy, should stipulate that ceiling finishes may only be modified where necessary, for example, to accommodate new partitions, lighting or other services, to replace worn or damaged components or to replace small, localised areas with a specialist ceiling to account for abnormal conditions, such as wet areas.

Speculative office including floor finishes/suspended ceiling - KBCN0259

The requirements can still be met where a speculative development includes the installation of floor finishes/suspended ceilings provided a Lease Agreement will be implemented to confirm that tenants are not permitted to remove these finishes. BREEAM recognises that incoming tenants may need to adapt ceiling or floor finishes to suit the requirements of their fit-out. Therefore, where these finishes are installed throughout, in line with Criterion 2, the following applies: A tenancy agreement, applied to the first tenancy, should stipulate that floor or ceiling finishes may only be modified where necessary, for example, to accommodate new partitions, lighting or other services, to replace worn or damaged components or to replace small, localised areas with a specialist floor or ceiling to account for abnormal conditions, such as wet areas. Documentary evidence of this must be provided as evidence for the credit to be awarded.
04-Nov-2025 – Applicable to BREEAM NOR NC V6
18/04/2017 KBCN made applicable to NC 2016 and IRFO 2015  
05/07/2018 Paragraph added to clarify the requirements of the tenancy agreement
27 Jul 2021 Clarified that the terms of paragraph 2 apply also to floor finishes

Stakeholder consultation – Existing shared facilities - KBCN0360

The consultation must include any existing shared facilities relied on to achieve compliance as well as the new facilities. To ensure the shared existing facilities are appropriate and in line with the users' requirements.  

Studio Bedroom Daylighting Calculations - KBCN0733

Where studio rooms in multi-residential projects include multiple area types (e.g. A kitchen and lounge area), compliance can be achieved where either: 1. The entire studio room meets the more onerous requirements or 2. The room is nominally divided into the relevant spaces and the requirements are applied to each as appropriate.

Sub-metering at least 90% of each fuel - KBCN0657

In a scenario whereby several energy consuming systems are not sub-metered because they account for less than 10% of the annual energy consumption (see Ene 02 methodology), and this results in less than 90% of the estimated annual energy consumption of that fuel being metered, the M&E consultant should review the metering strategy and advise which of these energy consuming systems would most benefit from sub-metering to make up the 90%. This may be based on which of the energy consuming systems has the highest annual energy consumption, or which has the most potential for reducing energy consumption as a result of sub-metering. This will not necessarily have to mean that the energy consuming systems chosen have to have their own sub-meter, the M&E consultant may decide they would most benefit from metering alongside another consuming system. However ultimately 90% of each fuel must be metered. Justification should be given within the metering strategy and the BREEAM assessment report as to which lower energy consuming systems were chosen to be sub-metered to make up the 90%, and how this was done to best suit the development (i.e. individual sub-meters or paired with another consuming system).

Sub-metering by calculation - KBCN0700

For simple sub-metering strategies, it is acceptable to calculate a single end-use by subtraction of known, sub-metered end-uses from the relevant main utility meter reading. For more complex strategies, where a BMS/BEMS is used, the software should be capable of calculating and displaying all required end-uses in line with the criteria.

Sub-metering technologies – Compliance Principle - KBCN1561

Where it can be demonstrated that alternative sub-metering technologies can meet or exceed the capabilities of systems set out in the BREEAM guidance, subject to approval, these can also be considered compliant. It is the role of the Assessor and the project team to provide evidence and justification in a compliance principle query (see KBCN1555). The following metering standards or technologies are currently recognised as alternatives to pulsed output meters:

Sub-metering using non-intrusive load monitoring (NILM) systems - KBCN1710

Non-intrusive load monitoring (NILM) systems cannot be used to demonstrate compliance for the sub-metering credits within BREEAM. Hardware-based sub-meters must be installed. NILM systems are generally retrofit systems which can be easily removed and are not integral to the building or installed building services.

Surface water run-off – discharge to a tidal estuary or the sea - KBCN1023

The peak rate of run-off and volume run-off criteria can be deemed to be met if the site discharges rainwater directly to a tidal estuary or the sea. The site run-off must discharge directly into the tidal estuary or the sea. Typically, drainage pipes would only carry run-off from the site and would not need to cross privately owned land outside the boundary of the development before reaching the sea. A definition of tidal estuary is in the technical manual.

Surface water run-off – Highways and impermeable areas - KBCN1035

Where new non-adoptable highways are built, all new impermeable surfaces must be included in the calculations to demonstrate compliance with the peak rate of run-off and volume of run-off criteria. Where buildings are built beside existing highways or where adoptable highways are built, the impermeable area of the highway does not need to be included in the calculations.

Sustainable transport measures – Shell only and shell & core assessments - KBCN1181

Assessment option 3 “Public transport information system” A public transport information system may not be in the scope of works for a shell only or shell & core assessment. In such cases, this measure is not available, however points can be achieved through demonstrating compliance with alternative options in this issue. If it does fall within the scope of works, this measure is still available. Assessment option 4 “Electric Vehicle recharging stations” For shell only and shell & core assessments it is permissible to demonstrate compliance through provision of all necessary infrastructure required for future installation of compliant electric recharging stations. BREEAM recognises that full installation of recharging terminals may be outside the scope of shell only and shell & core stages. Assessment option 5 “Car Sharing” For speculative shell only and shell & core assessments, measures 5.7 and 5.8 might not be achievable. Where this is demonstrated and justified, the one point available for this option can be achieved through compliance with measures 5.9 & 5.10 only. Where the building occupier is not known, project teams are unable to influence the implementation phase of a car sharing scheme.
26/06/2020 Note relating to Option 3 - wording amended to clarify the intent.

Temporary power solutions in noise impact assessments - KBCN0171

Plants such as standby generators that are only used temporarily are excluded from the noise impact assessment.

Thermal comfort – Changing rooms - KBCN1133

Whilst thermal comfort in changing rooms may be considered as significant, such spaces are, generally, outside the scope of this Issue, as they would not fall within the definition of an 'occupied space'.
17/06/2019 - This supersedes the advice previously provided in this KBCN, which was published in error on 13/06/2018

Thermal modelling for large scale projects - KBCN1171

In cases where the scale of the project makes it unfeasible to provide thermal modelling for every space, it is acceptable to demonstrate compliance with a representative sample of floors or rooms, ensuring any worst case scenarios are included.

Thermal modelling for shell only developments - KBCN0784

For shell only developments, in order to achieve criterion 1, thermal modelling can be completed on the basis of a typical notional layout and equipment specification for the particular building type (retail, restaurants, cinema etc.) can be used to demonstrate compliance.
04-Nov-2025 – Applicable to BREEAM NOR NC V6 - N/A to BREEAM NOR NC2016

Timing of Ecological survey/report - KBCN0292

If the ecologist's site survey and/or report is completed at a later stage than required, the assessor would need to be satisfied that it was produced early enough for the recommendations to influence the Concept Design/design brief stage and leads to a positive outcome in terms of protection and enhancement of site ecology.
30-Oct-2025 - Applicable to all HQM versions and UKNCR V6.1
21/02/2017 Wording clarified.

Towel rails - KBCN00081

Towel rails cannot count towards the drying line requirements. Clothes drying lines are provided to reduce the need to tumble drying clothes, which uses a lot of energy. Using towel rails to dry clothes would require the potentially damp towels to be stored while the clothes dry. This is inconvenient and therefore means the aim of the credit is less likely to be met. 

Transport assessments and transport statements - KBCN1367

For many projects, a Transport Assessment or Transport Statement will be required for planning purposes. Where this is the case, this information can be used to demonstrate compliance with the requirement to undertake a site-specific transport/travel assessment. Where a Transport Assessment or Transport Statement is not specifically required for planning purposes, a site-specific transport/travel assessment must be completed that covers points a to g in criterion 2. In such instances, it is permissible for the results of this assessment to be reported within the travel plan rather than in a separate report. The applicable information must be clearly identifiable within the travel plan document, and the travel plan must clearly demonstrate how the transport/travel assessment has been used to inform the plan’s strategy.    

Transportation analysis carried out by the lift manufacturer - KBCN0232

BREEAM recognises that lift manufacturers / suppliers are often engaged to provide such specialist advice. Where the assessor is satisfied that the analysis has been carried out correctly, the analysis can be submitted as compliant evidence.

Untreated buildings - KBCN1030

Buildings designed to be untreated, i.e. where internal spaces will not be serviced by heating, ventilation or air-conditioning systems and therefore have no noise generating plant will not assess this issue. An example of such a building could be for industrial warehouse storage.

Urinals – calculation of litres/bowl/hour - KBCN1010

A flushing frequency of two flushes per hour is used in the Wat 01 tool and should be applied when calculating the volume of water dispensed by urinals and compared against the water efficient consumption levels by component type for the Wat 01 issue. This method should be applied to calculate litres/bowl/hour. For example, a 13.5 L cistern feeding 3 bowls which is flushed 2 times per hour: (13.5 L / 3 bowls) x 2 times an hour = 9 litres/bowl/h.  

Using water from natural underground sources to offset water consumption - KBCN00094

Water from natural underground sources (for instance aquifer water accessed via boreholes) cannot be used to offset: A significant amount of water used for public consumption is already drawn from aquifers. Private boreholes may be drawing water from the same sources as public utility companies.
29-Jul-2025 - Applied to Issue Wat 04
27-Mar-2024 - Title and text updated to broaden definition. Scheme applicability updated.

Ventilation – e-cigarettes - KBCN1014

The use of e-cigarettes and vaporizers is considered equivalent to smoking. A smoking ban must also include a ban on e-cigarettes and vaporizers.
11-Oct-2022 - Scheme applicability updated.
   

Ventilation – external requirement for window opening restrictors - KBCN1032

Opening restrictors to windows may sometimes need to be installed to meet: Where such external requirements are in force, these requirements cannot be used as a mitigating factor for meeting the BREEAM ventilation criteria. Even with window restrictors, adequate ventilation can still be achieved.
19-Oct-2022 Wording and title clarified. Scheme applicability updated.

Ventilation – Single room MVHRs - KBCN1042

Single room mechanical ventilation heat recovery units do not need to show that the air intake and exhaust are a suitable distance apart. However, the air intakes of these units must be located to minimise intake of other potential external pollutants.
11-Oct-2022 - Title amended for clarity and consistency. Wording simplified. Scheme applicability updated.

Verification of an ecology report / information - KBCN1192

If the appointed ecologist does not meet the definition of a ‘suitably qualified ecologist’ (SQE) the report / information submitted to support the assessment must be verified by an individual who does. 1. The individual verifying the report must provide written confirmation that they comply with the definition of a ‘suitably qualified ecologist’. 2. The verifier must provide signed confirmation that they have checked and approved the report. This must clearly reference the report and can be in the form of a signed letter or their printed name and signature on a completed pro-forma. In doing so, they are deemed to confirm that the report: a. represents sound industry practice b. is correctly, truthful, and objective c. is appropriate given the local site conditions and scope of works proposed d. avoids invalid, biased, or exaggerated statements Such confirmation from the verifier must be provided in addition to all other information required by the relevant technical manual and referenced as part of the evidence submitted to demonstrate compliance. It can take a number of years for an ecologist to meet the SQE definition. Verification of information by an existing SQE supports the practical application of the assessment criteria and is in line with industry practice.
30-Oct-2025 - Applicable to HQM One, HQM V6 and UKNCR V6.1
13-Aug-2019 Updated to clarify, in practical terms, what evidence of verification will be considered acceptable.
 

Verification of measurements undertaken by non-SQA - KBCN1661

It is acceptable for individuals who do not meet the BREEAM definition of a suitably qualified acoustician (SQA) for Pol 05 to undertake the testing for this issue, provided the measurements or calculations are verified by a SQA. The SQA must review the report and confirm in writing that they have found it to:
  1. Represent sound industry practice
  2. Be appropriate given the building being assessed and scope of works proposed
  3. Avoid invalid, biased and exaggerated recommendations
Additionally, written confirmation from the SQA how they comply with the definition of a SQA is required.

View out – Bedrooms in Residential and Residential institutions - KBCN1798

The 'View out' criteria are generally not applicable to bedrooms in assessments of Residential and Residential institutions (long-term stay and short-term stay), where the occupants are likely to be elsewhere during the daylight hours. Although a multi-purpose desk or work surface may often be provided in bedrooms for short-term working, study and other uses, this would not normally be considered as a dedicated workspace. An exception to this would be where a separate dedicated office or study space is provided, for example within a bedroom suite. Please also refer to any building-type-specific guidance, as bedrooms in sheltered housing, for example, may be considered differently. It is the role of the assessor to determine whether individual spaces should be determined as ‘relevant building areas’ in accordance with guidance provided.

View out – eye level - KBCN0581

BREEAM defines an adequate view out as being at seated eye level (1.2 – 1.3m) within the relevant building areas. However, where occupants will not have the option to be seated, for example in some industrial operational areas where the work being undertaken requires occupants to remain standing, the height of the view out can be changed accordingly to suit the eye level of occupants. All other view out requirements have to be met and clear justification provided for changing the height/level of the view out. In some relevant building areas, occupants may not be sitting down to undertake tasks. Allowing the view out height requirements to be changed accordingly ensures building occupants gain maximum benefit from the view out.   

View Out – First Aid Rooms - KBCN1104

The view out criteria do not apply to dedicated first aid or medical rooms in non-healthcare projects. BREEAM recognises the need for user privacy in such areas and that these are intermittently occupied.

View out – No relevant areas - KBCN0876

If the scope of the assessment does not include any relevant building areas, as defined within the manual, the criteria for 'view out' can be considered as met by default. Only spaces that fall within the definition of relevant areas and are within the assessment's scope need to be assessed.

View out – percentage area - KBCN0166

For the view out credit, compliance must be demonstrated for the percentage of the floor area in each relevant building area, rather than the percentage of the total relevant building area in the building.
09-Oct-2025 - Applicability to NC V6 standards confirmed.
14-Feb-2017 Wording amended to clarify that the percentage must be achieved for each 'relevant building area'.

View out – rooms used for security or other critical functions - KBCN1040

The View out criteria are not applicable to rooms containing security or critical systems or sensitive material, such as CCTV monitoring rooms. Where it can be demonstrated that the presence of compliant windows would compromise a critical function of the space, the criteria can be considered not applicable.
19-Feb-2025 - Scheme applicability updated.
06-Mar-2018 - Published.

View out – Shell only/Shell & Core - KBCN1354

Where it is not possible to confirm which areas of the building will contain workstations/benches or desks, then all areas of the building designed for and/or likely to be occupied by workstations/benches or desks must comply with the relevant criteria.

View out for commercial kitchens - KBCN1216

It is not necessary to provide a view out for commercial kitchens. This is because in such a space it is likely that kitchen staff will move around, doing various tasks. This makes the requirements for the view out to rest the eyes unnecessary.

VOC credit issues – Clarification of scope - KBCN1797

The scope of these requirements does not include furnishings or moveable furniture, e.g. desks, seats or shelving. It includes fixtures and fittings that are integral to the building, such as kitchen units and toilet cubicles. However, bespoke fixtures, such as purpose-made items of fixed furniture, can be excluded, as the specified compliance testing is not appropriate for such items.

Washer dryers - KBCN0699

Where a washer dryer is specified, the water consumption figure for the wash and dry cycle should be used. The drying cycle of a washer dryer is taken into account because it usually uses water during this drying process (e.g. for cooling during the drying cycle) and in some cases, this water usage can be significant.
18-Nov-2022 - Updated to apply to BREEAM In-Use Version 6

Washing machines and dishwashers – Water consumption data - KBCN1571

The water consumption data used to demonstrate compliance may be based on the lowest full wash cycle (i.e. not a pre-wash cycle, for example).

Waste from temporary structures - KBCN1038

Temporary support structures, or any other materials or systems brought on site to facilitate construction of a building and that subsequently enter the waste stream (albeit for recycling) will be considered as construction waste and contribute to the construction waste generated for the development. If the support structure is reused on another site by the contractor (or another contractor) it has not entered the waste stream and, therefore, would not be included in the figures for waste generated. Reused timber formwork would be excluded in the same way.

Waste storage provision for catering - KBCN0755

As the manual states, the additional 2m2 per 1000 m2 of waste storage area provided for catering is measured against the "net floor area where catering is provided" and NOT the floor area of the catering facility. Generally, a catering facility will serve building users throughout the building. If it can be demonstrated that this is not the case, for example if part of the development is subject to a separate tenancy, not served by the catering facility, the area calculation can be adjusted accordingly. Where the net floor area is not indicative of the actual occupancy, the default values may not be appropriate. In such cases, the predicted waste streams should be calculated based on the actual occupancy and waste streams generated. This requirement accounts for the increase in waste produced by building based on the likely number of building users served by the catering facility. Please note that these default calculations are only intended for use where it is not possible to determine accurately what provision should be made based on predicted waste streams. 
15 06 2017 Wording updated to clarify

Water consumption calculation for sensor taps - KBCN0180

The water flow rate of sensor taps can be entered directly into the flow rate cells of the Wat 01 tool. The amount of water dispensed by sensor taps for each use is determined by occupant demand in the same way as normal taps. Therefore, the default frequency of use will be applied in the Wat 01 tool and no adjustment calculation is needed for sensor taps.

Water fittings specification evidence at design stage - KBCN0420

For a design stage assessment, it is acceptable to provide data based on reasonable assumptions if the final specification of fittings is not yet available.

Water fittings used for a process related function - KBCN0418

Water fittings used for a process related function, e.g. low level ablution taps, laboratory / classroom taps, scrub-up taps, cleaners' sinks etc., should be excluded from the assessment of regulated water consumption. Only kitchen taps and those used for general hygiene washing are to be included in the assessment of regulated water consumption.
04/08/17 Added low level ablution taps (typically used for religious purposes) to exemptions.

Water monitoring when only part of a building is under assessment - KBCN0548

When only part of the building is under assessment, there are two cases for achieving compliance with the requirement to specify a water meter on the mains water supply of the building: If the whole building is under the same tenancy or ownership and management, then a meter monitoring the entire building is acceptable. However, if the floors subject to assessment are separately tenanted, then a meter at the point of entry to the assessed areas is required. Assessed areas have to be monitored separately for water consumption when only part of the building falls within the scope of assessment and where the assessed areas are separately tenanted.

Weather files – 50th percentile - KBCN0117

For the thermal simulation of climate change environments, where this not specified in the manuals, the 50th percentile weather file is used in all cases. This applies also to the use of any alternative weather files or formats which are not listed in the manual. See KBCN1182.
18-Dec-2024 - Title updated for clarity. Scheme applicability updated. Link to KBCN1182 added.

Weather files – alternative format or location - KBCN1182

If they achieve the aim of the credit, alternative weather file formats not listed in the manuals can be used instead of those referenced in the manual. Format - current climate The alternative weather files must include same variables as the specified weather files for each hour of the year e.g.: - Dry bulb & wet bulb temperature, - Wind speed & direction, - Solar altitude & azimuth, - Cloud cover etc. For example, TMY (Typical Meteorological Year) is an accepted alternative format for BREEAM, meeting the requirements above. The assessor or design team must verify this and ensure that meeting the BREEAM criteria does not become easier by using the alternative weather file. Format - projected climate These alternative files must be based on climate projections with equal or higher temperatures than those specified in the relevant criteria, setting an equally or more robust standard for overheating. Where there are no suitable weather files available for projected climate change, use any one of the following: To modify weather data for existing climates into the relevant future climate change scenarios required in the criteria. Alternative location Where the weather file for the nearest location for the project is not representative of the actual location’s climatic conditions, the project team can use the weather file from another nearby location which is more representative. This can take account of the climatic influences of altitude, prevailing wind, proximity to climate-moderating features, or heat island effect.
19-May-2025 - Added example alternative format. Added links to future climate change resources.
18-Dec-2024 - Merged with KBCN1013. Scheme applicability updated.

Zoning and control – Dimming - KBCN1018

Localised dimming controls installed in line with the criteria, along with a master on/off switch, can be considered as meeting the aim of the requirement for 'controls' in open plan offices. The aim is for occupants to have local control over their lighting and maintain comfortable lighting levels.

Zoning and control – PIR in circulation spaces - KBCN0332

PIR controls can be deemed compliant in circulation spaces such as corridors. In this instance 'separate occupant controls' are not required. The requirement for user control is so that the building users can have direct control over their immediate work environment to ensure it is suitable for their personal needs. In circulation spaces, occupancy is transient and PIR control in these spaces is acceptable.  

Zoning and occupant control – access to lighting controls - KBCN00032

The relevant areas for the criteria apply only to areas where users are expected to have control. For instance, this means that areas intended for the general public, or a shop floor would not be expected to have lighting controls. The general principle which applies to user access to general environmental controls (heating, cooling, ventilation) may also apply to access to lighting controls. See KBCN0170. However, the the exact approach may differ between the two types of systems and assessor judgement must be used to determine compliance. In all cases zoning is required in all areas of the asset where specified in the assessment criteria. Please refer to the specific requirements of the applicable BREEAM standard to interpret this guidance appropriately.
14-Dec-2022 - KBCN applicability updated to include BIU. Wording updated. Link to KBCN0170 created.

Zoning and occupant control – PIR detection systems - KBCN0335

The aim of the Health & Wellbeing category is to recognise ways to benefit occupants through giving them control of their lighting environment. Without manual overrides, presence or absence detection lighting controls (such as PIR detection systems) are not compliant with the criteria. BREEAM recognises the energy efficiency benefits of detection systems in buildings through the Energy category. In some cases, the design team may have to prioritise one particular lighting strategy to the detriment of achieving a credit elsewhere.
17 09 2024 Updated to apply to BIU Part 1 - Lighting Controls
28 04 2021 Wording amended to include absence detection systems.
18 09 2017 Wording amended to clarify the meaning.
 

Zoning and occupant control – whiteboards and display screens - KBCN1433

Whiteboards and display screens in dedicated teaching or presentation spaces require separate zoning and control for lighting, as specified in the criteria. Lighting around whiteboards and display screens which are typically found in general office areas, meeting rooms, or in other generic spaces do not require separate zoning and control to meet the criteria. In such cases, the assessor should provide justification. Whiteboards and display screens in dedicated teaching / presentation spaces are likely to be used frequently, and require appropriate zoning and control. An increasing number of offices and meeting rooms now include display screens - however separate zoning and control may not be appropriate.

Zoning and occupant controls – handheld remote controls - KBCN1243

Remote control light switches can be considered as compliant, on the basis that these are provided in sufficient numbers/locations to meet the aim of the criteria.